| Notes |
| Date |
Text |
| 2002-08-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) PLEASE PROVIDE CALCULATIONS FOR MIN- | | | IMUM FACILITIES PER TABLE 403.1. SHOW | | | SQUARE FOOTAGE FOR SPACE BEING OCCUPIED. | | | | | | 2) SHT A-4 WATER COOLER SHALL COMPLY | | | WITH ARI-1010. PLEASE PROVIDE MANUF. IN- | | | FORMATION. | | | | | | 3) SHT P-1 WATER RISER DIAGRAM, AIR | | | CHAMBERS ARE NOT APPROVED. WATER HAMMER | | | ARRESTORS SHALL BE INSTALLED WHERE REQ- | | | UIRED PER SEC 604.9 AND LOCATED NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" NOT AT | | | THE TOP OF DROPS AS SHOWN. PDI-WH 201 & | | | MANUF. INSTALL. INSTRUCTIONS. | | | | | | 4) SHT P-2 PLUMBING SPECIFICATIONS #7, | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | | DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|