| Plan Review Notes For Permit 02080925 |
| Permit Number |
02080925 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-29 00:00:00 | ********** UNSAT ************ | | | | | | PLEASE NOTE, PLANS DO NOT CORRELATE. | | | TWO SEPARATE ELECTRICAL RISER DIAGRAMS | | | WERE SUBMITTED FOR REVIEW. | | | | | | PLEASE NOTE THAT NO MORETHAN 8' OF | | | UNPROTECTED CONDUCTORS INSIDE THE BLDG | | | PER LOCAL AMENDMENTS 230-70A | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|