Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop M
Sequence Number 2
Notes
Date Text
2002-10-08 00:00:00DENIED:
  
 RESPONSE TO COMMENTS FROM 1ST PLAN
 REVIEW BY NANCY DENMARK:
  
 3. PROVIDE INFORMATION ON PARKING
 GARAGE. RES: REFER TO REVISED
 VENTILATION LAYOUT ON DRAWINGS.
 PLEASE CLARIFY WHAT IS EXHAUST AND
 WHAT IS AIR MAKE UP.
  
 4. PROVIDE OUTSIDE AIR CALCULATIONS FOR
 THE APARTMENTS. RES: O.A CALCS DWG
 AC-201.THE SCHEDULE SEEMS TO
 INDICATE O.A. SUPPLIED FROM THE RTU'S
 SERVING THE CORRIDOR?
  
 6. 50 CFM PER TOILET FIXTURE OR URINAL
 PER TABLE 403.3 FBC(M). RES: SEE
 REVISED VENTILATION FAN SCHEDULE, DWG
 AC-201. PLEASE NOTE, PLAN SHEET AC1.0
 INDICATES EF-1 FOR THE LOBBY RESTROOM
 & EQUIPMENT SCHEDULE ON PLAN SHEET
 AC-201 LIST EF 3 & 4. PLEASE CLARIFY.
  
 9. RES: EQUIPMENT CLEARANCE NOTES HAVE
 BEEN ADDED ON DWGS AC-1.0 & AC-2.0.
 THERE IS NO NOTE ON PLAN SHEET AC-2.0
  
 11.DRYER DUCT LENGTHS SHALL NOT EXCEED
 MANUFACTURERS SPECS OR 25'. RES:
 DRYER PERFORMANCE SPECIFICATION HAS
 BEEN REVISED. PLEASE NOTE:
 A. MANUFACTURER SUBMITTAL FOR A
 SPECIFIC DRYER WAS NOT SUBMITTED.
 B. SOME OF THE APARTMENTS HAVE 3 - 90
 DEGREE BENDS IN THE RUN. ACCORDING
 TO THE SCHEDULE THE LENGTH DOES
 NOT MEET THE SCHEDULE REQUIREMENT.
 C. PLAN SHEET AC-201 IN THE NOTE
 SECTION - NOTE #7 C. SUBPARAGRAPH
 E. STATES THE EXHAUST SHALL NOT
 EXCEED 25 FT.
  
 NEW NOTES BY PATTY KRAUSS
 1.O.A. DUCT TO FCU-11 PENETRATES A
 RATED WALL, ALSO THE SUPPLY & RETURN
 PENETRATING THE CORRIDOR WALL TO THE
 PACKAGE STO.- NO FIRE DAMPERS ARE
 SHOWN ON THE PLAN. PLEASE CLARIFY.
  
 2.CLARIFY 6" A.F.F. (3) 5'X3' 11,670
 CFM EACH, ARE THESE GRILLES GOING
 INTO A "SHAFT" ARE THEY EXHAUST OR
 FRESH AIR MAKE-UP?
  
 3.PLAN SHEET AC-1.1 DUCT PENETRATING
 "DOMESTIC WATER PUMP" ROOM - THESE
 WALLS HAVE A 2 HR RATING. NO DAMPER
  
 4.CLARIFY FIRE DAMPER AT THE FLOOR, IS
 THIS DUCT PENETRATING ONLY ONE FLOOR
 OR IN A SHAFT?
  
 5.PLEASE INDICATE ON MECHANICAL PLANS
 WHAT WILL BE RUN IN A RATED SHAFT
 I.E. DUCTS FROM RTU'S, REFRIGERATION
 LINES, PIPES, DUCTS, ETC.PLEASE
 PROVIDE A DETAIL AND UL# SHOWING
 CONTRUCTION OF SHAFT.SHOULD THE
 DETAIL BE SHOWN IN THE ARCHITECTURAL
 PLEASE REFERENCE THE PLAN SHEET.
  
 6.PLAN SHEET AC-202 ROOFTOP EQUIPMENT
 HEIGHT REQUIREMENT.SCHEDULE SHOWS
 THE HEIGHT REQUIREMENT MEASURING '
 THE LEG LENGTH OF THE STAND. THE
 CODE STATES FROM THE ROOF SURFACE.
 SEE 2001 FBC TABLE 1511.7.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR THE RTU'S SERVING THE
 COMMON CORRIDORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.