| 2002-09-24 00:00:00 | CHECKLIST: |
| | 1-FLOOD ZONE A8: WILL NEED THE ELEVATION |
| | CERTIFICATE. |
| | 2-NEED RECORDED N.O.C. |
| | 3-SHEET C-1: UPDATE FOUNDATION NOTE. |
| | NEED 0.006 MIL VISQUEEN. SEC. 1909.2 |
| | 4-SHEET A-2: A) REVISE WINDOW SCHEDULE. |
| | 24SH & 34SH WINDOWS DON'T ALLOW THE |
| | 24" MIN. CLEAR HEIGHT OPENING AND THE |
| | 5.7 S.F. MIN. TOTAL CLEAR OPENING. |
| | SEC. 1005.4.4 FBC 2001. |
| | B)GLASS BLOCK TO BE 1 HR FIRE RATED |
| | ASSEMBLY. TABLE 600 FBC 2001. |
| | **NOTE A): SEE PRODUCT APPROVAL AND UL |
| | SPECS SUBMITTED BY CONTRACTOR & REVISE |
| | DETAIL AS REQUIRED. ALSO, NOTE THAT |
| | GLASS BLOCK SUBMITTED IS NOT BY P.C. |
| | **NOTE B) GLASS BLOCK TO BE SAFETY GLASS |
| | IF UNIFORM FACE THICKNESS IS LESS THAN |
| | 0.25". SEC. 2405.2 FBC 2001. |
| | C)UPDATE PLUMBING INFORMATION ON NOTE #6 |
| | 5-SHEET A-4: A)REVISE STAIR KEY NOTE #1. |
| | HANDRAIL HEIGHT TO BE BET. 34" AND 38" |
| | SEE SEC. 1007.5.1 FBC 2001. |
| | B)NOTE #14: SPEC. FIREBLOCKING MATERIAL |
| | SEE SEC. 2305.1.4 FBC FOR LOCATION OF |
| | FIREBLOCKING AT STAIRS. ALSO, SEE SEC. |
| | 2305.1.2 FBC 2001. |
| | C)PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| | AT ALL CONCEALED AREAS AS REQUIRED BY |
| | SEC. 2305.1.4 FBC 2001. |
| | 6-NOTE #14: VENT SIZE DOESN'T MATCH VENT |
| | CALCULATIONS. REVISE AS REQUIRED. |
| | 7-SHEET S-1: A) SPECIFY SPACING FOR WWM |
| | SUPPORTS IN CONCRETE SLAB. SEC. 1909.3 |
| | B)CLARIFY SIZE OF BUCKET SHOWN ON DETAIL |
| | S6. SEE SIZE OF GIRDER TRUSS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | C)DETAIL S21 DOESN'T MATCH CONDITIONS ON |
| | PLAN. PROVIDE DETAIL SHOWING ACTUAL |
| | CORNER CONDITIONS. **NOTE: KEEP IN |
| | MIND SIZE OF POST. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | D)CLARIFY WHY SOME TRUSS GIRDERS ON 2ND |
| | FLOOR PLAN ARE NOT RESTING ON COLUMNS. |
| | SEE PLAN.SEC. 104.2.1.2 CITY AMENDM. |
| | E)SPECIFY UPLIFT LOADS ON ROOF FRAMING |
| | PLAN AND KEY PROPER ANCHOR. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | F)SHOW NAILING ZONES IN ROOF PLAN. SEE |
| | TABLE 2306.1 CITY AMENDMENTS TO FBC. |
| | 8-REVISE TRUSS ANCHOR SCHEDULE TO MATCH |
| | USP PUBLISHED VALUES. PROVIDE ENGINEE- |
| | RING CALCS FOR DIFFERENT VALUES. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 9-SHEET S-3: A)PROVIDE FIRECUT SPECS IN |
| | WALL SECTIONS. SEC. 2305.4 FBC 2001. |
| | B)SECTION S2 HAS SOME INFORMATION THAT |
| | IS OVERLAPPING. REVISE AS REQUIRED. |
| | C)DETAIL F14: SPECIFY HOW LONG ARE THE |
| | ANCHOR BOLTS. SEC. 104.2.1.2 CITY AM. |
| | 10-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | FRAMED OPENING TO RECEIVE ARCHED WIND. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 11-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS. SEE LIMITATIONS |
| | ON PRODUCT APPROVAL. |
| | 12-PROVIDE PRODUCT APPROVAL FOR: A)ONE |
| | HR FIRE RATED GLASS BLOCK ASSEMBLY W/ |
| | LEGIBLE INFORMATION. |
| | B)GARAGE DOORS W/ LEGIBLE DRAWINGS. |
| | |
| | |
| | NOTE: |
| | SEE REVIEWED SET OF PLANS FOR REFERENCE |
| | AND PLEASE RETURN THEM AFTER CORRECTIONS |
| | ARE DONE TO THE ORIGINAL DRAINGS IN |
| | ORDER TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU. |