Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop E
Sequence Number 9
Notes
Date Text
2004-06-08 00:00:00********** UNSAT ****************
  
 REVIEW FOR APT LAYOUTS ONLY.
  
 1)NOTE: PLEASE SEE NOTES FOR SD'S ON
 EACH SHEET HAS NOT BEEN UPDATED.
  
 SD'S ARE REQUIRED TO A MIN OF 3' FROM
 SUPPLY AIR GRILLES AND 5' FROM RETURNS.
 PLEASE ALSO SEE NFPA-72 8-1.4.2.1
 WHICH REQUIRES SD'S TO BE 3' FROM BATH(S
 DOORS/ KITCHEN DOORS AND 20' FROM
 COOKING APPLIANCES W/ EXCEPTIONS. ETC
 PLEASE SEE NFPA AND NOTE NFPA ART. ON
 PLANS FOR INSTALLATION.
  
 2)NOTE: PLEASE SEE UNIT/ LAYOUTS,
 SOME SHOW SMALL APPLIANCE CIRCUITS
 IN DEN AREA. THESE CAN BE IN DINING RM
 AREA BUT NOT DEN.
 210.52-2-B
  
 3)NOTE: PLEASE SEE SOME UNITS ARE
 CIRCUITING FOR SD'S.
 ALSO MISSING SOME CIRCUITING FOR SOME
 NEW ITEMS.
 PLEASE GOING OVER CIRCUITING FOR ALL
 UNITS.
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OF WALL SPACE IN SOME
 UNITS.
 PLEASE SEE ONE SET HAS SOME REDLINED/
 CIRCILED FOR THIS. E-117/118 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]