2002-12-18 00:00:001) PLEASE EXPLAIN HOW PERSONS EXIT
 BETWEEN PARKED VEHICLES TO REACH THE
 EXIT DOOR WHERE TRAVEL DISTANCES HAVE
 BEEN OBTAINED. WHAT IS THE WIDTH THAT
 YOUR FIRM IS EXPECTING TO BE PRESENT
 BETWEEN THE PARKED VEHICLES.
  
 2) EXIT SIGNS ARE MISSING IN THE
 PARKING GARAGE ON THE ARCHITECTURAL
 DRAWINGS.
  
 3) DOOR SCHEDULE STILL CARRIES DOOR 72
 WITH PAINT INFORMATION. PLEASE REMOVE
 THE NOTE FROM THE DOOR SCHEDULE.
  
 4) ALL EXTERIOR DOORS ARE TO BE
 ACCESSIBLE TO FIRE RESCUE. LOCKING
 DEVICES ON EXIT DOORS SHALL COMPLY
 WITH DELAYED EGRESS OR ACCESS CONTROLLED
 EGRESS. IT IS IMPERATIVE THAT FIRE
 RESCUE PERSONNEL BE ABLE TO ACCESS
 THE BUILDING IN THE EVENT OF A MEDICAL
 EMERGENCY REGARDLESS OF THE STATUS
 OF THE FIRE ALARM SYSTEM. DUMMY LOCK
 INFORMATION PROVIDED WITH THE PLAN
 REVIEW NOTES STILL SEEM CONFUSING.
  
 5) GARAGE FD CONNECTION RISER ON A.80
 SHOWS A 2 1/2 FIRE DEPARTMENT CONNECTION
 ALL 2 1/2 HOSE CONNECTIONS EXCEPT THE
 FIRE DEPARTMENT CONNECTIONS SHALL HAVE
 1 1/2 REDUCERS ON THEM.
  
 6) TRAVEL DISTANCES IN THE BUILDING
 CODE AND THE FIRE CODE SHALL BE
 REVIEWED. IF TRAVEL DISTANCES ARE NOT
 THE SAME, THEN THE MOST RESTRICTIVE
 CODE WILL APPLY. PLEASE PROVIDE A
 CODE COMPARISON ON THE PLANS WITH
 REGARDS TO TRAVEL DISTANCES.
  
 7) ALL STAIRS AND RAMPS ARE REQUIRED
 TO HAVE HANDRAILS ON BOTH SIDES. THE
 AMENITY LEVEL LAYOUT PLAN ONLY DISPLAYS
 HANDRAILS ON ONE SIDE OF STAIRS.
  
 8) THE FIRE PUMP ROOM IS REQUIRED TO
 HAVE EMEREGNCY LIGHTING IN IT.
  
 9) NO FIRE LINE PIPING IS ALLOWED TO
 RUN UNDERNEATH THE BUILDING FOUNDATION.
  
 10) SOME MECHANICAL,ELECTRICAL COMMENTS
 NOT PROPERLY ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910