2005-07-29 00:00:00NEED TO CORRELATE DRAWINGS AND PANEL
 SCHEDULES CIRCUITS SHOWN ON LAYOUTS OF
 ROOMS NOT SHOWN ON PANEL SCHEDULES.
  
 PAGES 13.0,13.1,13.2 DO NOT SHOW ADDED
 TRANSFORMERS ON A/C UP ON ROOF.
  
 PAGE 109 UNITS B1,B1.1,B1.2,B1.3,B1.4,
 B1.5 ADDED OUTLETS ON KITCHEN COUNTER
 MISSING FROM DRAWINGS.
  
 PAGE 208NOTE 20 AND ALL PANEL
 SCHEDULES SHOW RACEWAYS NOT MC CABLES
 PLEASE CHANGE NOTE AND PANEL SCHEDULES
 TO SHOW WHAT IS INSTALLED.
  
 PAGE 207 NEED TO SHOW WIRE SIZES TO THE
 FIRE PUMP FROM CONTROLER. NOT SHOWN.
  
 I DO NOT HAVE THE TIME TO LIST ALL
 PROBLEMS THAT WE HAVE PLEASE LOOK AT THE
 UNIT DRAWINGS AND THE PANEL SCHEDULES
 THAT IS WHERE MOST OF THE PROBLEMS ARE!!