Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-15 00:00:001) THE BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS AND CERTAIN RESTRICTIONS
 WILL APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 2) PLEASE INDICATE CONSTRUCTION TYPE FOR
 BUILDING.
  
 3) THE PARKING SPACES BY LEVEL TOTAL
 IS INCORRECT.
  
 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 6) A KNOX-BOX WILL BE REQUIRED.
  
 7) ALL SHAFTWAYS THAT PERSONS CAN FALL
 INTO SHALL BE MARKED "SHAFTWAY" IN
 RED LETTERS ON A WHITE BACKGROUND.
  
 8) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATION.
  
 9) STAIR # 2 DOOR ON THE UPPER FLOORS
 SWINGS IN THE WRONG DIRECTION.
  
 10) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 11) PLEASE INDICATE WHICH ELEVATORS
 MEET THE STRETCHER REQUIREMENTS PER THE
 FLORIDA BUILDING CODE, SECTION 3003.4.
  
 12) PLEASE DEMONSTRATE COMPLIANCE WITH
 FLORIDA BUILDING CODE, SECTION 3003.6.
  
 13) FABRIC AWNINGS ARE TO BE FIRE
 RATED.
  
 14) BUILDING ELEVATIONS APPEAR TO BE
 INCORRECT.
  
 15) PLEASE INDICATE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 16) PLANS REFLECT EXTERIOR GRADE
 PLYWOOD. AGAIN THE BUILDING IS LOCATED
 IN THE FIRE LIMITS, ONLY FIRE RATED
 PLYWOOD IS ALLOWED.
  
 17) PLEASE PROVIDE FLAME-SPREAD
 INFORMATION FOR SOUND WRAP FOR
 TRASH-CHUTE.
  
 18) IT APPEARS THAT ONE PARKING SPACE
 ON THE SECOND LEVEL INTERFERES WITH
 EXIT ACCESS FROM THE PARKING GARAGE.
  
 19) ARE THE EXIT DOORS FROM THE POOL
 LEVEL TO THE CORRIDOR SWINGING IN THE
 RIGHT DIRECTION.
  
 20) PLEASE PROVIDE INFORMATION FOR
 THE PARKING GARAGE. THE GARAGE IF
 CONSIDERED ENCLOSED, MUST HAVE
 MECHANICAL VENTILATION THAT PROVIDES
 AT LEAST SIX AIR CHANGES PER HOUR.
  
 21) PLEASE INDICATE ON THE DRAWINGS
 OTHER BUILDINGS THAT ARE IN CLOSE
 PROXIMITY TO THE SUBJECT BUILDING.
  
 22) WILL THE CLICK CAFE BE USING GREASE
 DUCTS AND IF SO WHERE WILL THEY
 TERMINATE.
  
 23) IT APPEARS THAT SOME HANDRAILS
 ARE OVER THE BUILDING'S PROPERTY LINE.
  
 24) PLEASE DEMONSTRATE COMPLIANCE THAT
 ALL ELEVATOR EQUIPMENT ROOMS HAVE
 INDEPEDENT VENTILATION OR AIR
 CONDITIONING.
  
 25) MANUAL PULL STATIONS ARE NOT
 REQUIRED IN MERCANTILE OCCUPANCIES IF
 FIRE SPRINKLER PROTECTED.
  
 26) NO FLOW OR TAMPER SWITCHES SHOWN
 ON FIRE ALARM DRAWINGS.
  
 27) A MANUAL PULL STATION WAS OBSERVED
 IN THE MIDDLE OF SOME PARKING SPACES.
  
 28) WHERE IS THE MAIN FIRE ALARM CONTROL
 PANEL LOCATED FOR THE BUILDING.
  
 29) PLEASE REVIEW TRAVEL DISTANCES TO
 EXITS IN THE FLORIDA FIRE CODE. ALSO
 IT APPEARS THAT TWO OUT OF THE THREE
 EXIT STAIRS DISCHARGE DIRECTLY INTO
 THE BUILDING. PLEASE EXPLAIN HOW THIS
 MEETS THE 50 PERCENT RULE.
  
 30) PLEASE INDICATE FIRE STANDPIPE
 LOCATIONS. ALL PORTIONS OF THE BUILDING
 MUST BE REACH WITH 100 FEET OF HOSE
 AND 30 FEET OF NOZZLE SPRAY.
  
 31) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 32) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 33) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED WHEN THE BUILDING REACHES
 THREE FLOORS OR THIRTY FEET IN HEIGHT.
  
 34) PLEASE PROVIDE EXIT DISCHARGE
 INFORMATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910