| 2002-10-28 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | --PROVISO-- |
| | FBC 1606.1.4THE SUBMITTED MADDEN |
| | IMPACT PROTECTION PANEL DRAWING (NUMBER |
| | 28GAWC/3-2002/S) DOES NOT CORRESPOND TO |
| | ITEM# 6 OF THE SUBMITTED SBCCI PRODUCT |
| | APPROVAL REPORT# 2056 FOR MADDEN STORM |
| | PANELS. SUBMIT TWO COPIES OF THE CORRECT |
| | PRODUCT APPROVED MADDEN STORM PANEL |
| | DRAWINGS LISTED UNDER THE ITEM# 6 |
| | HEADING 'SUBSTANTIATING DATA', OR SUBMIT |
| | AN ALTERNATIVE PRODUCT APPROVAL. |
| | |
| | --PROVISO-- |
| | FBC 1504ROOF COVERINGS.THE SOUTH |
| | ELEVATION SHOWS 'ROOF SHINGLE TO MATCH |
| | EXISTING' OVER THE DEN, BUT THE |
| | SUBMITTED PRODUCT APPROVAL IS FOR A FLAT |
| | PROFILE CONCRETE ROOF TILE.BEFORE ROOF |
| | SHEATHING INSPECTION, SUBMIT TWO COPIES |
| | OF AN APPROPRIATE PRODUCT APPROVAL FOR |
| | THE SPECIFIED ROOF COVERING TYPE.ALSO, |
| | SHEETS 2,3,6,7 AND 8 OT THE SUBMITTED |
| | TAMKO MODIFIED BITUMEN ROOF SYSTEM |
| | PRODUCT APPROVAL NOA# 01-0509.01 ARE |
| | EITHER MISSING OR IMPROPERLY COPIED. |
| | SUBMIT TWO COPIES. |