| 2002-09-26 00:00:00 | 1) PLEASE NOTE ON THE PLANS THAT THE |
| | BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS. COMPLIANCE WITH APPENDIX F |
| | OF THE LOCAL AMENDMENTS IS REQUIRED. |
| | |
| | 2) TRAVEL DISTANCES TO EXCEED THE |
| | MINIMUM CODE REQUIREMENTS. TRAVEL |
| | DISTANCES SHALL NOT EXCEED 200 FEET. |
| | THE LIFE SAFETY PLANS REVEAL TRAVEL |
| | DISTANCES IN EXCESS OF 200 FEET. |
| | |
| | 3) PULL STATIONS ARE NOT REQUIRED IN |
| | THE RETAIL SPACES LOCATED ON THE FIRST |
| | FLOOR. |
| | |
| | 4) TWO OF THE THREE EXITS DO NOT |
| | DIRECTLY EXIT TO THE INTERIOR. FIFTY |
| | PERCENT OF THE EXITS MUST EXIT DIRECTLY |
| | TO THE EXTERIOR. |
| | |
| | 5) END OF LINE RESISTORS NOTED ON FIRE |
| | ALARM RISER DIAGRAM. ONLY CLASS A, |
| | STYLE D CIRCUITS ARE ALLOWED. NO EOL'S |
| | ALLOWED IN THE FIELD. |
| | |
| | 6) ELECTRONIC SWITCHES ARE REQUIRED ON |
| | THE BACKFLOW DEVICES. |
| | |
| | 7) EXIT DISCHARGE FROM STAIR # 3 RUNS |
| | DIRECTLY INTO WATER METER AND TREE. |
| | |
| | 8) FIRE LINES ARE NOT PERMITTED TO BE |
| | RUN UNDERNEATH THE BUILDING. THE FDC |
| | IS TO BE WITHIN 150 FEET OF A FIRE |
| | HYDRANT. |
| | |
| | 9) DOORS SWING INWARD ON WEST SIDE OF |
| | GARAGE WHERE AN EXIT SIGN IS SHOWN. ARE |
| | THE DOOR SWINGS PROPER. |
| | |
| | 10) PARKING SPACES LOCATED DIRECTLY |
| | IN FRONT OF EXIT SIGNS IN PARKING |
| | GARAGE, THIRD LEVEL. |
| | |
| | 11) WHERE ARE THE EMERGENCY LIGHTS IN |
| | THE CORRIDORS. THE ELECTRICAL PLANS |
| | DISPLAY NIGHTLITES ONLY. |
| | |
| | 12) EXIT SIGN PLACEMENT CANNOT EXCEED |
| | 200 FEET. |
| | |
| | 13) PLEASE INDICATE ON THE PLANS THAT |
| | SMOKE DETECTORS ARE TO BE INSTALLED A |
| | MINIMUM OF AT LEAST THREE FEET FROM |
| | AIR CONDITIONER DIFFUSERS. |
| | |
| | 14) PLEASE EXPLAIN NOTE ON DOOR SCHEDULE |
| | WHICH INDICATES THAT A/C CLOSET DOORS |
| | WILL BE PAINTED WITH FIRE RETARDANT |
| | PAINT TO PROVIDE C LABEL RATING AS |
| | PER SFBC. THE SFBC IS NOT APPLICABLE. |
| | |
| | 15) PLEASE EXPLAIN KEYED HARDWARE |
| | LOCKSET OF STAIR DOORS. |
| | |
| | 16) PLEASE EXPLAIN NOTE ON LIFE SAFETY |
| | PLANS, MAGNETIC LOCKS TIED INTO FIRE |
| | ALARM SYSTEM. |
| | |
| | 17) NO ADDRESS FOR THE BUILDING COULD |
| | BE LOCATED ON THE ELEVATION DRAWINGS. |
| | |
| | 18) IT APPEARS THAT PORTIONS OF THE |
| | BUILDING EXTEND OVER THE PROPERTY LINE. |
| | |
| | 19) HOW DOES EXITING WORK IN THE GARAGE |
| | WHEN THE OVERHEAD SLIDE GATES ARE IN |
| | OPERATION. |
| | |
| | 20) WHAT PREVENTS PERSONS FROM BEING |
| | HIT BY CARS IN THE 12' ALLEY NEAR |
| | STAIR # 2. |
| | |
| | 21) NO INFORMATION PROVIDED ON GREASE |
| | REMOVAL FOR THE FUTURE GLICK CAFE. |
| | |
| | 22) MECHANICAL PLANS MUST INDICATE A |
| | MINIMUM OF AT LEAST SIX AIR CHANGES |
| | PER HOUR FOR THE GARAGE. |
| | |
| | 23) PLEASE REVIEW EXIT DISCHARGE |
| | CRITERIA, FBC, SECTION 1010. |
| | |
| | 24) PLEASE INDICATE WHICH ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 25) AN EXIT SIGN IS LOCATED WITHIN A |
| | ROOM IN THE GARAGE ON THE FOURTH LEVEL. |
| | |
| | 26) EXIT SIGNS ON THE FIFTH FLOOR |
| | ARE LOCATED BEYOND THE DOORS. |
| | |
| | 27) FIRST FLOOR EXITING FROM THE GARAGE |
| | IS CONFUSING. EXIT SIGNS APPEAR TO |
| | DIRECT PERSONS TOWARDS THE AREA WHERE |
| | A SECURITY GATE WILL BE LOCATED. PLEASE |
| | EXPLAIN. |
| | |
| | 28) EXIT SIGNS APPEAR TO BE MISSING |
| | ON THE FIRST FLOOR. |
| | |
| | 29) HANDRAILS FOR STAIRS APPEAR TO |
| | EXCEED THE PROPERTY LINES. |
| | |
| | 30) PLEASE EXPLAIN DUMMY LOCKS. THE |
| | FIRE RESCUE DEPARTMENT MAY NEED TO ENTER |
| | THE BUILDING WHEN THE FIRE ALARM SYSTEM |
| | IS NOT ACTIVATING. |
| | |
| | 31) PLEASE REVIEW SECTIONS OF THE CODE |
| | WITH REGARDS TO SECURITY DEVICES ON |
| | EXIT DOORS. |
| | |
| | 32) ALL MAINTENANCE ROOMS AND TRASH |
| | COLLECTION ROOMS ARE TO BE AT LEAST |
| | ONE HOUR SEPARATED WITH SPRINKLERS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |