| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
B |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2003-07-31 00:00:00 | STEEL CONSTRUCTION SYSTEMS PRELIMINARY | | | TRUSS ENGINEERING PACKAGE DATED 6/24/03 | | | | | | THE DESIGN LOADINGS DECLARE FBC 1606.2 | | | AND 60'.SOME SHEETS DECLARE 130 MPH | | | AND 30' ASCE 7-98. | | | | | | THIS BUILDING IS >60' TALL AND IS | | | LOCATED IN AN 140 MPH ZONE THUS THE | | | ABOVE IS INCORRECT. | | | | | | THE EOR SHOULD RE-ASSERT THE DESIGN | | | CRITERIA FOR DELEGATED ENGINEERING | | | RESPONSIBILITIES IN ACCORDANCE WITH | | | RULE 61G15-30.005 OF THE FAC TO THE | | | TRUSS DESIGNERS. | | | | | | CC: DON NEELY |
|