| Date |
Text |
| 2003-12-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHTS P-1.3 & P-208.0 RELIEF VENT RE- |
| | QUIRD FOR AAV IN TRASH ROOM. SEC 917.3.2 |
| | 2) SHT P-1.3 CLAIRFY THIRD RISER NEXT TO |
| | AAV AT TRASH ROOM. MAIN DRAIN ISOMETRIC |
| | DIAGRAM ONLY SHOWS 2/29 & S/33. SECTION |
| | 104.2.1 |
| | 3) SHT P-3.1 IDENTIFY RISERS COL. LINE G |
| | SHT P-1.4 SHOWS S/3 AS CENTER RISER, BUT |
| | RISER DIAG. SHOWS S/8 AS CENTER RISER. |
| | PLEASE CLAIRFY. SEC 104.2.1 |
| | 4) SHT P-1.3 CLEANOUTS REQUIRED MINIMUM |
| | 100'. SECTION 708.3.2 |
| | 5) SHTS P-1.4 & P-208.0 IDENTIFY RISER |
| | AT COL. LINE N.12. SECTION 104.2.1 |
| | 6) SHTS P-1.4 & P-208.0 SANT. RISER DOES |
| | NOT REFLECT THE FLOOR PLAN AT RISERS S/7 |
| | S/7, S/3A, & S/1A. RISER SHOWS 2 RISERS, |
| | AND FLOOR PLAN SHOWS 1 RISER. PLEASE |
| | CLAIRFY. SECTION 104.2.1 |
| | 7) SHTS P-1.4 & P-208.0 RELIEF VENT REQ- |
| | UIRED FOR AAV IN FIRE PUMP ROOM. SECTION |
| | 917.3.2 |
| | 8) SHT P-1.4 CLEANOUTS REQUIRED NEAR COL |
| | LINES S.7 & C AND S.20 & C. SEC 708.3.2. |
| | 9) SHT P-1.5 CLEANOUT SHOWN ON RISER BUT |
| | NOT ON FLOOR PLAN NEAR COL. LINE S.43 |
| | BETWEEN C & D. PLEASE CLAIRFY. 104.2.1 |
| | 10) SHTS P-1.5 & P-208.0 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN AT TRASH ROOM. |
| | RISER SHOWS 2 RISERS AND NO AAV, FLOOR |
| | PLAN SHOWS SINGLE RISER WITH AN AAV. |
| | PLEASE CLAIRFY. 104.2.1 - RELIEF VENT |
| | REQUIRED FOR AAV. SEC 917.3.2 |
| | 11) SHT P-2.1 SANT. RISER NOT IDENTIFIED |
| | BETWEEN COLS. N.13 & N.14 BY STAIR #3. |
| | 104.2.1 |
| | 12) MANY SHEETS, THE REVISION NUMBERS DO |
| | NOT MATCH REVISION CALLD OUT, AND MANY |
| | REVISIONS HAVE NO REV. NUMBER AT ALL. |
| | PLEASE CLAIRFY. 104.2.1 |
| | 13) MANY SHEETS SANT. RISER NUMBER IS |
| | SUPERIMPOSED OVER OTHER INFORMATION SO |
| | THE NUMBER CAN NOT BE READ. 104.2.1 |
| | 14) SHT P-2.2 STUDIOS 1, 2, & 3. SANT. |
| | RISERS, NEW RISERS ADDED AND SUPERIMPOS- |
| | ED OVER OLD RISER NUMBERS MAKING IT SO |
| | THE RISER NUMBERS CAN NOT BE READ. |
| | 15) SHT P-6.2 REVISION 5 SHOWN. PLEASE |
| | CLAIRFY. 104.2.1 |
| | 16) SHT P-7.2 REVISION 2 SHOWN. IS THIS |
| | A NEW REVISION? PLEASE CLAIRFY. 104.2.1 |
| | 17) SHTS P-100 THRU P-119 INDICATE RISER |
| | NUMBERS FOR ALL UNITS. 104.2.1 |
| | 18) SHT P-119 STUDIO #6 SHOWS S/13A, & |
| | S/21. THESE RISERS ARE NOT FOUND ON THE |
| | RISER SHEETS. ALSO RISER S/5A SHOWS A |
| | KITCHEN SINK W/DISHWASHER, AND FLOOR |
| | PLAN SHOWS A TUB. PLEASE CLAIRFY. SECT- |
| | ION 104.2.1 |
| | 19) SHT P-208.0 SANITARY RISERS SHOWN UP |
| | TO S/17, BLDG DRAIN ISOMETRIC AND FLOOR |
| | PLAN SHEETS SHOW RISERS UP TO S/39. PRO- |
| | VIDE ALL MISSING SANT. RISER DIAGRAMS |
| | FOR REVIEW. SEC 104.2.1 |
| | 20) SHTS P-120, P-203, P-204, & P-205 |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | & MANUFACTURE INSTALLATION INSTRUCTIONS. |
| | 21) SHT P-200 OFFSET VENTS REQUIRED FOR |
| | SANT. RISERS S/1B, S/2C, & S/7A. SECTION |
| | 915. |
| | 22) SHT P-201, SHOW VENT SIZE FOR MAIN |
| | VENT FOR WASH MACHINES ON RISER S/17 PER |
| | TABLE 916.1. |
| | 23) SHT P-200 SANT. RISERS S/2, S/2A, & |
| | S/2B, RELIEF VENTS REQUIRED FOR AAV'S |
| | BELOW THE 5TH FLOOR. SEC 917.3.2 |
| | 24) SHT P-200 SANT RISER S/1B RELIEF |
| | VENT REQUIRED FOR AAV BELOW 5TH FLOOR. |
| | SECTION 917.3.2 |
| | 25) SHT P-200 RISER S/5 NOT FOUND ON 1ST |
| | FLOOR BLDG DRAIN ISOMETRIC SHT P-208.0 |
| | 26) SHT P-202 RPZ BACKFLOW REQUIRED ON |
| | THE TRASH CHUTE RING. SEC 608.13.2 |
| | 27) SHT P-202 RELIEF VALVE DISCHARGE, |
| | (P/T) AND PAN DRAIN LINE SHALL DRAIN |
| | SEPARATELY. SECTION 504.7 - 504.7.1 |
| | 28) SHT P-202 RAIN WATER LEADER NOT SIZ- |
| | ED PROPERLY FOR HORIZONTAL OFFSETS. |
| | TABLE 1106.3 |
| | 29) SHT P-208.1 IDENTIFY ALL FIXTURES. |
| | BATHROOM BY RISER S/7B INDICATES KITCHEN |
| | SINK DRAINING THRU BATHROOM GROUP WET |
| | VENT, WHICH IS NOT ALLOWED PER SECTION |
| | 909.1. BATHROOM BY S/8, S/11, S/5 INDI- |
| | CATES LAV, BUT PIPED LIKE A TUB OR SHR. |
| | PLEASE CLAIRFY. 104.2.1 |
| | 30) SHT P-208.0 SHOW FIXTURE UNITS ADDED |
| | AT THE BASE OF EACH RISER, AND AS THEY |
| | ACCUMULATE IN THE SANT. SYSTEM TO CHECK |
| | THE PIPE SIZING OF BLDG DRAIN. 104.2.1 |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |