2002-09-26 00:00:001) PLEASE NOTE ON THE PLANS THAT THE
 BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. COMPLIANCE WITH APPENDIX F
 OF THE LOCAL AMENDMENTS IS REQUIRED.
  
 2) TRAVEL DISTANCES TO EXCEED THE
 MINIMUM CODE REQUIREMENTS. TRAVEL
 DISTANCES SHALL NOT EXCEED 200 FEET.
 THE LIFE SAFETY PLANS REVEAL TRAVEL
 DISTANCES IN EXCESS OF 200 FEET.
  
 3) PULL STATIONS ARE NOT REQUIRED IN
 THE RETAIL SPACES LOCATED ON THE FIRST
 FLOOR.
  
 4) TWO OF THE THREE EXITS DO NOT
 DIRECTLY EXIT TO THE INTERIOR. FIFTY
 PERCENT OF THE EXITS MUST EXIT DIRECTLY
 TO THE EXTERIOR.
  
 5) END OF LINE RESISTORS NOTED ON FIRE
 ALARM RISER DIAGRAM. ONLY CLASS A,
 STYLE D CIRCUITS ARE ALLOWED. NO EOL'S
 ALLOWED IN THE FIELD.
  
 6) ELECTRONIC SWITCHES ARE REQUIRED ON
 THE BACKFLOW DEVICES.
  
 7) EXIT DISCHARGE FROM STAIR # 3 RUNS
 DIRECTLY INTO WATER METER AND TREE.
  
 8) FIRE LINES ARE NOT PERMITTED TO BE
 RUN UNDERNEATH THE BUILDING. THE FDC
 IS TO BE WITHIN 150 FEET OF A FIRE
 HYDRANT.
  
 9) DOORS SWING INWARD ON WEST SIDE OF
 GARAGE WHERE AN EXIT SIGN IS SHOWN. ARE
 THE DOOR SWINGS PROPER.
  
 10) PARKING SPACES LOCATED DIRECTLY
 IN FRONT OF EXIT SIGNS IN PARKING
 GARAGE, THIRD LEVEL.
  
 11) WHERE ARE THE EMERGENCY LIGHTS IN
 THE CORRIDORS. THE ELECTRICAL PLANS
 DISPLAY NIGHTLITES ONLY.
  
 12) EXIT SIGN PLACEMENT CANNOT EXCEED
 200 FEET.
  
 13) PLEASE INDICATE ON THE PLANS THAT
 SMOKE DETECTORS ARE TO BE INSTALLED A
 MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 14) PLEASE EXPLAIN NOTE ON DOOR SCHEDULE
 WHICH INDICATES THAT A/C CLOSET DOORS
 WILL BE PAINTED WITH FIRE RETARDANT
 PAINT TO PROVIDE C LABEL RATING AS
 PER SFBC. THE SFBC IS NOT APPLICABLE.
  
 15) PLEASE EXPLAIN KEYED HARDWARE
 LOCKSET OF STAIR DOORS.
  
 16) PLEASE EXPLAIN NOTE ON LIFE SAFETY
 PLANS, MAGNETIC LOCKS TIED INTO FIRE
 ALARM SYSTEM.
  
 17) NO ADDRESS FOR THE BUILDING COULD
 BE LOCATED ON THE ELEVATION DRAWINGS.
  
 18) IT APPEARS THAT PORTIONS OF THE
 BUILDING EXTEND OVER THE PROPERTY LINE.
  
 19) HOW DOES EXITING WORK IN THE GARAGE
 WHEN THE OVERHEAD SLIDE GATES ARE IN
 OPERATION.
  
 20) WHAT PREVENTS PERSONS FROM BEING
 HIT BY CARS IN THE 12' ALLEY NEAR
 STAIR # 2.
  
 21) NO INFORMATION PROVIDED ON GREASE
 REMOVAL FOR THE FUTURE GLICK CAFE.
  
 22) MECHANICAL PLANS MUST INDICATE A
 MINIMUM OF AT LEAST SIX AIR CHANGES
 PER HOUR FOR THE GARAGE.
  
 23) PLEASE REVIEW EXIT DISCHARGE
 CRITERIA, FBC, SECTION 1010.
  
 24) PLEASE INDICATE WHICH ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 25) AN EXIT SIGN IS LOCATED WITHIN A
 ROOM IN THE GARAGE ON THE FOURTH LEVEL.
  
 26) EXIT SIGNS ON THE FIFTH FLOOR
 ARE LOCATED BEYOND THE DOORS.
  
 27) FIRST FLOOR EXITING FROM THE GARAGE
 IS CONFUSING. EXIT SIGNS APPEAR TO
 DIRECT PERSONS TOWARDS THE AREA WHERE
 A SECURITY GATE WILL BE LOCATED. PLEASE
 EXPLAIN.
  
 28) EXIT SIGNS APPEAR TO BE MISSING
 ON THE FIRST FLOOR.
  
 29) HANDRAILS FOR STAIRS APPEAR TO
 EXCEED THE PROPERTY LINES.
  
 30) PLEASE EXPLAIN DUMMY LOCKS. THE
 FIRE RESCUE DEPARTMENT MAY NEED TO ENTER
 THE BUILDING WHEN THE FIRE ALARM SYSTEM
 IS NOT ACTIVATING.
  
 31) PLEASE REVIEW SECTIONS OF THE CODE
 WITH REGARDS TO SECURITY DEVICES ON
 EXIT DOORS.
  
 32) ALL MAINTENANCE ROOMS AND TRASH
 COLLECTION ROOMS ARE TO BE AT LEAST
 ONE HOUR SEPARATED WITH SPRINKLERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL