| Date |
Text |
| 2003-02-19 00:00:00 | 1) SOME BUILDING FEATURES APPEAR TO |
| | HANG OVER THE PROPERTY LINE IN |
| | SEVERAL LOCALES. |
| | |
| | 2) THE RECOMMENDED ACCESSIBLE PARKING |
| | SPACE DETAIL IS ILLEGIBLE ON PAGE A.02. |
| | |
| | 3) THE COLUMN WITHIN STAIR # 5 IS NOT |
| | TO INTERFERE WITH ANY EXIT DISCHARGE. |
| | WHY IS THIS STAIR LABELED # 5. |
| | |
| | 4) THE ELECTRICAL ROOM DOORS NEAR |
| | ELEVATORS # 2 AND 3 APPEAR TO DECREASE |
| | THE EXIT HALLWAY BY 50 PERCENT. |
| | |
| | 5) THE BUILDING ADDRESS NOT SHOWN ON |
| | THE ELEVATION DRAWINGS. |
| | |
| | 6) HANDRAILS ARE REQUIRED AT MONUMENTAL |
| | STAIR LOCATIONS. |
| | |
| | 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | INFORMATION FOR 1/2 GALV.STEEL TENSION |
| | CABLES. |
| | |
| | 8) LIFE SAFETY PLAN LS-6 DOES NOT |
| | APPEAR TO CORRESPOND WITH LS-7. |
| | |
| | 9) LIFE SAFETY PLAN LS-2 SHOWS EXITING |
| | VIA A SOLID WALL ADJACENT TO TRAVEL |
| | DISTANCE 189. OTHER LS PLANS DISPLAY |
| | THE VERY SAME THING. |
| | |
| | 10) PLEASE SHOW TRAVEL DISTANCES FROM |
| | RECREATION AREAS. |
| | |
| | 11) NO COMBUSTIBLES ALLOWED IN ANY |
| | RETURN AIR PLENUMS. |
| | |
| | 12) AN EXIT SIGN APPEARS TO BE MISSING |
| | DIRECTLY IN FRONT OF STAIR # 5. |
| | |
| | 13) END OF LINE RESISTORS NOTED ON FIRE |
| | ALARM RISER DIAGRAMS. PLEASE BE ADVISED |
| | ONLY CLASS A, STYLE D OR FULLY |
| | ADDRESSABLE FIRE ALARM SYSTEMS WILL BE |
| | ALLOWED. |
| | |
| | 14) APARTMENTS USED FOR HANDICAPPED |
| | PERSONS SHALL BE EQUIPPED WITH HORN |
| | STROBES. |
| | |
| | 15) NO SMOKE DETECTOR IN ELECTRICAL |
| | ROOM NEAR ELEVATOR # 3. |
| | |
| | 16) THERE APPEARS TO BE AT LEAST THREE |
| | FIRE DEPARTMENT CONNECTIONS. TWO ARE |
| | ONLY NEEDED. AT LEAST ONE FIRE |
| | DEPARTMENT CONNECTION SHALL BE WITHIN |
| | 150 FEET OF A FIRE HYDRANT. |
| | |
| | 17) PLEASE PROVIDE PRESSURE REDUCING |
| | VALVES NOTED IN FP 201. |
| | |
| | 18) A 750 GPM FIRE PUMP IS NOT |
| | ACCEPTABLE. ONE STANDPIPE IS REQUIRED |
| | TO PROVIDE 500 GPM, AND 250 GPM FOR |
| | EACH ADDITIONAL STANDPIPE. EACH REQUIRED |
| | STAIRWELL IS REQUIRED TO HAVE A |
| | STANDPIPE. PLEASE REVISE THE DRAWINGS. |
| | ALSO A 6" PIPE CANNOT BE USED. A MINIMUM |
| | OF AT LEAST AN 8" PIPE IS TO BE USED. |
| | |
| | 19) THE FIRE SPRINKLER SYSTEM SHALL |
| | HAVE QUICK RESPONSE OR RESIDENTIAL |
| | SPRINKLER HEADS. |
| | |
| | 20) THE FIRE SPRINKLER PLANS SHALL |
| | CLEARLY INDICATE WHAT ROOMS THAT WILL |
| | NOT BE SPRINKLER PROTECTED. EXAMPLES |
| | COULD INCLUDE BATHROOMS AND CLOSETS. |
| | PLEASE ADVISE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |