2004-02-24 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE BLDG REV FOR VAULT
 / ELECTRICAL ROOMS. PLEASE SEE 450.42
 FOR A MIN OF 3HR REATED WALLS.
 NO PIPING OF ANYKIND PERMITTED WITHIN
 3HR RATED WALLS.
 PLEASE PROVIDE INFORMATION ON STUCTURAL
 AND ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  