| Date |
Text |
| 2003-01-06 00:00:00 | DENIED: |
| | |
| | RESPONSE FROM RJP DATED 10/23/02, ONLY |
| | ADDRESSES COMMENTS FROM NANCY DEMMARK |
| | DATED 8/20/02.COMMENTS FROM PATTY |
| | KRAUSS DATED 10/08/02 WHERE NOT |
| | ADDRESSED. |
| | |
| | 1.DRYER SCHEDULE ON PLAN SHEET AC-201 |
| | INDICATES MAXIMUM LENGTH AS 35 FT WITH |
| | 3 90 DEGREE BENDS, SOME UNITS AS SHOWN |
| | ON PLAN SHEET AC-116 ARE 36 TO 44 FT IN |
| | LENGTH WHICH EXCEEDS THE MAXIMUM LENGTH |
| | ALLOWED. |
| | |
| | 2.OUTSIDE AIR CALCULATIONS FOR THE |
| | APARTMENTS IS ACHIEVED THROUGH RTUS 1-7 |
| | WITH A TOTAL OF 23,800 CFM.CLARIFY |
| | HOW THE OUTSIDE AIR IS INTRODUCED INTO |
| | THE APARTMENT.PLANS DO NOT INDICATE |
| | ANY DUCTWORK OR SPECIFY HOW THE OUTSIDE |
| | AIR REQUIREMENT IS MET. |
| | |
| | 3.LIFE SAFETY PLAN SHEET 1 IS NOT |
| | CLEAR AS TO THE SEPARATION BETWEEN THE |
| | APARTMENT & THE COMMERICAL SPACE.PLAN |
| | DOES NOT INDICATE THE RATING OF THE |
| | CORRIDOR, REF. LINE I & N.3 ON LS-1. |
| | DUCTS DO NOT INDICATE FIRE DAMPER AT |
| | THE CORRIDOR PENETRATION TO FCU-11. |
| | |
| | 4.SHAFTS ARE NOT INDICATED ON MECH |
| | PLANS FIRE DAMPERS ARE SHOWN AT FLOOR |
| | PENTRATIONS, THIS IS ONLY ACCEPTABLE |
| | WHEN DUCT PENETRATES ONE FLOOR.IF |
| | DUCT PENETRATES MORE THAN ONE FLOOR A |
| | SHAFT ENCLOSURE IS REQUIRED AS PER 2001 |
| | FBC(M) 607.4.PLEASE INDICATE ALL SHAFT |
| | ENCLOSURES ON THE PLAN. |
| | |
| | PLEASE NOTE: |
| | ACCESS FOR FCU (HORIZONTAL) SHALL BE |
| | LARGE ENOUGH TO REMOVE THE LARGEST |
| | PIECE OF EQUIPMENT (COIL, FAN, MOTOR). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |