| Notes |
| Date |
Text |
| 2005-06-27 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P-120 ALL CHANGES MADE TO THE | | | LAYOUT OF THE MEN'S AND WOMEN'S | | | BATHROOMS SHALL BE REFLECTED IN A | | | REVISION OF THE ARCHITECTURAL SHEETS. | | | SECTION 104.2.1. | | | 2. SHT P-120 WATER PIPING ISOMETRIC: | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AS SHOWN FOR FIXTURE | | | P-7. PDI-WH 201 & MANUF. INSTALLATION | | | INSTRUCTIONS. | | | 3. SHT P-120 WATER PIPING ISOMETRIC: THE | | | DISCHARGE OF THE RELIEF VALVE SHALL NOT | | | HAVE ANY TRAPPED SECTIONS, AND SHALL | | | HAVE A VISIBLE AIR GAP OR AIR GAP | | | FITTING LOCATED IN THE SAME ROOM AS THE | | | WATER HEATER. SECTION 504.7.1 | | | 4. THE STEAM GENERATORS SHALL BE | | | INSTALLED IN A GALVANIZED STEEL OR OTHER | | | METAL PAN OF EQUAL CORROSION RESISTANCE | | | HAVING A MINIMUM THICKNESS OF 24 GUAGE. | | | INDICATE THE PAN DRAIN PIPING ON | | | REVISION. SECTION 504.8. | | | 5. INDICATE THE MATERIAL FOR THE RVD | | | PIPING AND THE EMERGENCY PAN DRAIN FOR | | | THE STEAM GENERATORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|