Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop B
Sequence Number 3
Notes
Date Text
2003-01-10 00:00:00SEE THE FOUNDATION PERMIT COMMENTS FOR
 1. THE THRESHOLD INSPECTION PLAN ISSUES
 NOT YET RESOLVED.
  
 2. THE PREVIOUS COMMENT RE: SITE
 ACCESSIBILITY ISSUES PERTAINS TO
 IMPROVEMENTS EFFECTING THE SIDEWALKS ON
 ALL FOUR SIDES, DROP OFF ZONES, TENANT
 SPACE ENTRANCES AND ANY OTHER PERTINENT
 INFORMATION, NOT JUST THE ARCADE.
  
 3. STAIR #1 DOES NOT COMPLY WITH
 CONDITION #1 OF FBC 1010, PARTICULARLY
 THE SECOND CLAUSE, "SUCH WAY BEING
 READILY VISIBLE AND IDENTIFIABLE FROM
 THE POINT OF EXIT DISCHARGE."
  
 4.
  
  
  
 5. AS PREVIOUSLY STATED, PLYWOOD ROOF
 SHEATHING IS NOT PERMITTED IN TYPE I
 CONSTRUCTION FOR USE AS A STRUCTURAL
 COMPONENT.THE ARCHITECT'S REFERENCE
 TOFBC 707.1 EXCEPTIONS, IS WITHOUT
 STANDING SINCE EXCEPTION 3 WHICH SPEAKS
 TO FRT CITES TABLE 600, WHICH IN TURN
 AT FOOTNOTE "E" APPLIES TO TWO STORY
 BUILDINGS, AND THE REFERENCE TO 609 IS
 APPLICABLE TO PARTITIONS.FURTHER, FRT
 IS NOT EQUIVALENT TO NON-COMBUSTIBLE.
 SEE FBC 202 DEFINITIONS.
  
 8. SEE THE FOUNDATION PERMIT COMMENTS
 REGARDING THE HC RAMP IN THE VALET
 LOBBY AREA.
  
 9.THE PREVIOUSLY NOTED METHOD FOR
 CALCULATING AREA FOR THE APPLICATION OF
 TABEL 600 REMAINS.THE "STATE"
 INTERPRETATION PROVIDED IS
 WITHOUTSTANDING. ALSO, THE REFERENCED
 SHEET A46A WAS NOT FOUND.
  
 10.MY PREVIOUS CHECKLIST REQUESTED
 FIRE RESISTANCE FOR THE EXTERIOR WALLS
 AS BEING IN THE CATEGORY OF BEARING
 WALLS.
 THE ARCHITECTS' RESPONSE IS THAT THEY
 ARE NON BEARING.PLEASE PROVIDE A
 SIGNED AND SEALED STATEMENT FROM THE
 STRUCTURAL ENGINEER OF RECORD THAT THEY
 ACT AS CURTAIN WALLS AND DO NOT SUPPORT
 OR TRANSMIT ANY GRAVITY LOADS.
  
 11. SHEET A62 SHOWS AN HC RAMP FOR THE
 RECREATION AREA BUT THE "HP" DRAWINGS
 REFERENCED IN THE ARCHITECT'S RESPONSE
 ARE NOT FOUND.
  
 12. PREVIOUSLY NOTED WAS THAT FOAM TRIM
 WAS NOT PERMITTED FOR EXTERIOR USE. IT
 WAS RESPONDED THAT THE TRIM IS
 "PRECAST"PRE CAST WHAT?CONCRETE?ARE
 THERE
 ANY DELEGATED DESIGN OR ATTACHMENT
 DETAILS?SEE FBC 104.2.
  
 13.THE REVISED FIRE RATED CEILING
 SECTIONS ON SHEET A64 IS LACKING SOME
 ATTACHMENT DETAILS.
  
 14.THE COMMENT REGARDING FIRE STOP
 SYSTEMS IS A CAVEAT.WHILE ALL OF THE
 SYSTEMS ARE UL LISTED, THERE ARE
 NUANCES INVOLVED WITH THEIR APPLICATION
 THAT MAY RESULT IN ADDITIONAL COST,
 TIME AND REWORK.
  
 15.PLEASE PROVIDE SIGNED, SEALED AND
 DATED SPECIFICATIONS.SEE FBC 104.2.
  
 16. DOOR 46 ON THE EAST SIDE OF THE
 FITNESS CENTER IS REQUIRED TO BE FIRE
 RATED AS IT IS LOCATED LESS THAN
 FIFTEEN FEET FROM A COMMON PROERTY LINE
 AND IS LOCATED IN AN EXTERIOR THREE
 HOUR RATED BEARING WALL.