| 2002-10-09 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: A FIXTURE SCHEDULE IS NOW |
| | SUBMITTED. PLEASE NOTE THAT THERE ARE |
| | FIXTURES IN HALLS ETC THAT NEED TO BE |
| | LABLED TO CORRELATE WITH SUBMITTED |
| | FIXTURE SCHEDULE. PLEASE NOTE SOME ARE |
| | SHOWN WITH WHAT APPEARS TO BE A CIRCUIT |
| | # AND DO NOT SEEM TO CORRELATE WITH THE |
| | PANEL SCHEDULE? |
| | PLEASE SEE FIRE REVIEW COMMENTS FOR |
| | EMERGENCY LIGHTING CONCERNS. |
| | PLEASE NOTE 700-12 FOR BRANCH CIRCUITING |
| | PLEASE NOTE THERE ARE STILL NOTES ON |
| | E-11.0.11.1,11.2 THAT SHOW CIRCUIT #`S |
| | THAT DO NOT CORRELATE WITH PLAN LAYOUT? |
| | |
| | 2)NOTE: PLEASE CLARIFY PAGE #`S CHANGING |
| | ? PLEASE CLARIFY IF WHAT USED TO BE |
| | 16IS NOW 13?? ETC. |
| | PLEASE NOTE THAT THE REVISIONS ARE |
| | SHOWN/NOTED ON SIDE BUT NO TRIANLGES |
| | ARE SHOWN ON ANY OF THE PAGES THAT |
| | CHANGES WERE MADE? |
| | |
| | 3)NOTE: IT IS NOTED THAT GFI`S WERE |
| | ADDED TO SOME PENINSULARS. PLEASE NOTE |
| | SOME UNITS ARE SHOWING MORETHAN ONE |
| | PENINSULAR?210-52C-3. IF 6" DOWN THEN |
| | COUNTERSPACE SHALL NOT EXCEED 6" OVER- |
| | HANG? |
| | |
| | 4)NOTE: PLEASE NOTE SOME OUTLETS ARE |
| | STILL NOT BEING SHOWN WITHIN 6' OF DOOR? |
| | 210-52 PLEASE CALL FOR THIS,CAN BE DONE |
| | AT FEILD INSPECTION, BUT SHOULD BE |
| | NOTED ON PLANS. |
| | |
| | 5)NOTE: PLEASE CLARIFY RISER ONE-201 |
| | DOES NOT SEEM TO CORRELATE W/ E-207? |
| | NOTE 8 BOTH RISERS? NOTE 8 MENTIONS |
| | 1000A BUS TO WHICH 1000A DISC ON 207? |
| | |
| | |
| | 6)NOTE; PLEASE NOTE PLANS/RISER STILL |
| | MISSING SOME EQUIPMENT GROUNDS. |
| | SIZE PER 250-122 |
| | |
| | |
| | |
| | |
| | 7)NOTE: PLEASE CLARIFY HOW FEED FROM |
| | FPL COMES DIRECTLY INTO EM MAIN, INSTEAD |
| | OF TRANSFER SWITCH?ON RISER DIAGRAM |
| | ON E-207? |
| | |
| | 8)NOTE: PLEASE SEE E206, CLARIFY MAIN |
| | 1 OF 6 SHOWN IN THE MIDDLE OF GENERATOR |
| | ROOM.??? |
| | |
| | 9)NOTE; PLEASE NOTE INFORMATION FOR |
| | OCP FOR FIR PUMP NOT SHOWN. PLEASE SEE |
| | 695-4-B-1 |
| | |
| | 10)NOTE: PLEASE NOTE AICRATINGS ARE |
| | STILL MISSING ON SOME. 110-9/215-5 |
| | |
| | 11)NOTE: PLEASE SEE "S" PANELS FOR THE |
| | SAME COMMENT STILL STANDS FOR 50A OCP |
| | ON #14 AWG. CORRECTED ON ONE ONLY. |
| | |
| | 12)NOTE: PLEASE NOTE STILL MISSING |
| | EQUIPMENT GROUNDING ON ONE-LINE.? |
| | SIZE PER 250-122 |
| | |
| | 13)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING FOR FEEDS TO UNITS.IT IS NOTED |
| | THAT FEEDERS ARE SHOWN ON E208.1 |
| | CLARIFY EQUIP.GRND. |
| | |
| | 14)NOTE: PLEASE SHOW WHERE ON ONE-LINE |
| | DOES IT SHOW FEED TO MC, SE 1/2 IS |
| | SHOWN.? |
| | |
| | 15)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | THAT MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |