Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop E
Sequence Number 2
Notes
Date Text
2002-10-09 00:00:00***************** UNSAT **************
  
 1)NOTE: A FIXTURE SCHEDULE IS NOW
 SUBMITTED. PLEASE NOTE THAT THERE ARE
 FIXTURES IN HALLS ETC THAT NEED TO BE
 LABLED TO CORRELATE WITH SUBMITTED
 FIXTURE SCHEDULE. PLEASE NOTE SOME ARE
 SHOWN WITH WHAT APPEARS TO BE A CIRCUIT
 # AND DO NOT SEEM TO CORRELATE WITH THE
 PANEL SCHEDULE?
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 EMERGENCY LIGHTING CONCERNS.
 PLEASE NOTE 700-12 FOR BRANCH CIRCUITING
 PLEASE NOTE THERE ARE STILL NOTES ON
 E-11.0.11.1,11.2 THAT SHOW CIRCUIT #`S
 THAT DO NOT CORRELATE WITH PLAN LAYOUT?
  
 2)NOTE: PLEASE CLARIFY PAGE #`S CHANGING
 ? PLEASE CLARIFY IF WHAT USED TO BE
 16IS NOW 13?? ETC.
 PLEASE NOTE THAT THE REVISIONS ARE
 SHOWN/NOTED ON SIDE BUT NO TRIANLGES
 ARE SHOWN ON ANY OF THE PAGES THAT
 CHANGES WERE MADE?
  
 3)NOTE: IT IS NOTED THAT GFI`S WERE
 ADDED TO SOME PENINSULARS. PLEASE NOTE
 SOME UNITS ARE SHOWING MORETHAN ONE
 PENINSULAR?210-52C-3. IF 6" DOWN THEN
 COUNTERSPACE SHALL NOT EXCEED 6" OVER-
 HANG?
  
 4)NOTE: PLEASE NOTE SOME OUTLETS ARE
 STILL NOT BEING SHOWN WITHIN 6' OF DOOR?
 210-52 PLEASE CALL FOR THIS,CAN BE DONE
 AT FEILD INSPECTION, BUT SHOULD BE
 NOTED ON PLANS.
  
 5)NOTE: PLEASE CLARIFY RISER ONE-201
 DOES NOT SEEM TO CORRELATE W/ E-207?
 NOTE 8 BOTH RISERS? NOTE 8 MENTIONS
 1000A BUS TO WHICH 1000A DISC ON 207?
  
  
 6)NOTE; PLEASE NOTE PLANS/RISER STILL
 MISSING SOME EQUIPMENT GROUNDS.
 SIZE PER 250-122
  
  
  
  
 7)NOTE: PLEASE CLARIFY HOW FEED FROM
 FPL COMES DIRECTLY INTO EM MAIN, INSTEAD
 OF TRANSFER SWITCH?ON RISER DIAGRAM
 ON E-207?
  
 8)NOTE: PLEASE SEE E206, CLARIFY MAIN
 1 OF 6 SHOWN IN THE MIDDLE OF GENERATOR
 ROOM.???
  
 9)NOTE; PLEASE NOTE INFORMATION FOR
 OCP FOR FIR PUMP NOT SHOWN. PLEASE SEE
 695-4-B-1
  
 10)NOTE: PLEASE NOTE AICRATINGS ARE
 STILL MISSING ON SOME. 110-9/215-5
  
 11)NOTE: PLEASE SEE "S" PANELS FOR THE
 SAME COMMENT STILL STANDS FOR 50A OCP
 ON #14 AWG. CORRECTED ON ONE ONLY.
  
 12)NOTE: PLEASE NOTE STILL MISSING
 EQUIPMENT GROUNDING ON ONE-LINE.?
 SIZE PER 250-122
  
 13)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING FOR FEEDS TO UNITS.IT IS NOTED
 THAT FEEDERS ARE SHOWN ON E208.1
 CLARIFY EQUIP.GRND.
  
 14)NOTE: PLEASE SHOW WHERE ON ONE-LINE
 DOES IT SHOW FEED TO MC, SE 1/2 IS
 SHOWN.?
  
 15)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372