Plan Review Notes
Plan Review Notes For Permit 02080601
Permit Number 02080601
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-12 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE IMPORTANCE FACTOR (1.00)
 AND THE INTERNAL PRESSURE COEFFICIENT
 WHICH IS + OR - .18 ON THE PLANS.
  
 3) PLEASE SPECIFY THE CONNECTORS FOR ALL
 OF THE TRUSSES. WHAT CONNECTORS ARE TO
 BE USED FOR THE TRUSSES THAT ARE NOT
 TAGGED?
  
 4) THE ENERGY CALCS. MUST BE SIGNED AND
 SEALED BY THE OWNER/AGENT.
  
 5)STORM PANELS;CITY AMEND.& FBC SECTIONS
 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. PROVIDE (2) COPIES OF KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS OR A SEPARATE PERMIT WITH
 ADDITIONAL FEES WILL BE REQUIRED.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS
 - STEEL ENTRY DOOR (THE ONE SUBMITTED
 HAS EXPIRED)
  
 7) GENERAL NOTE #1 ON SHEET 4 IS NOT
 CORRECT. SEE CITY OF WPB AMENDMENTS TO
 THE 2001 FBC REVISED TABLE 2306.1.
  
 8)WALLS SHALL BE FIREBLOCKED AT CEILINGS
 PER FBC 705.3.1. PLEASE INDICATE ON THE
 WALL SECTION ON SHEET 2.
  
 9) PLEASE REMOVE THE PLOT PLAN FROM
 SHEET 1, THAT WAS NOT APPROVED BY ZONING
 DUE TO TOO MUCH PAVED AREA IN THE FRONT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202