| Date |
Text |
| 2003-01-10 00:00:00 | SEE THE FOUNDATION PERMIT COMMENTS FOR |
| | 1. THE THRESHOLD INSPECTION PLAN ISSUES |
| | NOT YET RESOLVED. |
| | |
| | 2. THE PREVIOUS COMMENT RE: SITE |
| | ACCESSIBILITY ISSUES PERTAINS TO |
| | IMPROVEMENTS EFFECTING THE SIDEWALKS ON |
| | ALL FOUR SIDES, DROP OFF ZONES, TENANT |
| | SPACE ENTRANCES AND ANY OTHER PERTINENT |
| | INFORMATION, NOT JUST THE ARCADE. |
| | |
| | 3. STAIR #1 DOES NOT COMPLY WITH |
| | CONDITION #1 OF FBC 1010, PARTICULARLY |
| | THE SECOND CLAUSE, "SUCH WAY BEING |
| | READILY VISIBLE AND IDENTIFIABLE FROM |
| | THE POINT OF EXIT DISCHARGE." |
| | |
| | 4. |
| | |
| | |
| | |
| | 5. AS PREVIOUSLY STATED, PLYWOOD ROOF |
| | SHEATHING IS NOT PERMITTED IN TYPE I |
| | CONSTRUCTION FOR USE AS A STRUCTURAL |
| | COMPONENT.THE ARCHITECT'S REFERENCE |
| | TOFBC 707.1 EXCEPTIONS, IS WITHOUT |
| | STANDING SINCE EXCEPTION 3 WHICH SPEAKS |
| | TO FRT CITES TABLE 600, WHICH IN TURN |
| | AT FOOTNOTE "E" APPLIES TO TWO STORY |
| | BUILDINGS, AND THE REFERENCE TO 609 IS |
| | APPLICABLE TO PARTITIONS.FURTHER, FRT |
| | IS NOT EQUIVALENT TO NON-COMBUSTIBLE. |
| | SEE FBC 202 DEFINITIONS. |
| | |
| | 8. SEE THE FOUNDATION PERMIT COMMENTS |
| | REGARDING THE HC RAMP IN THE VALET |
| | LOBBY AREA. |
| | |
| | 9.THE PREVIOUSLY NOTED METHOD FOR |
| | CALCULATING AREA FOR THE APPLICATION OF |
| | TABEL 600 REMAINS.THE "STATE" |
| | INTERPRETATION PROVIDED IS |
| | WITHOUTSTANDING. ALSO, THE REFERENCED |
| | SHEET A46A WAS NOT FOUND. |
| | |
| | 10.MY PREVIOUS CHECKLIST REQUESTED |
| | FIRE RESISTANCE FOR THE EXTERIOR WALLS |
| | AS BEING IN THE CATEGORY OF BEARING |
| | WALLS. |
| | THE ARCHITECTS' RESPONSE IS THAT THEY |
| | ARE NON BEARING.PLEASE PROVIDE A |
| | SIGNED AND SEALED STATEMENT FROM THE |
| | STRUCTURAL ENGINEER OF RECORD THAT THEY |
| | ACT AS CURTAIN WALLS AND DO NOT SUPPORT |
| | OR TRANSMIT ANY GRAVITY LOADS. |
| | |
| | 11. SHEET A62 SHOWS AN HC RAMP FOR THE |
| | RECREATION AREA BUT THE "HP" DRAWINGS |
| | REFERENCED IN THE ARCHITECT'S RESPONSE |
| | ARE NOT FOUND. |
| | |
| | 12. PREVIOUSLY NOTED WAS THAT FOAM TRIM |
| | WAS NOT PERMITTED FOR EXTERIOR USE. IT |
| | WAS RESPONDED THAT THE TRIM IS |
| | "PRECAST"PRE CAST WHAT?CONCRETE?ARE |
| | THERE |
| | ANY DELEGATED DESIGN OR ATTACHMENT |
| | DETAILS?SEE FBC 104.2. |
| | |
| | 13.THE REVISED FIRE RATED CEILING |
| | SECTIONS ON SHEET A64 IS LACKING SOME |
| | ATTACHMENT DETAILS. |
| | |
| | 14.THE COMMENT REGARDING FIRE STOP |
| | SYSTEMS IS A CAVEAT.WHILE ALL OF THE |
| | SYSTEMS ARE UL LISTED, THERE ARE |
| | NUANCES INVOLVED WITH THEIR APPLICATION |
| | THAT MAY RESULT IN ADDITIONAL COST, |
| | TIME AND REWORK. |
| | |
| | 15.PLEASE PROVIDE SIGNED, SEALED AND |
| | DATED SPECIFICATIONS.SEE FBC 104.2. |
| | |
| | 16. DOOR 46 ON THE EAST SIDE OF THE |
| | FITNESS CENTER IS REQUIRED TO BE FIRE |
| | RATED AS IT IS LOCATED LESS THAN |
| | FIFTEEN FEET FROM A COMMON PROERTY LINE |
| | AND IS LOCATED IN AN EXTERIOR THREE |
| | HOUR RATED BEARING WALL. |