Plan Review Notes
Plan Review Notes For Permit 02080601
Permit Number 02080601
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-16 00:00:00************UNSAT ******************
  
 1)NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE OUTLETS TO MEET 210-52-C-1 FOR
 WALL SPACE AND 210-52-C-3 FOR PENINSULAR
  
 2)NOTE: PLEASE CLARIFY GROUNDING ELEC-
 -TRODE NOTE AS ( 2-#6 OR 1-#2) ??
 PLEASE SEE 250-66 FOR SIZING OF GROUND-
 -ING ELECTRODE CONDUCTOR.
  
 3)NOTE: PLEASE ALSO NOTE GROUDING ELEC-
 -TRODE TO COLD WATER PIPE ALSO PER 250-
 50.
  
 4)NOTE: PLEASE LIST THE REQ`D BATH CIR-
 -CUITS PER 210-52D/210-11-C-3 ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE LIST THE REQ`DARC-
 -FAULT PROTECTED CIRCUITS PER 210-12 ON
 PANEL SCHEDULE.
  
 6)NOTE: PLEASE NOTE CLEARENCE REQ`MENTS
 FOR WATER HEATER PER 422.17
  
 7)NOTE: PLEASE NOTE OVERCURRENT PROTECT-
 -ION FOR AHU IS NOT SIZED LARGE ENOUGH
 PER 424-3. MIN 125%.
  
 8)NOTE: PLEASE KW RATINGS FOR FRIG AND
 DRYER DO NOT CORRELATE WITH LOAD
 CALCULATIONS.
  
 9)NOTE: PLEASE CLARIFY/NOTE CONDUIT SIZE
 SHOWN ON RISER DIAGRAM GOING TO AHU IS
 SHOWN AT 1 1/2"? PLEASE NOTE IF SHOWN ON
 PLAN, THEN THATS WHAT SIZE WILL BE REQ`D
 TO BE INSTALLED. PLEASE CLARIFY THAT
 THIS 1 1/2" CONDUIT NOTE SHOULD HAVE
 BEEN FOR CONDUIT FROM METER TO PANEL??
  
 10)NOTE: PLEASE NOTE MISSING OUTLET IN
 MASTER BEDROOM PER 210-52.
  
 11)NOTE: PLEASE NOTE SD`S ARE TO BE A
 MIN OF 3' FROM BATHROOM DOORS PER NFPA-
 72 2-5.2.1.6.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 CHNAGES FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372