| 2002-08-27 00:00:00 | ************* PROVISO/NOTES ********** | | | | | | 1)NOTE: PLEASE NOTE EQUIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN AND PANEL NOT | | | SHOWN. SIZE PER 250-122 | | | | | | 2)NOTE: PLEASE NOTE WRONG ARTS FROM NEC | | | ARE REFERENCED IN NOTES. THOSE ARTS ARE | | | FROM THE 96 NEC. PLEASE CORRECT TO 99 | | | NEC. | | | | | | 3)NOTE: PLEASE NOTE, NO INDICATION FOR | | | REQ`D ARC FAULT PROTECTION PER 210-12. | | | IT IS NOTED THAT RECEPTS ARE SHOWN W/ | | | A SLASH BUT NO INDICATION IS SHOWN ON | | | SCHEDULE. | | | | | | 4)NOTE: PLEASE NOTE AIC RATING SHOWN AS | | | A MISPRINT AS 22.00, SHOULD BE 22,000. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -IONIS CALLED IN. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|