2003-02-25 00:00:00SHEET A46A IMPROPERLY CALCULATES THE
 RATIO OF WALL OPENINGS TO WALL AREA FOR
 DETERMINATION OF COMPLIANCE WITH FBC
 TABLE 600.
  
 THE WALL AREA IS MEASURED ON A PER
 FLOORBASIS.WIDTH IS DETEMINED ALONG
 THE WALL IN A SINGLE PLANE.
  
 THE HEIGHT IS MEASURED ON THE INTERIOR
 FROM THE FINISH FLOOR TO THE CEILING
 ABOVE.
  
 OPENINGS ARE DETERMINED BY THE ROUGH
 OPENING DIMENSIONS.
  
 EACH FLOOR IN TURN, ALONG THE SOUTH
 ELEVATION ON TANGLEWOOD CT. WHICH WALL
 IS SETBACK EIGHTEEN FEET FROM THE
 CENTERLINE DOES NOT COMPLY WITH FBC
 TABLE 600 AS TO THE PERCENTAGE OF
 OPENINGS ALLOWED. (20%)
  
 SHEET A88 SHOWS TWO WINDOWS OF
 DIFFERING SIZE DESIGNATED AS TYPE "M"
  
 THE DOOR SHOWN AS #46 FOR THE CLUB HOUSE
 IS REQUIRED TO BE FIRE RATED SINCE THE
 EXTERIOR WALL IS LESS THAN FIFTEEN FEET
 FROM THE PROPERTY LINE.SHOW THE FIRE
 DESIGN NUMBER FOR THE 3 HOUR RATED WALL
 ALSO.SEE FBC 705.1.1.2.
  
 SHEET S21.B, WHERE IS THE STRUCTURAL
 SHEATHING FOR THE CLUBHOUSE ROOF? HOW
 WILL IT BE ATTACHED?SEE FBC 104.2.