| 2004-06-08 00:00:00 | ********** UNSAT **************** |
| | |
| | REVIEW FOR APT LAYOUTS ONLY. |
| | |
| | 1)NOTE: PLEASE SEE NOTES FOR SD'S ON |
| | EACH SHEET HAS NOT BEEN UPDATED. |
| | |
| | SD'S ARE REQUIRED TO A MIN OF 3' FROM |
| | SUPPLY AIR GRILLES AND 5' FROM RETURNS. |
| | PLEASE ALSO SEE NFPA-72 8-1.4.2.1 |
| | WHICH REQUIRES SD'S TO BE 3' FROM BATH(S |
| | DOORS/ KITCHEN DOORS AND 20' FROM |
| | COOKING APPLIANCES W/ EXCEPTIONS. ETC |
| | PLEASE SEE NFPA AND NOTE NFPA ART. ON |
| | PLANS FOR INSTALLATION. |
| | |
| | 2)NOTE: PLEASE SEE UNIT/ LAYOUTS, |
| | SOME SHOW SMALL APPLIANCE CIRCUITS |
| | IN DEN AREA. THESE CAN BE IN DINING RM |
| | AREA BUT NOT DEN. |
| | 210.52-2-B |
| | |
| | 3)NOTE: PLEASE SEE SOME UNITS ARE |
| | CIRCUITING FOR SD'S. |
| | ALSO MISSING SOME CIRCUITING FOR SOME |
| | NEW ITEMS. |
| | PLEASE GOING OVER CIRCUITING FOR ALL |
| | UNITS. |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| | MISSING FOR 2' OF WALL SPACE IN SOME |
| | UNITS. |
| | PLEASE SEE ONE SET HAS SOME REDLINED/ |
| | CIRCILED FOR THIS. E-117/118 ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |