| Plan Review Notes For Permit 02080648 |
| Permit Number |
02080648 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-21 00:00:00 | 1) NO FIRE DEPARTMENT CONNECTION SHOWN | | | ON DRAWINGS. PLEASE PROVIDE A FIRE | | | DEPARTMENT CONNECTION WITHIN 150 FEET | | | OF A FIRE HYDRANT. | | | | | | 2) UNDERGROUND PIPING TO BE RESTRAINED | | | IN ACCORDANCE WITH NFPA 24. | | | | | | 3) ALL UNDERGROUND PIPING TO BE PRESSURE | | | TESTED AT 200 PSI FOR TWO HOURS. | | | | | | 4) FIRE LINES ARE NOT ALLOWED TO BE RUN | | | UNDERNEATH THE BUILDING UNLESS | | | ABSOLUTLEY NECESSARY. PLEASE CLARIFY | | | AND REVISE PLANS AS NECESSARY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|