| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-02-25 00:00:00 | SHEET A46A IMPROPERLY CALCULATES THE | | | RATIO OF WALL OPENINGS TO WALL AREA FOR | | | DETERMINATION OF COMPLIANCE WITH FBC | | | TABLE 600. | | | | | | THE WALL AREA IS MEASURED ON A PER | | | FLOORBASIS.WIDTH IS DETEMINED ALONG | | | THE WALL IN A SINGLE PLANE. | | | | | | THE HEIGHT IS MEASURED ON THE INTERIOR | | | FROM THE FINISH FLOOR TO THE CEILING | | | ABOVE. | | | | | | OPENINGS ARE DETERMINED BY THE ROUGH | | | OPENING DIMENSIONS. | | | | | | EACH FLOOR IN TURN, ALONG THE SOUTH | | | ELEVATION ON TANGLEWOOD CT. WHICH WALL | | | IS SETBACK EIGHTEEN FEET FROM THE | | | CENTERLINE DOES NOT COMPLY WITH FBC | | | TABLE 600 AS TO THE PERCENTAGE OF | | | OPENINGS ALLOWED. (20%) | | | | | | SHEET A88 SHOWS TWO WINDOWS OF | | | DIFFERING SIZE DESIGNATED AS TYPE "M" | | | | | | THE DOOR SHOWN AS #46 FOR THE CLUB HOUSE | | | IS REQUIRED TO BE FIRE RATED SINCE THE | | | EXTERIOR WALL IS LESS THAN FIFTEEN FEET | | | FROM THE PROPERTY LINE.SHOW THE FIRE | | | DESIGN NUMBER FOR THE 3 HOUR RATED WALL | | | ALSO.SEE FBC 705.1.1.2. | | | | | | SHEET S21.B, WHERE IS THE STRUCTURAL | | | SHEATHING FOR THE CLUBHOUSE ROOF? HOW | | | WILL IT BE ATTACHED?SEE FBC 104.2. |
|