| Notes |
| Date |
Text |
| 2002-08-14 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE/CLARIFY THE USE OF | | | EMT TO TRANSFORMER. PLEASE NOTE CONNECT- | | | ION DUE TO VIBRATION. | | | | | | 2)NOTE: PLEASE NOTE GROUNDING PER 450-10 | | | AND 250-30 REQ`D BONDING JUMPER. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 220-3,220-10,220-13 ETC | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | | 215-3,230-42 ETC. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATING FOR NEW | | | MAIN DISCONNECT. AIC RATING IS NOTED FOR | | | PANELS. 110-9 | | | | | | 5)NOTE: PLEASE CLARIFY SHOW WINDOW RECEP | | | PER 210-62 | | | | | | 6)NOTE: PLEASE CLARIFY COVER SHEET SHOWS | | | SETS TO INCLUDE AN E-4? E-1,2,3 WAS ONLY | | | ONES SUBMITTED? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|