Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop E
Sequence Number 14
Notes
Date Text
2004-12-29 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED DATED
 7/14/04
 SOME OF THESE NOTES STILL NEED TO BE
 ADDRESSED.
 PLEASE SUBMIT OTHER REVISED SHEETS FROM
 THE MOST CURRENT AND LATEST PLANS WHICH
 HAD COMMENTS FROM 7/14/04
 A REVIEW FOR CODE COMPLIANCE CAN NOT BE
 DONE UNTIL WE ARE ABLE TO VERIFY
 FEEDS/OCP/PANELS ETC.
 PLEASE PROVIDE REVISED PANEL SCHEDULES
 TO CORRELATE WITH RISER DIAGRAM.
  
 2)NOTE: PLEASE SEE NOTE#3 FROM 7/14/04.
 PLEASE SEE MAIN #6 ON RISER.
  
 3)NOTE: PLEASE SEE FEEDER NOTES: MANY
 HAVE CHANGED TO ALUM, SOME STILL SHOWN
 AS COPPER ON RISER. IT IS OUR
 UNDERSTANDING, THESE WERE ALL CHANGED TO
 ALUM DUE TO VE.?
  
 4)NOTE: PLEASE VERIFY LOAD SHEDDING
 UNIT. DOES THIS SHED THE LOAD FOR LIFT
 STATION?
  
  
 ** PLEASE ALSO NOTE: IT HAS NEVER BEEN
 SETTLED SINCE OUR LAST MEETING WHAT
 LOADS WILL BE ON EM POWER.
 THIS NEEDS TO BE SETTLED BY ALL PARTIES
 BEFORE IT BECOMES A FINAL/CO ISSUE.
  
  
 PLEASE SEE ANY POSSIBLE FIRE REVIEW
 COMMENTS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]