| 2002-09-19 00:00:00 | CHECKLIST: |
| | 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND |
| | COMPLETE SECTIONS/DETAILS/SPECS FOR |
| | DESIGN OF GABLE END AT FRONT ELEVATION |
| | CONSIDERING THAT CENTER OF GABLE IS |
| | MASONRY AND THE TWO SIDES ARE WOOD |
| | TRUSSES. CLARIFY HOW IS THE WALL PUT |
| | TOGETHER TO TRANSFER ALL LOADS. SEE |
| | SECTIONS 1604.2.4, 2105, 2107, 2117 |
| | AND 2313 FBC 2001. |
| | 2-NEED RECORDED N.O.C. |
| | 3-REVISE ATTIC ACCESS SIZE. NEED 36" MIN |
| | NOT 30". SEC. 2309.6 FBC 2001. |
| | 4-34SH WINDOW DOESN'T PROVIDE 24" MIN. |
| | CLEAR HEIGHT OPENING. SEC. 1005.4.4. |
| | 5-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS.***NOTE SEE |
| | PRODUCT APPROVAL FOR LIMITATIONS. |
| | 6-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE ENTRY DOOR WITH SINGLE SIDELITE |
| | ONLY AS SHOWN ON PLANS. |
| | B)SINGLE HUNG WINDOWS. |
| | C)FIXED WINDOWS. |
| | D)WINDOW MULLIONS. |
| | E)SLIDING GLASS DOORS. |
| | F)GARAGE DOORS WITH LEGIBLE DRAWINGS. |
| | |
| | 7-PROVIDE UL LISTING AND COMPLETE SPECS |
| | FOR ONE HOUR FIRE RATED GLASS BLOCK |
| | ASSEMBLY REQUIRED BY TABLE 600 FBC. |
| | **NOTE: NEED SAFETY GLASS IF GLASS BLOCK |
| | UNIFORM FACE THICKNESS IS LESS THAN |
| | 0.25". SEC. 2405.2.2 FBC 2001. |
| | 8-REVISE GLASS BLOCK ASSEMBLY DETAIL TO |
| | MATCH UL SPECIFICATIONS.SEE SUB- |
| | MITTAL PRESENTED BY CONTRACTOR. |
| | **NOTE: WINDOW SCHEDULE TO SPECIFY ONE |
| | HOUR FIRE RATED GLASS BLOCK ASSEMBLY. |
| | 9-SPECIFY SPACING FOR WWM SUPPORTS IN |
| | CONCRETE SLAB. SEC. 1909.3 FBC 2001. |
| | 10-PROVIDE COMPLETE STRUCTURAL DETAIL |
| | FOR RECESSED WINDOWS TO ALLOW FOR |
| | STORM SHUTTERS INSTALLATION. ***NOTE: |
| | SEE PRODUCT APPROVAL FOR LIMITATIONS |
| | AND REQUIRED ADDITIONAL ENGINEERING. |
| | 11-ENERGY CALCULATIONS: |
| | A)REVISE UNDER ATTIC AREA. SEE SECTION |
| | 602.1.ABC.1.2 CHAPTER 13 FBC 2001. |
| | B)OWNER/AGENT TO DATE BOTTOM OF FORM TOO |
| | 12-WALL SECTIONS NOTE #14 AND VENT CALCS |
| | DON'T MATCH. REVISE AS REQUIRED. |
| | 13-SHEET S-2:A) UPDATE NOTE #2: SEMCO |
| | IS NOT LONGER IN BUSINESS. |
| | B)UPDATE NOTE #3 TO REFLECT FBC 2001. |
| | C)CLARIFY WHY BLOCKING AT FRONT GABLE |
| | END IS SHOWN PARTIALLY AND NOT ALL THE |
| | WAY DOWN TO THE ENDS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 14-SHEET S-1:A)CLARIFY DIMENSION OF |
| | 4'-1 1/2" SHOWN ON SECTION 5. |
| | B)PROVIDE INSTALLATION DETAIL FOR LINTEL |
| | L-7 AT FRONT PORCH SHOWING CONTINUOUS |
| | VERTICAL REINFORCEMENT. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | C)REVISE LINTEL SCHEDULE TO MATCH PLANS. |
| | CHECK SIZES SPECIFIED. |
| | 15-IDENTIFY ROOF ZONES ON ROOF FRAMING |
| | PLAN. TABLE 2306.1 CITY AMENDMENTS. |
| | 16-REVISE TRUSS ANCHOR SCHEDULE TO MATCH |
| | USP PUBLISHED VALUES. PROVIDE ENGINEE- |
| | RING CALCS FOR DIFFERENT VALUES. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 17-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| | STRUCTURAL BUCK REQUIREMENTS. REVISE |
| | DETAIL AS REQUIRED. |
| | **SPECIFY SIZE OF WASHER. |
| | 18-UPDATE FOUNDATION NOTE ON SHEET C-1: |
| | NEED 0.006 MIL VISQUEEN MIN. SECTION |
| | 1909.2 FBC 2001. |
| | 19-REVIEW ALL FLOOR PLANS AND MAKE SURE |
| | KEYED DETAILS/SECTIONS MATCH THOSE |
| | SHOWN ON THE OTHER SHEETS. |
| | 20-UPDATE GENERAL NOTE ON SHEET A-1: |
| | REFER TO FPC 2001, NOT SPC 1994. |
| | 21-SHEET A-3: REVISE SECTION THRU ENTRY |
| | PORCH TO MATCH MASONRY GABLE END SPECS |
| | SEE SECTION 2117 FBC 2001. |
| | 22-SURVEY AND FLOOR PLANS DON'T MATCH. |
| | ZERO LOT WALL IS ON THE OPPOSITE SIDE. |
| | CLARIFY WHY. |
| | 23-PROVIDE SOIL TEST REPORT. |