| 2004-06-08 00:00:00 | ************* UNSAT ****************** |
| | |
| | REVISION FOR HOUSE PANELS/ RISER/ |
| | GENERATOR/ LOAD CALCS ETC. |
| | |
| | 1)NOTE: PLEASE CORRELATE ALL PANELS ON |
| | PANEL SCHEDULES AND HOW THEY ARE |
| | LABELED |
| | ON OTHER PANEL SCHEDULES AND PLANS. |
| | PLEASE SEE ONE SET HAS SOME OF THESE |
| | ITEMS REDLINED. |
| | |
| | 2)NOTE: PLEASE SEE SOME PANEL |
| | SCHEDULES/ |
| | RISER/FEEDERS ETC HAS HAD CONDUCTOR |
| | SIZES CHANGE DUE TO VE ISSUES. PLEASE |
| | SEE SOME CONDUCTOR SIZES WERE INCREASED |
| | FOR ALUM/ 310.16 YET SOME |
| | CONDUCTOR/FEED |
| | -ERS SIZES WERE NOT CHANGED. IF THESE |
| | ARE TO REMAIN COPPER AS ORIG THEN THIS |
| | WOULD BE OK, BUT SEEMS MOST ALL FEEDERS |
| | HAVE BEEN CHANGED TO ALUM? |
| | PLEASE CLARIFY IF THIS IS INDEED THE |
| | CASE. IF SO, PLEASE ADJUST SOME |
| | FEEDERS. |
| | |
| | 3)NOTE: PLEASE CORRELATE E-206 AND 207 |
| | FOR DIST SECTION AND MCB'S SHOWN FOR |
| | OCP. |
| | |
| | 4)NOTE: PLEASE CLARIFY FEED FOR SECTION |
| | SE-1, SHOWS 400A ON RM LAYOUT PLANS AND |
| | RISER, HOWEVER SE-1/2? SHOWS 800A. IS |
| | THIS THE SAME? |
| | |
| | 5)NOTE: PLEASE SEE RISER SHOWS FEEDERS |
| | TO PKA AS #1 ALUM YET OCP ON PANEL |
| | SCHEDULE IS SHOWN AT 125A'S. PLEASE |
| | VERIFY. PLEASE SEE PREVIOUS NOTES FOR |
| | THIS ALSO ON THIS REVIEW. |
| | |
| | PLEASE SEE ONE SET OF THESE PLANS HAVE |
| | SOME OF THESE ITEMS REDLINED |
| | |
| | PLEASE CLARIFY GENERATOR SITUATION, AT |
| | LAST MEETING IT WAS MENTIONED THE FIRE |
| | PUMP AND ONE ELEVATOR WAS GOING TO |
| | REMAIN ON EM POWER? THIS REVISION DOES |
| | NOT SUPPORT THIS. |
| | PLEASE SUBMIT UPDATED PLANS DUE TO |
| | CHANGE IN OCCUPANCY AND IF EM POWER |
| | WILL |
| | BE PROVIDED FOR MORE THAN LIFT STATION. |
| | PLEASE ALSO SEE FIRE PLAN REVIEW FOR |
| | ANY |
| | POSSIBLE COMMENTS FOR THIS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |