Text |
| 2002-11-12 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | INDICATE THE IMPORTANCE FACTOR (1.00) |
| | AND THE INTERNAL PRESSURE COEFFICIENT |
| | WHICH IS + OR - .18 ON THE PLANS. |
| | |
| | 3) PLEASE SPECIFY THE CONNECTORS FOR ALL |
| | OF THE TRUSSES. WHAT CONNECTORS ARE TO |
| | BE USED FOR THE TRUSSES THAT ARE NOT |
| | TAGGED? |
| | |
| | 4) THE ENERGY CALCS. MUST BE SIGNED AND |
| | SEALED BY THE OWNER/AGENT. |
| | |
| | 5)STORM PANELS;CITY AMEND.& FBC SECTIONS |
| | 103.6, 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. PROVIDE (2) COPIES OF KEY PLAN |
| | AND INSTALLATION SCHEDULE FOR STORM |
| | PANELS OR A SEPARATE PERMIT WITH |
| | ADDITIONAL FEES WILL BE REQUIRED. |
| | |
| | 6)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS |
| | - STEEL ENTRY DOOR (THE ONE SUBMITTED |
| | HAS EXPIRED) |
| | |
| | 7) GENERAL NOTE #1 ON SHEET 4 IS NOT |
| | CORRECT. SEE CITY OF WPB AMENDMENTS TO |
| | THE 2001 FBC REVISED TABLE 2306.1. |
| | |
| | 8)WALLS SHALL BE FIREBLOCKED AT CEILINGS |
| | PER FBC 705.3.1. PLEASE INDICATE ON THE |
| | WALL SECTION ON SHEET 2. |
| | |
| | 9) PLEASE REMOVE THE PLOT PLAN FROM |
| | SHEET 1, THAT WAS NOT APPROVED BY ZONING |
| | DUE TO TOO MUCH PAVED AREA IN THE FRONT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |