| Plan Review Notes For Permit 02080761 |
| Permit Number |
02080761 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-22 00:00:00 | THE TWO UNDATED, UNSIGNED TRACINGS, | | | FROMTHE FS-1 MERLINO ASSOCIATES PLANS | | | ARE NOT COMPLETELY CLEAR AS TO THE | | | SCOPE OF WORK TO BE ACCOMPLISHED. | | | | | | A CONSTRUCTION DETAIL FOR PARTITIONS | | | WILL BE NECESSARY INCLUDING MATERIALS, | | | TERMINATION POINTS, AND OTHER PERINENT | | | INFORMATION. | | | | | | THE PLAN WILL NEED DIMENSIONS SHOWN. | | | | | | IF THE FOOD SERVICE EQUIPMENT SHOWN IS | | | INTENDED TO BE INSTALLED, THEN THE | | | NECESSARY SUPPORT INFORMATION MUST BE | | | SHOWN ONTHE PLANS, IE MECHANICAL, | | | PLUMBING AND ELECTRIC SERVICES. | | | | | | WHAT IS THE ADJACENT AREA SHOWN USED | | | FOR?IS TENANT SEPARATION EXISTING OR | | | TO BE PROVIDED? WHAT IS THE DOOR SHOWN | | | OPENING INTO THE CORRIDOR AREA NEAR THE | | | TOILET ROOM? | | | | | | SEE FBC 104.3.1.1 FOR A COMPREHENSIVE | | | LIST OF THE MINIMUM ITEMS REQUIRED FOR | | | PLAN REVIEW AND SUBSEQUENT PERMITTING AS | | | WELL AS FBC 104.2. | | | | | | IF THE FOOD EQUIPMENT IS TO BE | | | INSTALLED THEN AN ARCHITECT OR ENGINEER | | | WILL BE REQUIRED TO PREPARE THE PLANS. | | | FBC 104.1.3. |
|