| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2004-03-04 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | ABOUT EM POWER ETC. | | | PLEASE SEE PLANS/RISER STILL INDICATE | | | EM GENERATOR. | | | | | | 2)NOTE: NO ALUM EQUIPMENT GRNDS/ BONDING | | | IS PERMITTED UNDER LOCAL AMENDMENTS. | | | 310.2(B)2 | | | | | | 3)NOTE: PLEASE CORRELATE RISER. | | | FIRE PUMP CONT SHOWN WITH ATS? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|