Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop P
Sequence Number 7
Notes
Date Text
2003-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS P-1.3 & P-208.0 RELIEF VENT RE-
 QUIRD FOR AAV IN TRASH ROOM. SEC 917.3.2
 2) SHT P-1.3 CLAIRFY THIRD RISER NEXT TO
 AAV AT TRASH ROOM. MAIN DRAIN ISOMETRIC
 DIAGRAM ONLY SHOWS 2/29 & S/33. SECTION
 104.2.1
 3) SHT P-3.1 IDENTIFY RISERS COL. LINE G
 SHT P-1.4 SHOWS S/3 AS CENTER RISER, BUT
 RISER DIAG. SHOWS S/8 AS CENTER RISER.
 PLEASE CLAIRFY. SEC 104.2.1
 4) SHT P-1.3 CLEANOUTS REQUIRED MINIMUM
 100'. SECTION 708.3.2
 5) SHTS P-1.4 & P-208.0 IDENTIFY RISER
 AT COL. LINE N.12. SECTION 104.2.1
 6) SHTS P-1.4 & P-208.0 SANT. RISER DOES
 NOT REFLECT THE FLOOR PLAN AT RISERS S/7
 S/7, S/3A, & S/1A. RISER SHOWS 2 RISERS,
 AND FLOOR PLAN SHOWS 1 RISER. PLEASE
 CLAIRFY. SECTION 104.2.1
 7) SHTS P-1.4 & P-208.0 RELIEF VENT REQ-
 UIRED FOR AAV IN FIRE PUMP ROOM. SECTION
 917.3.2
 8) SHT P-1.4 CLEANOUTS REQUIRED NEAR COL
 LINES S.7 & C AND S.20 & C. SEC 708.3.2.
 9) SHT P-1.5 CLEANOUT SHOWN ON RISER BUT
 NOT ON FLOOR PLAN NEAR COL. LINE S.43
 BETWEEN C & D. PLEASE CLAIRFY. 104.2.1
 10) SHTS P-1.5 & P-208.0 RISER DOES NOT
 REFLECT THE FLOOR PLAN AT TRASH ROOM.
 RISER SHOWS 2 RISERS AND NO AAV, FLOOR
 PLAN SHOWS SINGLE RISER WITH AN AAV.
 PLEASE CLAIRFY. 104.2.1 - RELIEF VENT
 REQUIRED FOR AAV. SEC 917.3.2
 11) SHT P-2.1 SANT. RISER NOT IDENTIFIED
 BETWEEN COLS. N.13 & N.14 BY STAIR #3.
 104.2.1
 12) MANY SHEETS, THE REVISION NUMBERS DO
 NOT MATCH REVISION CALLD OUT, AND MANY
 REVISIONS HAVE NO REV. NUMBER AT ALL.
 PLEASE CLAIRFY. 104.2.1
 13) MANY SHEETS SANT. RISER NUMBER IS
 SUPERIMPOSED OVER OTHER INFORMATION SO
 THE NUMBER CAN NOT BE READ. 104.2.1
 14) SHT P-2.2 STUDIOS 1, 2, & 3. SANT.
 RISERS, NEW RISERS ADDED AND SUPERIMPOS-
 ED OVER OLD RISER NUMBERS MAKING IT SO
 THE RISER NUMBERS CAN NOT BE READ.
 15) SHT P-6.2 REVISION 5 SHOWN. PLEASE
 CLAIRFY. 104.2.1
 16) SHT P-7.2 REVISION 2 SHOWN. IS THIS
 A NEW REVISION? PLEASE CLAIRFY. 104.2.1
 17) SHTS P-100 THRU P-119 INDICATE RISER
 NUMBERS FOR ALL UNITS. 104.2.1
 18) SHT P-119 STUDIO #6 SHOWS S/13A, &
 S/21. THESE RISERS ARE NOT FOUND ON THE
 RISER SHEETS. ALSO RISER S/5A SHOWS A
 KITCHEN SINK W/DISHWASHER, AND FLOOR
 PLAN SHOWS A TUB. PLEASE CLAIRFY. SECT-
 ION 104.2.1
 19) SHT P-208.0 SANITARY RISERS SHOWN UP
 TO S/17, BLDG DRAIN ISOMETRIC AND FLOOR
 PLAN SHEETS SHOW RISERS UP TO S/39. PRO-
 VIDE ALL MISSING SANT. RISER DIAGRAMS
 FOR REVIEW. SEC 104.2.1
 20) SHTS P-120, P-203, P-204, & P-205
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUFACTURE INSTALLATION INSTRUCTIONS.
 21) SHT P-200 OFFSET VENTS REQUIRED FOR
 SANT. RISERS S/1B, S/2C, & S/7A. SECTION
 915.
 22) SHT P-201, SHOW VENT SIZE FOR MAIN
 VENT FOR WASH MACHINES ON RISER S/17 PER
 TABLE 916.1.
 23) SHT P-200 SANT. RISERS S/2, S/2A, &
 S/2B, RELIEF VENTS REQUIRED FOR AAV'S
 BELOW THE 5TH FLOOR. SEC 917.3.2
 24) SHT P-200 SANT RISER S/1B RELIEF
 VENT REQUIRED FOR AAV BELOW 5TH FLOOR.
 SECTION 917.3.2
 25) SHT P-200 RISER S/5 NOT FOUND ON 1ST
 FLOOR BLDG DRAIN ISOMETRIC SHT P-208.0
 26) SHT P-202 RPZ BACKFLOW REQUIRED ON
 THE TRASH CHUTE RING. SEC 608.13.2
 27) SHT P-202 RELIEF VALVE DISCHARGE,
 (P/T) AND PAN DRAIN LINE SHALL DRAIN
 SEPARATELY. SECTION 504.7 - 504.7.1
 28) SHT P-202 RAIN WATER LEADER NOT SIZ-
 ED PROPERLY FOR HORIZONTAL OFFSETS.
 TABLE 1106.3
 29) SHT P-208.1 IDENTIFY ALL FIXTURES.
 BATHROOM BY RISER S/7B INDICATES KITCHEN
 SINK DRAINING THRU BATHROOM GROUP WET
 VENT, WHICH IS NOT ALLOWED PER SECTION
 909.1. BATHROOM BY S/8, S/11, S/5 INDI-
 CATES LAV, BUT PIPED LIKE A TUB OR SHR.
 PLEASE CLAIRFY. 104.2.1
 30) SHT P-208.0 SHOW FIXTURE UNITS ADDED
 AT THE BASE OF EACH RISER, AND AS THEY
 ACCUMULATE IN THE SANT. SYSTEM TO CHECK
 THE PIPE SIZING OF BLDG DRAIN. 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]