Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE ROUTE PLANS TO THE PALM BEACH
 COUNTY HEALTH UNIT DIVISION OF ENVIRON-
 MENTAL HEALTH 901 EVERNIA STREET WPB
 (561) 355-3018 FOR REVIEW OF THE POOL
 BATHROOM FACILITIES.
 2) POOL SEPARATE PERMIT FOR POOL/PLUMB-
 ING AND ELECTRIC.
 3) BACKFLOW FOR ENTRANCE FOUNTAIN REQUIR
 ED.
 4) GREASE TRAP FOR FUTURE "CLICK CAFE"
 PLEASE CONTACT RODNEY COMPO, ENVIRONMEN-
 TAL COMPLIANCE MANAGER FOR SIZE OF TRAP.
 (561) 837-4074-WASTE ORD. #2938-96
 5) SHT A.62 POOL TANK DRAIN SHALL DRAIN
 TO SANITARY.
 6) PLEASE PROVIDE INFORMATION FOR POOL
 EQUIPMENT ROOM.
 7) SHT A.62 SUBMIT MANUF. INFO. FOR
 STEAM UNIT. SHOW PIPING FOR T/P RELIEF
 DRAIN.
 8) SHTS A.93 THRU A-116 ALL UNITS SHALL
 COMPLY WITH REQUIREMENTS 1 THRU 7 AND
 SPECIFY SPECIFICATION "A" OR "B" FOR
 EACH UNIT ON PLANS. FHA AMEND-98 DESIGN
 MANUAL.
 9) SHT A.118 BACKING FOR TUBS AND SHOW-
 ERS SHALL COMPLY WITH FHA-98 DESIGN MAN-
 UAL. SHOW HEIGHT OFF FLOOR TO BOTTOM &
 HEIGHT AND WIDTH OF ALL BACKING.
 10) SHT P-5.3 FOUNTAIN SHALL DRAIN TO
 SANITARY SYSTEM NOT TO STORM
 11) SHT P-115 UNIT B3 - 6' MAXIMUM DIS-
 TANCE FROM TRAP OF SHOWER TO VENT. TABLE
 906.1
 12) SHT P-117 5TH THRU 7TH & 8TH LEVEL
 FLOOR PLAN PIPING NOT SHOWN FOR C1 UNITS
 13) SHT P-120 PLEASE SUBMIT DETAIL FOR
 SHOWERS PER 11-4.21 AND ALL SUBSECTIONS.
 - WATER PIPE ISOMETRIC - WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" PER PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS
 NOT AT THE TOP OF DROP AS SHOWN.
 - PLEASE IDENTIFY FIXTURE P-7 - ITS NOT
 SHOWN ON SHT P-208 ON FIXTURE SCHEDULE.
 14) SHT P-200 SHTACK S/1, S/1A, & S/1C
 SHOWS P-4 (SHOWER) WITH DW DRAINING INTO
 THEM. PLEASE CLAIRFY. IF THEY ARE KITCH-
 EN SINKS, THEN 2" PIPE STACK IS NOT
 LARGE ENOUGH AND 3" IS REQUIRED. TABLE
 910.4
 15) SHTS P-4.2, P-5.0 (THREE SHEETS WITH
 SAME P NUMBER), SECOND AND THIRD, P-6.1,
 & P-7.1 DO NOT REFLECT THE SANITARY RIS-
 ER #23. RISER SHOWS BACK TO BACK TRAPS,
 BUT FLOOR PLAN DOES NOT REFLECT THIS.
 PLEASE CLAIRFY.
 16) SHTS P-102, P-103 & P-104 SHOW RISER
 S/23B, BUT NO RISER S/23B SHOWN ON RISER
 SHEETS.
 17) SHTS P-107 THRU P-119 PLEASE IDENTI-
 FY THE RISERS IN THESE UNITS.
 18) SHT P-117 NO PIPING LAYOUT SHOWN FOR
 UNITS C1A & C1A.2
 19) SHT P-203 WATER ISOMETRICS ALL UNITS
 AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMMER ARRESTORS ARE REQUIRED FOR ALL
 QUICK CLOSING VALVES PER SEC 604.9.
 (WASH MACHINES, ICE MAKERS (REFG.) &
 THE DISHWASHER.) THEY SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS AS SHOWN. PDI-WH
 201 & MANUF INSTALL. INSTRUCTIONS.
 20) SHT P-208 GENERAL PLUMBING NOTES:
 #1E 3" AND LARGER PIPE SHALL BE RUN AT
 1/8" PER FOOT AND 2-1/2" AND SMALLER
 PIPE SHALL BE RUN AT 1/8" PER FOOT. PER
 TABLE 704.1
 21) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM FOR THE BLDG DRAIN. SHOW ALL RISERS
 AND THE ACCUMULATED DFU'S, AND PIPE SIZE
 22) PLEASE PROVIDE A STORM RISER FOR THE
 HORIZONTAL DRAIN. SHOW ALL RISERS AND
 ACCUMULATED SQUARE FOOTAGE, AND SHOW
 PIPE SIZE.
 23) PLEASE PROVIDE A WATER RISER DIAGRAM
 WITH ALL PIPE SIZES. SHOW WHERE IT ENT-
 ERS THE BLDG AND ALL HORIZONTAL PIPING
 TO RISERS.
 24) PLEASE PROVIDE A CONDENSATE RISER
 DIAGRAM FOR THE CONDENSATE HORIZONTAL
 DRAIN. SHOW PIPE SIZES AND TERMINATION.
 COND. SHALL TIE INTO STORM OR CATCH
 BASIN OUTSIDE BLDG. RELIEF VENT REQD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377