| 2002-08-15 00:00:00 | 1) THE BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS AND CERTAIN RESTRICTIONS |
| | WILL APPLY. PLEASE SEE APPENDIX F, LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE. |
| | |
| | 2) PLEASE INDICATE CONSTRUCTION TYPE FOR |
| | BUILDING. |
| | |
| | 3) THE PARKING SPACES BY LEVEL TOTAL |
| | IS INCORRECT. |
| | |
| | 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 5) SUITABLE ROADS ARE TO BE PROVIDED |
| | FOR FIRE AND PARAMEDICAL EQUIPMENT |
| | DURING CONSTRUCTION. |
| | |
| | 6) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 7) ALL SHAFTWAYS THAT PERSONS CAN FALL |
| | INTO SHALL BE MARKED "SHAFTWAY" IN |
| | RED LETTERS ON A WHITE BACKGROUND. |
| | |
| | 8) SITE PLAN DOES NOT INDICATE FIRE |
| | HYDRANT LOCATION. |
| | |
| | 9) STAIR # 2 DOOR ON THE UPPER FLOORS |
| | SWINGS IN THE WRONG DIRECTION. |
| | |
| | 10) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. |
| | |
| | 11) PLEASE INDICATE WHICH ELEVATORS |
| | MEET THE STRETCHER REQUIREMENTS PER THE |
| | FLORIDA BUILDING CODE, SECTION 3003.4. |
| | |
| | 12) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | FLORIDA BUILDING CODE, SECTION 3003.6. |
| | |
| | 13) FABRIC AWNINGS ARE TO BE FIRE |
| | RATED. |
| | |
| | 14) BUILDING ELEVATIONS APPEAR TO BE |
| | INCORRECT. |
| | |
| | 15) PLEASE INDICATE PRESCRIPTIVE CODE |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 16) PLANS REFLECT EXTERIOR GRADE |
| | PLYWOOD. AGAIN THE BUILDING IS LOCATED |
| | IN THE FIRE LIMITS, ONLY FIRE RATED |
| | PLYWOOD IS ALLOWED. |
| | |
| | 17) PLEASE PROVIDE FLAME-SPREAD |
| | INFORMATION FOR SOUND WRAP FOR |
| | TRASH-CHUTE. |
| | |
| | 18) IT APPEARS THAT ONE PARKING SPACE |
| | ON THE SECOND LEVEL INTERFERES WITH |
| | EXIT ACCESS FROM THE PARKING GARAGE. |
| | |
| | 19) ARE THE EXIT DOORS FROM THE POOL |
| | LEVEL TO THE CORRIDOR SWINGING IN THE |
| | RIGHT DIRECTION. |
| | |
| | 20) PLEASE PROVIDE INFORMATION FOR |
| | THE PARKING GARAGE. THE GARAGE IF |
| | CONSIDERED ENCLOSED, MUST HAVE |
| | MECHANICAL VENTILATION THAT PROVIDES |
| | AT LEAST SIX AIR CHANGES PER HOUR. |
| | |
| | 21) PLEASE INDICATE ON THE DRAWINGS |
| | OTHER BUILDINGS THAT ARE IN CLOSE |
| | PROXIMITY TO THE SUBJECT BUILDING. |
| | |
| | 22) WILL THE CLICK CAFE BE USING GREASE |
| | DUCTS AND IF SO WHERE WILL THEY |
| | TERMINATE. |
| | |
| | 23) IT APPEARS THAT SOME HANDRAILS |
| | ARE OVER THE BUILDING'S PROPERTY LINE. |
| | |
| | 24) PLEASE DEMONSTRATE COMPLIANCE THAT |
| | ALL ELEVATOR EQUIPMENT ROOMS HAVE |
| | INDEPEDENT VENTILATION OR AIR |
| | CONDITIONING. |
| | |
| | 25) MANUAL PULL STATIONS ARE NOT |
| | REQUIRED IN MERCANTILE OCCUPANCIES IF |
| | FIRE SPRINKLER PROTECTED. |
| | |
| | 26) NO FLOW OR TAMPER SWITCHES SHOWN |
| | ON FIRE ALARM DRAWINGS. |
| | |
| | 27) A MANUAL PULL STATION WAS OBSERVED |
| | IN THE MIDDLE OF SOME PARKING SPACES. |
| | |
| | 28) WHERE IS THE MAIN FIRE ALARM CONTROL |
| | PANEL LOCATED FOR THE BUILDING. |
| | |
| | 29) PLEASE REVIEW TRAVEL DISTANCES TO |
| | EXITS IN THE FLORIDA FIRE CODE. ALSO |
| | IT APPEARS THAT TWO OUT OF THE THREE |
| | EXIT STAIRS DISCHARGE DIRECTLY INTO |
| | THE BUILDING. PLEASE EXPLAIN HOW THIS |
| | MEETS THE 50 PERCENT RULE. |
| | |
| | 30) PLEASE INDICATE FIRE STANDPIPE |
| | LOCATIONS. ALL PORTIONS OF THE BUILDING |
| | MUST BE REACH WITH 100 FEET OF HOSE |
| | AND 30 FEET OF NOZZLE SPRAY. |
| | |
| | 31) SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER SYSTEM. |
| | |
| | 32) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. |
| | |
| | 33) TEMPORARY STANDPIPE SYSTEMS ARE |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE FLOORS OR THIRTY FEET IN HEIGHT. |
| | |
| | 34) PLEASE PROVIDE EXIT DISCHARGE |
| | INFORMATION. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |