| Date |
Text |
| 2002-09-23 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4) INDICATE THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES IN PSF FOR ALL |
| | EXTERIOR WINDOW AND DOOR OPENINGS. |
| | |
| | 5) SPECIFY THE TYPE OF WINDOWS THAT ARE |
| | BEING USED ON THE PLAN. (SINGLE HUNG, |
| | AWNING, ETC.). THE PRODUCT APPROVAL THAT |
| | WAS SUBMITTED IS FOR SINGLE HUNG. |
| | |
| | 6) FBC 2405.2.1(2) REQUIRES SAFETY |
| | GLAZING IN WIDOWS AT BATHTUBS. PLEASE |
| | INDICATE TEMPERED GLASS ON PLANS AT |
| | THESE LOCATIONS. |
| | |
| | 7)1804.1.3 THE BOTTOM OF THE FOUNDA- |
| | TION SHALL EXTEND NO LESS THAN 12" |
| | BELOW FINISH GRADE. |
| | |
| | 8) PROVIDE EMERGENCY EGRESS WINDOW IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGHT OF 24INCHES,NET CLEAR |
| | OPENING WIDTH OF 20 INCHES AND NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT |
| | SHALL NOT BE MORE THAN 44 INCHES ABOVE |
| | THE FLOOR. 2001 FBC 1005.4 |
| | |
| | 9) PLEASE SPECIFY THE CONNECTORS FOR ALL |
| | OF THE TRUSSES. |
| | |
| | 10) THE UPLIFT VALUES LISTED IN THE |
| | CONNECTOR SCHEDULE ARE NOT CORRECT. |
| | PLEASE REFER TO THE 2002 SIMPSON |
| | CATALOG FOR VALUES. PROVIDE CALCULATIONS |
| | (SIGNED & SEALED) FOR UPLIFT VALUES |
| | WHEN USING LESS THAN THE NUMBER OF |
| | FASTENERS SPECIFIED IN THE CATALOG. |
| | |
| | 11) THE MINIMUM CENTER TO CENTER SPACING |
| | OF HETA CONNECTORS IS GIVEN AS 8" IN THE |
| | CATALOG. IF INSTALLED CLOSER THAN 8" A |
| | REDUCTION IN VALUE IS REQUIRED. |
| | |
| | 12) THE AREA UNDER ATTIC ON THE ENERGY |
| | CALCULATIONS IS 1526 SQFT AND THE A/C |
| | AREA GIVEN ON PLANS IS 1378 SQFT. NO |
| | VAULTED OR TRAY CEILINGS ARE INDICATED |
| | ON THE PLANS. PLEASE CORRECT. |
| | |
| | 13) THE ENERGY CALCS. MUST BE SIGNED AND |
| | DATED BY THE OWNER/AGENT. |
| | |
| | 14)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 15) INDICATE THE CEILING MATERIAL FOR |
| | THE COVERED ENTRY. (IF USING WIRE LATH & |
| | STUCCO, INSTALLATION MUST COMPLY WITH |
| | ASTM C 926 AND ASTM C 1063. SPECIFY LATH |
| | TYPE AND FASTENERS. HIGH RIB METAL LATH |
| | REQUIRES FASTENERS TO PENETRATE 1-3/4" |
| | INTO HORIZONTAL WOOD FRAMING.) |
| | |
| | 16) INDICATE THE MEAN ROOF HEIGHT ON THE |
| | PLANS. |
| | |
| | 17) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS |
| | - STEEL ENTRY DOOR (THE ONE SUBMITTED |
| | HAS EXPIRED) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |