Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop P
Sequence Number 4
Notes
Date Text
2003-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND. 98 DESIGN MANUAL
  
 1) NEW PLUMBING SHEETS FOR REVIEW - NEW
 PLAN REVIEW.
 2) SHT P.208 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLAT LAYOUT ON SHTS P-1.0,
 P-1.1 & P-1.2. SOME RISERS NOT SHOWN ON
 RISER DIAGRAM. PLEASE CORRELATE RISER
 WITH FLAT LAYOUT.
 3) SHTS P-1.0, P-1. P-1.2 & P.208 -
 CLEANOUTS REQUIRED ON HORIZONTAL BLDG
 DRAIN. MAXIMUM 100' APART. SEC 708.3.1
 AND AT CHANGE OF DIRECTION GREATER THAN
 45 DEGREES. SEC 708.3.3. ALSO REQUIRED
 AT BASE OF STACK SEC 708.3.4
 4) SHT A.112A UNITS B7, & B71, SPECIFIC-
 ATION "A" OR "B" TO BE INDICATED.
 5) SHT A.113 UNITS B6, B61, & B62, CLEAR
 FLOOR SPACE NOT SHOWN.
 6) SHTS P-203, P-204, & P-205, AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DE-
 LETE FROM WATER RISER DIAGRAMS.
 7) PLEASE SUBMIT CALCULATIONS FOR CON-
 DENSATE DISCHARGE FOR EACH A/C UNIT TO
 ESTABLISH DRAINAGE FIXTURE UNITS FOR
 CONDENSATE PIPE SIZING.
 8) SANITARY RISERS S/17 & S/21, ONLY
 THE FIXTURES FROM THE BATHROOM GROUP
 SHALL DRAIN INTO THE WET VENT. TIE
 KITCHEN SINK DOWNSTREAM OF BATHROOM
 GROUP ON THESE RISERS.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377