| 2002-10-08 00:00:00 | DENIED: |
| | |
| | RESPONSE TO COMMENTS FROM 1ST PLAN |
| | REVIEW BY NANCY DENMARK: |
| | |
| | 3. PROVIDE INFORMATION ON PARKING |
| | GARAGE. RES: REFER TO REVISED |
| | VENTILATION LAYOUT ON DRAWINGS. |
| | PLEASE CLARIFY WHAT IS EXHAUST AND |
| | WHAT IS AIR MAKE UP. |
| | |
| | 4. PROVIDE OUTSIDE AIR CALCULATIONS FOR |
| | THE APARTMENTS. RES: O.A CALCS DWG |
| | AC-201.THE SCHEDULE SEEMS TO |
| | INDICATE O.A. SUPPLIED FROM THE RTU'S |
| | SERVING THE CORRIDOR? |
| | |
| | 6. 50 CFM PER TOILET FIXTURE OR URINAL |
| | PER TABLE 403.3 FBC(M). RES: SEE |
| | REVISED VENTILATION FAN SCHEDULE, DWG |
| | AC-201. PLEASE NOTE, PLAN SHEET AC1.0 |
| | INDICATES EF-1 FOR THE LOBBY RESTROOM |
| | & EQUIPMENT SCHEDULE ON PLAN SHEET |
| | AC-201 LIST EF 3 & 4. PLEASE CLARIFY. |
| | |
| | 9. RES: EQUIPMENT CLEARANCE NOTES HAVE |
| | BEEN ADDED ON DWGS AC-1.0 & AC-2.0. |
| | THERE IS NO NOTE ON PLAN SHEET AC-2.0 |
| | |
| | 11.DRYER DUCT LENGTHS SHALL NOT EXCEED |
| | MANUFACTURERS SPECS OR 25'. RES: |
| | DRYER PERFORMANCE SPECIFICATION HAS |
| | BEEN REVISED. PLEASE NOTE: |
| | A. MANUFACTURER SUBMITTAL FOR A |
| | SPECIFIC DRYER WAS NOT SUBMITTED. |
| | B. SOME OF THE APARTMENTS HAVE 3 - 90 |
| | DEGREE BENDS IN THE RUN. ACCORDING |
| | TO THE SCHEDULE THE LENGTH DOES |
| | NOT MEET THE SCHEDULE REQUIREMENT. |
| | C. PLAN SHEET AC-201 IN THE NOTE |
| | SECTION - NOTE #7 C. SUBPARAGRAPH |
| | E. STATES THE EXHAUST SHALL NOT |
| | EXCEED 25 FT. |
| | |
| | NEW NOTES BY PATTY KRAUSS |
| | 1.O.A. DUCT TO FCU-11 PENETRATES A |
| | RATED WALL, ALSO THE SUPPLY & RETURN |
| | PENETRATING THE CORRIDOR WALL TO THE |
| | PACKAGE STO.- NO FIRE DAMPERS ARE |
| | SHOWN ON THE PLAN. PLEASE CLARIFY. |
| | |
| | 2.CLARIFY 6" A.F.F. (3) 5'X3' 11,670 |
| | CFM EACH, ARE THESE GRILLES GOING |
| | INTO A "SHAFT" ARE THEY EXHAUST OR |
| | FRESH AIR MAKE-UP? |
| | |
| | 3.PLAN SHEET AC-1.1 DUCT PENETRATING |
| | "DOMESTIC WATER PUMP" ROOM - THESE |
| | WALLS HAVE A 2 HR RATING. NO DAMPER |
| | |
| | 4.CLARIFY FIRE DAMPER AT THE FLOOR, IS |
| | THIS DUCT PENETRATING ONLY ONE FLOOR |
| | OR IN A SHAFT? |
| | |
| | 5.PLEASE INDICATE ON MECHANICAL PLANS |
| | WHAT WILL BE RUN IN A RATED SHAFT |
| | I.E. DUCTS FROM RTU'S, REFRIGERATION |
| | LINES, PIPES, DUCTS, ETC.PLEASE |
| | PROVIDE A DETAIL AND UL# SHOWING |
| | CONTRUCTION OF SHAFT.SHOULD THE |
| | DETAIL BE SHOWN IN THE ARCHITECTURAL |
| | PLEASE REFERENCE THE PLAN SHEET. |
| | |
| | 6.PLAN SHEET AC-202 ROOFTOP EQUIPMENT |
| | HEIGHT REQUIREMENT.SCHEDULE SHOWS |
| | THE HEIGHT REQUIREMENT MEASURING ' |
| | THE LEG LENGTH OF THE STAND. THE |
| | CODE STATES FROM THE ROOF SURFACE. |
| | SEE 2001 FBC TABLE 1511.7. |
| | |
| | 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | REQUIRED FOR THE RTU'S SERVING THE |
| | COMMON CORRIDORS. |
| | |