| Date |
Text |
| 2002-10-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FHA AMEND-98 DESIGN MANUAL |
| | |
| | 1) PLANS FOR POOL TOILET ROOM FACILITIES |
| | WILL BE ROUTED TO THE HEALTH DEPT WHEN |
| | THE POOL PERMIT IS APPLIED FOR. |
| | 2) NO GREASE TRAP REQUIRED - CLICK CAFE |
| | IS ONLY A COFFEE HOUSE. NO FOOD SERVICE. |
| | 3) FROM PREVIOUS REVIEW: SHTS A.93 THRU |
| | A-116 ALL UNITS SHALL COMPLY WITH RE- |
| | QUIREMENTS 1 THRU 7 AND SPECIFY SPECIFI- |
| | CATION "A" OR "B" AS REQUIRED FOR EACH |
| | UNIT ON PLANS. FHA DESIGN MANUAL |
| | 4) FROM PREVIOUS REVIEW: SHT A.118 BACK- |
| | ING FOR TUBS AND SHOWERS SHALL COMPLY |
| | WITH FHA-98 DESIGN MANUAL. SHOW HEIGHT |
| | OFF FLOOR TO BOTTOM OF BACKING& HEIGHT |
| | & WIDTH OF ALL BACKING. |
| | 5) FROM PREVIOUS REVIEW: PLEASE INDICATE |
| | WHERE RISER (S/23) IS LOCATED. UNABLE TO |
| | LOCATE BACK TO BACK P-5'S SHOWN ON RISER |
| | DIAGRAM. |
| | 6) FROM PREVIOUS REVIEW: PLEASE SUBMIT A |
| | CONDENSATE RISER DIAGRAM FOR THE HORIZON |
| | TAL DRAIN AND RISERS. SHOW PIPE SIZES & |
| | TERMINATION. CONDENSATE SHALL TIE INTO |
| | THE STORM SYSTEM OR CATCH BASIN OUTSIDE |
| | THE BLDG. PLEASE SHOW REQUIRED RELIEF |
| | VENT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |