Plan Review Notes
Plan Review Notes For Permit 02080980
Permit Number 02080980
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-04 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 SERVICE EQUIPMENT BEING INSTALLED.
 ALL DISC`S/PANEL/BRKRS MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9/
 215-5
  
 2)NOTE: PLEASE NOTE MISSING SD OUTSIDE
 BEDROOMS #`S 3&4
  
 3)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52H/ OUTSIDE 3&4.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED BRANCH CIRCUITS PER 210-12
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. PLEASE SIZE PER 250-122
  
 6)NOTE: PLEASESHOW REQ`D GFI
 PROTECTION FOR WHIRLPOOL/SPA TUB. 680-70
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372