Plan Review Notes
Plan Review Notes For Permit 02080980
Permit Number 02080980
Review Stop R
Sequence Number 1
Notes
Date Text
2002-09-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) ACTIVE LEAF OF FRONT EGRESS DOOR IS
 REQUIRED TO PROVIDE A CLEAR OPENING OF
 NOT LESS THAN 32"WIDE. FBC1012.1.1,
 1012.1.7 & 1012.1.8
  
 5) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR BBQ.
  
 6) SPECIFY THE SIZE OF THE ATTIC ACCESS
 OPENING ON THE PLANS.
  
 7) THE 14" FOOTING DEPTH INDICATED IN
 THE FOUNDATION SCHEDULE ON A2 IS NOT
 ADEQUATE. THE 2001 FBC REQUIRES THE
 BOTTOM OF FOOTINGS TO BE A MINIMUM A 12"
 BELOW GRADE AND THE CITY AMENDMENTS TO
 THE FBC REQUIRE FINISH FLOOR TO BE A
 MINIMUM OF 4" ABOVE GRADE AT HABITABLE
 AREAS. FBC 1804.1.3 AND CITY AMENDMENTS
 1804.1.7. PLEASE REVISE.
  
 8) THE FOUNDATION TYPE IS NOT SPECIFIED
 AT THE INTERIOR GARAGE WALL AND THE
 SHOWER FOR BATH #5.
  
 9) SPECIFY THE LENGTH/EMBEDMENT OF THE
 1/2" ANCHOR BOLTS FOR THE STEEL COLUMNS
 ON A6.
  
 10) PROVIDE A SECTION DETAIL OF THE
 FRONT ENTRY AREA.
  
 11) SPECIFY THE LENGTH/EMBEDMENT OF THE
 3/8" BOLTS, ATTACHING THE BUCKS FOR THE
 GARAGE DOOR ON DETAIL C ON A2.
  
 12) INDICATE THE CONNECTORS FOR THE TOP
 AND BOTTOM OF THE 4X4 WOOD POST.
  
 13) THE ROOF FRAMING PLAN LISTS AN A2
 ANCHOR FOR THE TRUSSES BETWEEN GARAGE
 AND FRONT ENTRY. THE UPLIFTS ON THE PLAN
 EXCEEDS THE VALUES FROM THE TRUSS ANCHOR
 SCHEDULE ON A3. PLEASE CORRECT.
  
 14) THE UPLIFT CAPACITIES OF THE ANCHORS
 LISTED FOR TRUSS ANCHORS D AND E ON A3
 CONTAIN ERRORS. THE RT24T WITH (18) 16D
 NAILS HAS UPLIFT VALUE OF 1565# AND THE
 TAPR216 WITH (11) 16D NAILS HAS AN
 UPLIFT VALUE OF 1485#. THERE IS ALSO A
 REDUCED VALUE WHEN USING MULTIPLE STRAPS
 INSTALLED CLOSER THAN 8" CENTER TO
 CENTER. SEE 2001 USP CATALOG. PLEASE
 REVISE.
  
 15) THE CONDITIONED SPACE SQUARE FOOTAGE
 ON THE ENERGY CALCS. IS DIFFERENT FROM
 THE LIVING AREA LISTED ON THE PLANS.
 PLEASE CORRECT.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS (THE ONE SUBMITTED
 IS FOR AN OXXO CONFIGURATION AND AN OXO
 CONFIG. IS INDICATED ON PLANS)
 - HORIZONTAL SLIDING WINDOWS (EXPIRED ON
 5-20-02 THE CONFIGURATION IS XO AND PLAN
 IS DIFFERENT, WIDTH OF WINDOW ON PLAN
 EXCEEDS PROD. APP.)
 - SERIES PW 701 FIXED WINDOW (EXPIRED ON
 5-20-02 AND SEVERAL FIXED GLASS WINDOWS
 ON PLAN EXCEED THE SIZE LIMITS OF PROD.
 APP.)
 - OVAL FIXED GLASS WINDOWS
 - ARCHED TOP FIXED GLASS WINDOWS
 - DOUBLE FRENCH DOOR WITH SIDELITES
 - GLASS BLOCK [ GLASS BLOCK AT MASTER
 BATH IS IN A HAZARDOUS LOCATION AND A
 MINIMUM UNIFORM FACE THICKNESS OF 0.25
 INCH IS REQUIRED PER FBC 2405.2.2(5)]
  
 17) SAFETY GLAZING IS REQUIRED IN FIXED
 AND OPERABLE PANELS WITH INDIVIDUAL
 PANES GREATER THAN 9 SQ FT, BOTTOM EDGE
 LESS THAN 18" ABOVE THE FLOOR, TOP EDGE
 GREATER THAN 36" ABOVE THE FLOOR AND
 WITHIN 36" OF A WALKING SURFACE PER
 FBC 2405.2.1(4). PLEASE INDICATE ON THE
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202