Plan Review Notes
Plan Review Notes For Permit 02080886
Permit Number 02080886
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM SHALL REFLECT
 FLOOR PLAN.
 2) SHOWER NOT VENTED.
 3) HORIZONTAL DRY VENT PAST TUB NOT
 PER CODE. SEC 905.3
 4) SEE ATTACHED SHEET FOR EXAMPLE OF
 SANITARY RISER
  
 REVIEW BY KEN STEVENS