| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-02-28 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.PLN SHEET AC-1.2, 18" X 12" O.A. | | | DUCT TO FCU-11 APPEARS TO PENETRATE A | | | RATED WALL, NO FIRE DAMPER INDICATED ON | | | PLAN. | | | | | | 2.PLANS INDICATE A DRYER BOOSTER FAN | | | IN SOME OF THE APARTMENTS. | | | A. PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE BOOSTER FAN. (UL LISTED) | | | B. PLEASE INDICATE WHAT KIND OF | | | PRECAUTIONS WILL BE TAKEN SHOULD | | | THE BOOSTER FAN FAIL. | | | | | | 3.PLEASE NOTE DRYERS TO BE INSTALLED | | | FOR FINAL INSPECTION. | | | | | | 4.FCU'S # 6,7,8, & 11, DUCT SMOKE | | | DETECTORS REQUIRED ON SUPPLY AIR DUCT | | | AS PER 2001 FBC(M) 606.2.1. (NO DUCT | | | SMOKE DETECTORS ARE IDENTIFIED ON PLAN) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|