Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2003-02-19 00:00:001) SOME BUILDING FEATURES APPEAR TO
 HANG OVER THE PROPERTY LINE IN
 SEVERAL LOCALES.
  
 2) THE RECOMMENDED ACCESSIBLE PARKING
 SPACE DETAIL IS ILLEGIBLE ON PAGE A.02.
  
 3) THE COLUMN WITHIN STAIR # 5 IS NOT
 TO INTERFERE WITH ANY EXIT DISCHARGE.
 WHY IS THIS STAIR LABELED # 5.
  
 4) THE ELECTRICAL ROOM DOORS NEAR
 ELEVATORS # 2 AND 3 APPEAR TO DECREASE
 THE EXIT HALLWAY BY 50 PERCENT.
  
 5) THE BUILDING ADDRESS NOT SHOWN ON
 THE ELEVATION DRAWINGS.
  
 6) HANDRAILS ARE REQUIRED AT MONUMENTAL
 STAIR LOCATIONS.
  
 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 INFORMATION FOR 1/2 GALV.STEEL TENSION
 CABLES.
  
 8) LIFE SAFETY PLAN LS-6 DOES NOT
 APPEAR TO CORRESPOND WITH LS-7.
  
 9) LIFE SAFETY PLAN LS-2 SHOWS EXITING
 VIA A SOLID WALL ADJACENT TO TRAVEL
 DISTANCE 189. OTHER LS PLANS DISPLAY
 THE VERY SAME THING.
  
 10) PLEASE SHOW TRAVEL DISTANCES FROM
 RECREATION AREAS.
  
 11) NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 12) AN EXIT SIGN APPEARS TO BE MISSING
 DIRECTLY IN FRONT OF STAIR # 5.
  
 13) END OF LINE RESISTORS NOTED ON FIRE
 ALARM RISER DIAGRAMS. PLEASE BE ADVISED
 ONLY CLASS A, STYLE D OR FULLY
 ADDRESSABLE FIRE ALARM SYSTEMS WILL BE
 ALLOWED.
  
 14) APARTMENTS USED FOR HANDICAPPED
 PERSONS SHALL BE EQUIPPED WITH HORN
 STROBES.
  
 15) NO SMOKE DETECTOR IN ELECTRICAL
 ROOM NEAR ELEVATOR # 3.
  
 16) THERE APPEARS TO BE AT LEAST THREE
 FIRE DEPARTMENT CONNECTIONS. TWO ARE
 ONLY NEEDED. AT LEAST ONE FIRE
 DEPARTMENT CONNECTION SHALL BE WITHIN
 150 FEET OF A FIRE HYDRANT.
  
 17) PLEASE PROVIDE PRESSURE REDUCING
 VALVES NOTED IN FP 201.
  
 18) A 750 GPM FIRE PUMP IS NOT
 ACCEPTABLE. ONE STANDPIPE IS REQUIRED
 TO PROVIDE 500 GPM, AND 250 GPM FOR
 EACH ADDITIONAL STANDPIPE. EACH REQUIRED
 STAIRWELL IS REQUIRED TO HAVE A
 STANDPIPE. PLEASE REVISE THE DRAWINGS.
 ALSO A 6" PIPE CANNOT BE USED. A MINIMUM
 OF AT LEAST AN 8" PIPE IS TO BE USED.
  
 19) THE FIRE SPRINKLER SYSTEM SHALL
 HAVE QUICK RESPONSE OR RESIDENTIAL
 SPRINKLER HEADS.
  
 20) THE FIRE SPRINKLER PLANS SHALL
 CLEARLY INDICATE WHAT ROOMS THAT WILL
 NOT BE SPRINKLER PROTECTED. EXAMPLES
 COULD INCLUDE BATHROOMS AND CLOSETS.
 PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910