Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop M
Sequence Number 3
Notes
Date Text
2003-01-06 00:00:00DENIED:
  
 RESPONSE FROM RJP DATED 10/23/02, ONLY
 ADDRESSES COMMENTS FROM NANCY DEMMARK
 DATED 8/20/02.COMMENTS FROM PATTY
 KRAUSS DATED 10/08/02 WHERE NOT
 ADDRESSED.
  
 1.DRYER SCHEDULE ON PLAN SHEET AC-201
 INDICATES MAXIMUM LENGTH AS 35 FT WITH
 3 90 DEGREE BENDS, SOME UNITS AS SHOWN
 ON PLAN SHEET AC-116 ARE 36 TO 44 FT IN
 LENGTH WHICH EXCEEDS THE MAXIMUM LENGTH
 ALLOWED.
  
 2.OUTSIDE AIR CALCULATIONS FOR THE
 APARTMENTS IS ACHIEVED THROUGH RTUS 1-7
 WITH A TOTAL OF 23,800 CFM.CLARIFY
 HOW THE OUTSIDE AIR IS INTRODUCED INTO
 THE APARTMENT.PLANS DO NOT INDICATE
 ANY DUCTWORK OR SPECIFY HOW THE OUTSIDE
 AIR REQUIREMENT IS MET.
  
 3.LIFE SAFETY PLAN SHEET 1 IS NOT
 CLEAR AS TO THE SEPARATION BETWEEN THE
 APARTMENT & THE COMMERICAL SPACE.PLAN
 DOES NOT INDICATE THE RATING OF THE
 CORRIDOR, REF. LINE I & N.3 ON LS-1.
 DUCTS DO NOT INDICATE FIRE DAMPER AT
 THE CORRIDOR PENETRATION TO FCU-11.
  
 4.SHAFTS ARE NOT INDICATED ON MECH
 PLANS FIRE DAMPERS ARE SHOWN AT FLOOR
 PENTRATIONS, THIS IS ONLY ACCEPTABLE
 WHEN DUCT PENETRATES ONE FLOOR.IF
 DUCT PENETRATES MORE THAN ONE FLOOR A
 SHAFT ENCLOSURE IS REQUIRED AS PER 2001
 FBC(M) 607.4.PLEASE INDICATE ALL SHAFT
 ENCLOSURES ON THE PLAN.
  
 PLEASE NOTE:
 ACCESS FOR FCU (HORIZONTAL) SHALL BE
 LARGE ENOUGH TO REMOVE THE LARGEST
 PIECE OF EQUIPMENT (COIL, FAN, MOTOR).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.