| Date |
Text |
| 2004-02-18 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: SHEETS E-117,118,119 HAD NOTES |
| | CORRECTED FOR SD' REQUIREMENTS,HOWEVER |
| | OTHER SHEETS REMAIN UNCHANGED? |
| | |
| | 2)NOTE: PLEASE SEE THERE ARE MANY OTHER |
| | SHEETS LABELED IN TITLE BLOCK AREA TO |
| | HAVE A VE REV AND DATED, HOWEVER PLANS |
| | ARE REQ'D TO BE IDENTIFIED WITH CLOUDS/ |
| | TRIANGLESTO INDICATE CHANGE. |
| | |
| | 3)NOTE: PLEASE CLARIFY: PLANS INDICATE |
| | ALL EM/EXT LTS STILL GOING TO EMERGENCY |
| | CIRCUITS. AS PER CONVERSATION WITH |
| | ENGINEER, THE GENERATOR/EMERGENCY BACK |
| | -UP SYSTEM WAS BEING PROPOSED FOR REMOVE |
| | -L. PLEASE NOTE: I HAVE SPOKEN TO ASST |
| | FIRE MARSHAL MIKE CARSILLO, AND THAT |
| | CONCLUSION HAS NOT YET BEEN FINALED BY |
| | THE FIRE MARSHALL'S OFFICE. |
| | IF NO BACK SYSTEM IS GOING TO BE PERMITT |
| | -ED, PLEASE ADJUST PLANS. |
| | |
| | 4)NOTE: |
| | PLEASE ALSO INCLUDE ADDRESS OF JOB IN |
| | TITLE BLOCK. FAC 61G1-16.004 |
| | THIS COMMENT IS FOR ALL TRADES WEATHER |
| | OR NOT COMMENT IS MADE. |
| | THIS WAS ALSO REQ'D AT THE TIME OF ORIG |
| | PERMIT,HOWEVER IT WAS NOT KNOWN TO THIS |
| | OFFICE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |