| Plan Review Notes For Permit 02080921 |
| Permit Number |
02080921 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-07 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02080921 | | | ADD: *****LIBERTY BAY***** | | | ****MODEL B***** | | | CONT: HOME DYNAMICS CONSTRUCTION | | | TEL: (954)275-8569 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) SHEET A-1 NOTE: MONOLITHIC CONCRETE | | | FOUNDATION WITHOUT HOOK BARS DESIGNED BY | | | RATIONAL ANLYSIS ACI 318-89. | | | ACI 530.8.5.2 EMBEDDMENT LENGHT MIN 12" | | | | | | 2) PLANS INDICATE BEING DESIGNED TO | | | 130 MPH. THE CITY IS LOCATED IN A 140 | | | MPH WIND ZONE.SEE A-2 BUILDING DATA. | | | DESIGN NOTES, SEE WIND LOADS PER | | | CHAP. 6 SHOULD BE CHAP 16. | | | DESIGN NOTES, DESIGNED TO ASCE 7- | | | NO YEAR NOTED!!!!! | | | | | | 3) SHEET A-3 NAILING FOR ROOF SHEATHING | | | FOR MEAN ROOF HEIGHT <25' | | | ZONES 1 & 28D COMMON | | | 6" O.C. EDGES & 6" O.C. INTERMEDIATES | | | ZONE 38D COMMONS | | | 4" O.C. EDGES & 6" O.C. INTERMEDIATES | | | | | | 4) PROVIDE MISSING KEY PLAN FOR STORM | | | SHUTTER INSTALLATION SCHEDULE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|