Plan Review Notes
Plan Review Notes For Permit 02080900
Permit Number 02080900
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-06 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS: A)DESIGN PRESSURES ON
 SCHEDULE LIMITS THE SIZE OF PANELS.
 SEE PLANS FOR CALCULATED DESIGN PRE-
 SSURES AND REVISE AS REQUIRED.
 B)CLARIFY WHICH ANCHOR IS USED RAWL OR
 CAUL-IN.
 C)MARK ON DRAWINGS MOUNTING CONDITIONS &
 ANCHOR TYPE & SPACING USED.
  
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR W/ SINGLE SIDELITE ASSEMBLY AS
 SHOWN ON PLANS.
 3-PROVIDE UL SPECS FOR ONE HR FIRE RATED
 GLASS BLOCK ASSEMBLY REQ'D BY TABLE
 600 FBC 2001.
 **PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 GLASS BLOCK.
 **SAFETY GLASS BLOCK REQUIRED IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 4-FOUNDATION PLAN AND FOOTING SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
 **LENGTH & WIDTH SPECIFIED ON WALL SEC-
 TIONS/DETAILS DON'T MATCH LENGTH AND
 WIDTH SHOWN ON FOOTING SCHEDULE.
 REVISE AS REQUIRED.
 5-PROVIDE SOIL TEST REPORT.