| 2002-09-16 00:00:00 | ************UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE OUTLETS TO MEET 210-52-C-1 FOR |
| | WALL SPACE AND 210-52-C-3 FOR PENINSULAR |
| | |
| | 2)NOTE: PLEASE CLARIFY GROUNDING ELEC- |
| | -TRODE NOTE AS ( 2-#6 OR 1-#2) ?? |
| | PLEASE SEE 250-66 FOR SIZING OF GROUND- |
| | -ING ELECTRODE CONDUCTOR. |
| | |
| | 3)NOTE: PLEASE ALSO NOTE GROUDING ELEC- |
| | -TRODE TO COLD WATER PIPE ALSO PER 250- |
| | 50. |
| | |
| | 4)NOTE: PLEASE LIST THE REQ`D BATH CIR- |
| | -CUITS PER 210-52D/210-11-C-3 ON PANEL |
| | SCHEDULE. |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`DARC- |
| | -FAULT PROTECTED CIRCUITS PER 210-12 ON |
| | PANEL SCHEDULE. |
| | |
| | 6)NOTE: PLEASE NOTE CLEARENCE REQ`MENTS |
| | FOR WATER HEATER PER 422.17 |
| | |
| | 7)NOTE: PLEASE NOTE OVERCURRENT PROTECT- |
| | -ION FOR AHU IS NOT SIZED LARGE ENOUGH |
| | PER 424-3. MIN 125%. |
| | |
| | 8)NOTE: PLEASE KW RATINGS FOR FRIG AND |
| | DRYER DO NOT CORRELATE WITH LOAD |
| | CALCULATIONS. |
| | |
| | 9)NOTE: PLEASE CLARIFY/NOTE CONDUIT SIZE |
| | SHOWN ON RISER DIAGRAM GOING TO AHU IS |
| | SHOWN AT 1 1/2"? PLEASE NOTE IF SHOWN ON |
| | PLAN, THEN THATS WHAT SIZE WILL BE REQ`D |
| | TO BE INSTALLED. PLEASE CLARIFY THAT |
| | THIS 1 1/2" CONDUIT NOTE SHOULD HAVE |
| | BEEN FOR CONDUIT FROM METER TO PANEL?? |
| | |
| | 10)NOTE: PLEASE NOTE MISSING OUTLET IN |
| | MASTER BEDROOM PER 210-52. |
| | |
| | 11)NOTE: PLEASE NOTE SD`S ARE TO BE A |
| | MIN OF 3' FROM BATHROOM DOORS PER NFPA- |
| | 72 2-5.2.1.6. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION AND |
| | CHNAGES FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |