| Plan Review Notes For Permit 02080898 |
| Permit Number |
02080898 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-07 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-SEE ENGINEERING ANALYSIS AND REVISE | | | THE DIAPHRAGM SCHEDULE AS REQUIRED. | | | **ALSO, REVISE THE SPECS ON THE WALL | | | SECTIONS AND DETAILS TO MATCH ENGINEER | | | ANALYSIS. | | | 2-STORM SHUTTERS: | | | A)DESIGN PRESSURES SPECIFIED HAVE LIMI- | | | TATIONS ON PANELS SPAN. SEE DESIGN | | | PRESSURES CALCULATED BY THE ARCHITECT | | | AND REVISE AS REQUIRED. ALSO, CLARIFY | | | ANCHOR USED RAWL OR CAULK-IN. | | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE & SPACING | | | TO BE USED. | | | | | | 3-REVISE DETAIL 11/S3. NEED ON HR FIRE | | | RATED ASSEMBLY CONSIDERING EXPOSURE TO | | | FIRE ON THE INTERIOR AND THE EXTERIOR | | | SIDE AS WELL AS REQUIRED BY TABLE 600 | | | FBC 2001, FOOTNOTE I. | | | 4-NO INFORMATION WAS GIVEN ON THE SIZE | | | OF ANCHOR BOLTS FOR BOTTOM OF STEEL | | | COLUMN. DETAIL 41/S2 REFERS TO COLUMN | | | SCHEDULE BUT THERE AREN'T SPECS ON IT. | | | PROVIDE SUCH INFORMATION. | | | 5-SURVEY DOESN'T MATCH FLOOR PLANS. SEE | | | REAR PORCH AND REVISE AS REQUIRED. |
|