| Plan Review Notes For Permit 02080900 |
| Permit Number |
02080900 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-STORM SHUTTERS: A)DESIGN PRESSURES ON | | | SCHEDULE LIMITS THE SIZE OF PANELS. | | | SEE PLANS FOR CALCULATED DESIGN PRE- | | | SSURES AND REVISE AS REQUIRED. | | | B)CLARIFY WHICH ANCHOR IS USED RAWL OR | | | CAUL-IN. | | | C)MARK ON DRAWINGS MOUNTING CONDITIONS & | | | ANCHOR TYPE & SPACING USED. | | | | | | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOOR W/ SINGLE SIDELITE ASSEMBLY AS | | | SHOWN ON PLANS. | | | 3-PROVIDE UL SPECS FOR ONE HR FIRE RATED | | | GLASS BLOCK ASSEMBLY REQ'D BY TABLE | | | 600 FBC 2001. | | | **PROVIDE LEGIBLE PRODUCT APPROVAL FOR | | | GLASS BLOCK. | | | **SAFETY GLASS BLOCK REQUIRED IF FACE | | | THICKNESS IS LESS THAN 0.25". SECTION | | | 2405.2.2 FBC 2001. | | | 4-FOUNDATION PLAN AND FOOTING SCHEDULE | | | DON'T MATCH. REVISE AS REQUIRED. | | | **LENGTH & WIDTH SPECIFIED ON WALL SEC- | | | TIONS/DETAILS DON'T MATCH LENGTH AND | | | WIDTH SHOWN ON FOOTING SCHEDULE. | | | REVISE AS REQUIRED. | | | 5-PROVIDE SOIL TEST REPORT. |
|