Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop E
Sequence Number 4
Notes
Date Text
2003-11-05 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SD'S AHVE BEEN
 REMOVED FROM INSIDE EACH SLEPPING RM OF
 UNITS??? PLEASE SEE THAT SD'S ARE REQ'D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1 AND FBC 905.2
 ETC.
  
 2)NOTE: PLEASE SEE MISSIG RECEPTS FOR
 2' OF WALL SPACE .E117,E118, E-119(STUD-
 -IO 4).PLEASE SEE THAT ONE OF THE SETS
 HAVE SOME REDLINED ON THESE PAGES.
  
 3)NOTE: PLEASE SEE NOTE ON ALL PAGES FOR
 UNITS: NOTE MENTIONS, SD TO BE 3' AWAY
 FROM ALL A/C EQUIPMENT. PLEASE SEE THAT
 NFPA-72 STIPULATES TO BE 3'FROM "SUPPLY'
 REGISTERS. PLEASE SEE THAT SD'S ARE TO
 BE 5' FROM RETURN AIR. PLEASE SEE SPECS
 ON SD'S BEING INSTALLED.
  
 4)NOTE: PLEASE SHOW/IDENTIFY ALL REV'S
 BY CLOUDS ON PLANS. PLEASE SEE E201,202
 E203.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  