Plan Review Notes
Plan Review Notes For Permit 02080635
Permit Number 02080635
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE PROVIDE CALCULATIONS FOR MIN-
 IMUM FACILITIES PER TABLE 403.1. SHOW
 SQUARE FOOTAGE FOR SPACE BEING OCCUPIED.
  
 2) SHT A-4 WATER COOLER SHALL COMPLY
 WITH ARI-1010. PLEASE PROVIDE MANUF. IN-
 FORMATION.
  
 3) SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS SHALL BE INSTALLED WHERE REQ-
 UIRED PER SEC 604.9 AND LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF DROPS AS SHOWN. PDI-WH 201 &
 MANUF. INSTALL. INSTRUCTIONS.
  
 4) SHT P-2 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377