Plan Review Notes
Plan Review Notes For Permit 02080898
Permit Number 02080898
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SEE ENGINEERING ANALYSIS AND REVISE
 THE DIAPHRAGM SCHEDULE AS REQUIRED.
 **ALSO, REVISE THE SPECS ON THE WALL
 SECTIONS AND DETAILS TO MATCH ENGINEER
 ANALYSIS.
 2-STORM SHUTTERS:
 A)DESIGN PRESSURES SPECIFIED HAVE LIMI-
 TATIONS ON PANELS SPAN. SEE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT
 AND REVISE AS REQUIRED. ALSO, CLARIFY
 ANCHOR USED RAWL OR CAULK-IN.
 B)MARK ON DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED.
  
 3-REVISE DETAIL 11/S3. NEED ON HR FIRE
 RATED ASSEMBLY CONSIDERING EXPOSURE TO
 FIRE ON THE INTERIOR AND THE EXTERIOR
 SIDE AS WELL AS REQUIRED BY TABLE 600
 FBC 2001, FOOTNOTE I.
 4-NO INFORMATION WAS GIVEN ON THE SIZE
 OF ANCHOR BOLTS FOR BOTTOM OF STEEL
 COLUMN. DETAIL 41/S2 REFERS TO COLUMN
 SCHEDULE BUT THERE AREN'T SPECS ON IT.
 PROVIDE SUCH INFORMATION.
 5-SURVEY DOESN'T MATCH FLOOR PLANS. SEE
 REAR PORCH AND REVISE AS REQUIRED.