Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop B
Sequence Number 2
Notes
Date Text
2002-09-27 00:00:00SECOND PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 SEVERAL OF THE COMMENTS ON THE 8/16/02
 REVIEW HAVE NOT BEEN ADDRESSED.
  
 THRESHOLD BUILDING INFORMATION IS
 ABSENT SEE FBC 105.13.
  
 SHEET A.01 CITES A "FLORIDA CODE 2000
 EDITION".THE STATE INVOKES THE
 FLORIDA BUILDING CODE 2001. THERE ARE
 NUMEROUS REFERENCES THROUGHOUT THE
 PLANS TO THE S. FL. BUILDING CODE.THE
 PLANS AND SPECIFICATIONS SHOULD BE
 REVISED TO INCLUDE THE CODE IN EFFECT,
 FBC 2001, AND INSURE COMPLIANCE WITH
 SAME.
  
 SHOW THE SITE ACCESSIBILITY FOR THE
 HANDICAP.SEE FBC 11-4.1.2, CURB CUTS,
 MAIN ENTRANCE, COVERED ARCADE, TACTILE
 WARNING AREAS, ETC.
  
 STAIR #1 AS SHOWN ON SHEET A.01A DOES
 NOT COMPLY WITH FBC 1010, AS WAS NOTED
 ON THE PREVIOUS REVIEW.
  
 WALL SECTION C ON SHEET A56 IMPLIES
 THAT THE HIGHEST OCCUPIABLE FLOOR WILL
 EXCEED 75' ABOVE FIRE DEPARTMENT
 VEHICLE ACCESS AND THEREFORE MUST
 COMPLYWITH FBC 412.1.
  
 SEVERAL OF THE STAIRS ON SHEET A.21,
 (FIFTH LEVEL RECREATION AREA) SHOW
 HANDRAILS ON JUST ONE SIDE OF THE
 STAIRS.FBC 11-4.9.4 REQUIRES HANDRAILS
 ON BOTH SIDES.
  
 THE PLYWOOD ROOF SHEATHING SHOWN IN
 SECTION 1/A.30 AND ELSEWHERE, IS NOT
 ALLOWED IN TYPE I AND II CONSTRUCTION
 AS A STRUCTURAL COMPONENT.SEE FBC 603
  
 THE H.C. ACCESSIBLE RAMP SHOWN NEAR THE
 GALLERY/VALET AREA ON SHEET A.34 DOES
 NOT COMPLY WITH THE LANDING
 REQUIREMENTS OF FBC 11-4.8.4.
  
 SHEET A46A USES AN INCORRECT METHOD FOR
 CALCULATING TABLE 600. THE DISTANCE
 FROM FINISH FLOOR TO NEAREST CEILING IS
 THE HEIGHT TO BE USED ON A PER FLOOR
 BASIS.NOT THE ENTIRE BUILDING FACADE.
 PLEASE REVISE AS NECESSARY.
  
 NOTE #23 ON SHEET S-01 IMPLIES THE
 EXTERIOR MASONRY WALLS AS BEING
 BEARING, AND AS SUCH IS SUBJECT TO THE
 FIRE RESISTANCE REQUIREMENTS OF FBC T
 600 FOR BEARING WALLS AS A FUNCTION OF
 DISTANCE SEPARATION.
  
 SHOW THE EXTERIOR WALL FIRE RATINGS,
 INCLUDING THE FIRE DESIGN NUMBER, AND
 THE OPENING PROTECTIVE WHERE REQUIRED.
 INCLUDE THE FITNESS CENTER ON THE FIFTH
 LEVEL.
  
 SHOW THE HANDICAP ACCESSIBLE ROUTE
 THROUGH THE FIFTH LEVEL RECREATION AREA.
  
 SHEET A56 AND OTHERS SHOW THE USE OF
 FOAM TRIM.AS NOTED IN THE PREVIOUS
 COMMENTS, THIS IS PROHIBITTED BY FBC
 F102.2.7 AS AMENDED BY THE CITY, AS
 WELL AS FBC 1404.1.1.
  
 SHOW THE 1.5 HOUR FIRE RESISTANCE RATING
 METHOD FOR THE ROOF TRUSSES OF THE CLUB
 HOUSE IN ACCORDANCE WITH FBC TABLE 600.
  
 SHEET A65 CALLS OUT POWDER ACTUATED
 FASTENER WITH A MAX 1/4" PENETRATION TO
 SUPPORT THE SUSPENDED GYPSUM BOARD
 CEILING AND SIMILAR CONSTRUCTION.
 PROVIDE SPECIFIC PIN DIAMETER, SPACING
 AND ASSUMMED DESIGN LOADING TOGETHER
 WITH REFERENCE TESTING.SEE FBC 104.2.1
  
 SHEET A90 REFERENCES NFPA 5-2.1.5 FOR
 THE FIRE RATES DOORS.THERE IS NO
 5-2.1.5 IN THE 2000 EDITION OF NFPA
 101.FURTHER, FBC 705.1.3 INVOKES NFPA
 80, 1995 EDITION.ALSO, THE DOOR
 SCHEDULE DOES NOT CALL OUT THE REQUIRED
 FIRE RATED DOORS.
  
 SEVERAL OF THE FIRE STOP SYSTEMS CALLED
 ON SHEET LS-9 DO NOT HAVE THE T RATING
 REQUIRED BY FBC 705.5.1 & 705.6.1.2.
  
 THE MECHANICAL PLANS DO NOT SHOW THE
 MAKEUP AIR FOR THE GARAGE VENTILATION
 SYSTEM.WHAT LEVEL OF NOISE WILL THE
 EIGHT FANS PRODUCE?
  
 HOW WILL THE 7' HEIGHT REQUIRED BY FBC
 411.2.2 BE MAINTAINED UNDER THE 30"
 DEEP DUCT?
  
 THE ROOF OVERHANGS THE PROPERTY LINE TO
 THE EAST NEAR GRID LINES N AND N20 ON
 SHEET A 32. (STAIR #3)
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 "COVERED ARCADE" ALONG HIBISCUS ST.
 INCLUDE THE FIRE PROTECTION INFORMATION.
  
  
 SOME OF THE EXTERIOR STAIR HANDRAILS
 EXTEND INTO THE PUBLIC RIGHT OF WAY ON
 THE TANGLEWOOD CT SIDE (SOUTH)SEE FBC
 3206.1.
  
 THE SPECIFICATIONS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE SPECIALTY
 ENGINEERS WHEN SUBMITTED FOR PUBLIC
 RECORD.SEE FBC 104.2.2.
  
 PROVIDE A COPY OF THE SOIL REPORT
 MENTIONED IN THE SPECIFICATIONS AS
 APPENDIX A AND ON THE STRUCTURAL PLANS
 IN NOTE 10, OF THE GENERAL NOTES.
  
 SHEET S.O2 DEPICTS A TERRACE IN THE
 PUBLIC R.O.W.
  
 THE STRUCTURAL DETAILS FOR THE CLUBHOUSE
 FITNESS CENTER AND SWIMMING POOL ARE
 NOT READILY DISCERNIBLE ON THE
 STRUCTURALPLANS.
  
 SHOW THE DESIGN INFORMATION FOR THE
 VARIOUS RAILINGS TO BE USED THROUGHOUT
 THE BUILDING.SEE FBC 1608.2.
  
 SHOW HOW FBC 1606.1.4 WILL BE COMPLIED
 WITH.
  
 PROVIDE THE INFORMATION REQUIRED BY FBC
 160.1.7 INCLUDING THE COMPONENT AND
 CLADDING PRESSURES.


Account Summary | Usage Policy | Privacy Policy