Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop P
Sequence Number 14
Notes
Date Text
2005-06-27 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-120 ALL CHANGES MADE TO THE
 LAYOUT OF THE MEN'S AND WOMEN'S
 BATHROOMS SHALL BE REFLECTED IN A
 REVISION OF THE ARCHITECTURAL SHEETS.
 SECTION 104.2.1.
 2. SHT P-120 WATER PIPING ISOMETRIC:
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN FOR FIXTURE
 P-7. PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
 3. SHT P-120 WATER PIPING ISOMETRIC: THE
 DISCHARGE OF THE RELIEF VALVE SHALL NOT
 HAVE ANY TRAPPED SECTIONS, AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. SECTION 504.7.1
 4. THE STEAM GENERATORS SHALL BE
 INSTALLED IN A GALVANIZED STEEL OR OTHER
 METAL PAN OF EQUAL CORROSION RESISTANCE
 HAVING A MINIMUM THICKNESS OF 24 GUAGE.
 INDICATE THE PAN DRAIN PIPING ON
 REVISION. SECTION 504.8.
 5. INDICATE THE MATERIAL FOR THE RVD
 PIPING AND THE EMERGENCY PAN DRAIN FOR
 THE STEAM GENERATORS.
  
 REVIEW BY KEN STEVENS