| 2002-08-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) PLEASE ROUTE PLANS TO THE PALM BEACH |
| | COUNTY HEALTH UNIT DIVISION OF ENVIRON- |
| | MENTAL HEALTH 901 EVERNIA STREET WPB |
| | (561) 355-3018 FOR REVIEW OF THE POOL |
| | BATHROOM FACILITIES. |
| | 2) POOL SEPARATE PERMIT FOR POOL/PLUMB- |
| | ING AND ELECTRIC. |
| | 3) BACKFLOW FOR ENTRANCE FOUNTAIN REQUIR |
| | ED. |
| | 4) GREASE TRAP FOR FUTURE "CLICK CAFE" |
| | PLEASE CONTACT RODNEY COMPO, ENVIRONMEN- |
| | TAL COMPLIANCE MANAGER FOR SIZE OF TRAP. |
| | (561) 837-4074-WASTE ORD. #2938-96 |
| | 5) SHT A.62 POOL TANK DRAIN SHALL DRAIN |
| | TO SANITARY. |
| | 6) PLEASE PROVIDE INFORMATION FOR POOL |
| | EQUIPMENT ROOM. |
| | 7) SHT A.62 SUBMIT MANUF. INFO. FOR |
| | STEAM UNIT. SHOW PIPING FOR T/P RELIEF |
| | DRAIN. |
| | 8) SHTS A.93 THRU A-116 ALL UNITS SHALL |
| | COMPLY WITH REQUIREMENTS 1 THRU 7 AND |
| | SPECIFY SPECIFICATION "A" OR "B" FOR |
| | EACH UNIT ON PLANS. FHA AMEND-98 DESIGN |
| | MANUAL. |
| | 9) SHT A.118 BACKING FOR TUBS AND SHOW- |
| | ERS SHALL COMPLY WITH FHA-98 DESIGN MAN- |
| | UAL. SHOW HEIGHT OFF FLOOR TO BOTTOM & |
| | HEIGHT AND WIDTH OF ALL BACKING. |
| | 10) SHT P-5.3 FOUNTAIN SHALL DRAIN TO |
| | SANITARY SYSTEM NOT TO STORM |
| | 11) SHT P-115 UNIT B3 - 6' MAXIMUM DIS- |
| | TANCE FROM TRAP OF SHOWER TO VENT. TABLE |
| | 906.1 |
| | 12) SHT P-117 5TH THRU 7TH & 8TH LEVEL |
| | FLOOR PLAN PIPING NOT SHOWN FOR C1 UNITS |
| | 13) SHT P-120 PLEASE SUBMIT DETAIL FOR |
| | SHOWERS PER 11-4.21 AND ALL SUBSECTIONS. |
| | - WATER PIPE ISOMETRIC - WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIX- |
| | TURES IN AN "EFFECTIVE RANGE" PER PDI-WH |
| | 201 AND MANUF. INSTALLATION INSTRUCTIONS |
| | NOT AT THE TOP OF DROP AS SHOWN. |
| | - PLEASE IDENTIFY FIXTURE P-7 - ITS NOT |
| | SHOWN ON SHT P-208 ON FIXTURE SCHEDULE. |
| | 14) SHT P-200 SHTACK S/1, S/1A, & S/1C |
| | SHOWS P-4 (SHOWER) WITH DW DRAINING INTO |
| | THEM. PLEASE CLAIRFY. IF THEY ARE KITCH- |
| | EN SINKS, THEN 2" PIPE STACK IS NOT |
| | LARGE ENOUGH AND 3" IS REQUIRED. TABLE |
| | 910.4 |
| | 15) SHTS P-4.2, P-5.0 (THREE SHEETS WITH |
| | SAME P NUMBER), SECOND AND THIRD, P-6.1, |
| | & P-7.1 DO NOT REFLECT THE SANITARY RIS- |
| | ER #23. RISER SHOWS BACK TO BACK TRAPS, |
| | BUT FLOOR PLAN DOES NOT REFLECT THIS. |
| | PLEASE CLAIRFY. |
| | 16) SHTS P-102, P-103 & P-104 SHOW RISER |
| | S/23B, BUT NO RISER S/23B SHOWN ON RISER |
| | SHEETS. |
| | 17) SHTS P-107 THRU P-119 PLEASE IDENTI- |
| | FY THE RISERS IN THESE UNITS. |
| | 18) SHT P-117 NO PIPING LAYOUT SHOWN FOR |
| | UNITS C1A & C1A.2 |
| | 19) SHT P-203 WATER ISOMETRICS ALL UNITS |
| | AIR CHAMBERS ARE NOT APPROVED. WATER |
| | HAMMER ARRESTORS ARE REQUIRED FOR ALL |
| | QUICK CLOSING VALVES PER SEC 604.9. |
| | (WASH MACHINES, ICE MAKERS (REFG.) & |
| | THE DISHWASHER.) THEY SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE |
| | NOT AT THE TOP OF DROPS AS SHOWN. PDI-WH |
| | 201 & MANUF INSTALL. INSTRUCTIONS. |
| | 20) SHT P-208 GENERAL PLUMBING NOTES: |
| | #1E 3" AND LARGER PIPE SHALL BE RUN AT |
| | 1/8" PER FOOT AND 2-1/2" AND SMALLER |
| | PIPE SHALL BE RUN AT 1/8" PER FOOT. PER |
| | TABLE 704.1 |
| | 21) PLEASE PROVIDE A SANITARY RISER DIA- |
| | GRAM FOR THE BLDG DRAIN. SHOW ALL RISERS |
| | AND THE ACCUMULATED DFU'S, AND PIPE SIZE |
| | 22) PLEASE PROVIDE A STORM RISER FOR THE |
| | HORIZONTAL DRAIN. SHOW ALL RISERS AND |
| | ACCUMULATED SQUARE FOOTAGE, AND SHOW |
| | PIPE SIZE. |
| | 23) PLEASE PROVIDE A WATER RISER DIAGRAM |
| | WITH ALL PIPE SIZES. SHOW WHERE IT ENT- |
| | ERS THE BLDG AND ALL HORIZONTAL PIPING |
| | TO RISERS. |
| | 24) PLEASE PROVIDE A CONDENSATE RISER |
| | DIAGRAM FOR THE CONDENSATE HORIZONTAL |
| | DRAIN. SHOW PIPE SIZES AND TERMINATION. |
| | COND. SHALL TIE INTO STORM OR CATCH |
| | BASIN OUTSIDE BLDG. RELIEF VENT REQD. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |