| Plan Review Notes For Permit 02080563 |
| Permit Number |
02080563 |
|
| Review Stop |
E |
| Sequence Number |
18 |
|
| Notes |
| Date |
Text |
| 2005-07-29 00:00:00 | NEED TO CORRELATE DRAWINGS AND PANEL | | | SCHEDULES CIRCUITS SHOWN ON LAYOUTS OF | | | ROOMS NOT SHOWN ON PANEL SCHEDULES. | | | | | | PAGES 13.0,13.1,13.2 DO NOT SHOW ADDED | | | TRANSFORMERS ON A/C UP ON ROOF. | | | | | | PAGE 109 UNITS B1,B1.1,B1.2,B1.3,B1.4, | | | B1.5 ADDED OUTLETS ON KITCHEN COUNTER | | | MISSING FROM DRAWINGS. | | | | | | PAGE 208NOTE 20 AND ALL PANEL | | | SCHEDULES SHOW RACEWAYS NOT MC CABLES | | | PLEASE CHANGE NOTE AND PANEL SCHEDULES | | | TO SHOW WHAT IS INSTALLED. | | | | | | PAGE 207 NEED TO SHOW WIRE SIZES TO THE | | | FIRE PUMP FROM CONTROLER. NOT SHOWN. | | | | | | I DO NOT HAVE THE TIME TO LIST ALL | | | PROBLEMS THAT WE HAVE PLEASE LOOK AT THE | | | UNIT DRAWINGS AND THE PANEL SCHEDULES | | | THAT IS WHERE MOST OF THE PROBLEMS ARE!! |
|