| Plan Review Notes For Permit 02080980 |
| Permit Number |
02080980 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-30 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE NOTE ONE FROM FIRST | | | REVIEW. PLEASE SUBMIT AIC RATING FOR | | | ALL NEW SERVICE EQUIPMENT. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE RISER DIAGRAM | | | NOW SHOWS EQUIPMENT GROUNDING CONDUCTORS | | | BETWEEN METER AND MAINS AND MAINS AND | | | PANELS.? PLEASE NOTE THERE ARE NO | | | EQUIPMENT GROUNDING CONDUCTORS BETWEEN | | | METER AND MAIN. THIS IS PARALLELING THE | | | NEUTRAL. PER 250-24. | | | | | | 3)NOTE: PLEASE INITIAL AND DATE ALL | | | HANDWRITTEN CHANGES ON PLANS BY AN | | | ARCH. FS/FAC 481.221. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|