| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE SD'S AHVE BEEN | | | REMOVED FROM INSIDE EACH SLEPPING RM OF | | | UNITS??? PLEASE SEE THAT SD'S ARE REQ'D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1 AND FBC 905.2 | | | ETC. | | | | | | 2)NOTE: PLEASE SEE MISSIG RECEPTS FOR | | | 2' OF WALL SPACE .E117,E118, E-119(STUD- | | | -IO 4).PLEASE SEE THAT ONE OF THE SETS | | | HAVE SOME REDLINED ON THESE PAGES. | | | | | | 3)NOTE: PLEASE SEE NOTE ON ALL PAGES FOR | | | UNITS: NOTE MENTIONS, SD TO BE 3' AWAY | | | FROM ALL A/C EQUIPMENT. PLEASE SEE THAT | | | NFPA-72 STIPULATES TO BE 3'FROM "SUPPLY' | | | REGISTERS. PLEASE SEE THAT SD'S ARE TO | | | BE 5' FROM RETURN AIR. PLEASE SEE SPECS | | | ON SD'S BEING INSTALLED. | | | | | | 4)NOTE: PLEASE SHOW/IDENTIFY ALL REV'S | | | BY CLOUDS ON PLANS. PLEASE SEE E201,202 | | | E203. | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | REVIEWERS THAT MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|