Plan Review Notes
Plan Review Notes For Permit 02080791
Permit Number 02080791
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-04 00:00:00*********** NOTE ***********
  
 PLANS REDLINED,
 BOTH A/C SYSTEMS SHOW 10KW HEAT W/ 2P-30
 A BREAKERS AND #10AWG.
 PLEASE HAVE LOADS/WIRE/BRKS CORRELATE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372