Text |
| 2002-08-21 00:00:00 | ***************** UNSAT ************* |
| | |
| | PLEASE NOTE THAT PLANS ARE NOT COMPLETE |
| | ENOUGH FOR FULL REVIEW AND THERE MAY BE |
| | OTHER COMMENTS TO FOLLOW. |
| | |
| | 1)NOTE: PLEASE NOTE THAT NO LIGHTING |
| | FIXTURE SCHEDULE WAS SUBMITTED FOR |
| | REVIEW AND TO CORRELATE WITH LIGHTING |
| | PLANS SUBMITTED. |
| | |
| | 2)NOTE: PLEASE CLARIFY REQ`MENTS FOR |
| | 700-16 FOR ELEVATOR RMS AND ANY OTHER |
| | AREAS THAT ONLY CONTAIN ONE FIXTURE FOR |
| | ILLUMINATION. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NOTE ON E-9.0 |
| | MENTIONS TO SEE 1/4" SCALE ON,,,,PLEASE |
| | INDICATE WHER TO FIND ON PLAN. WHEN |
| | PLANS WERE REVIEW PAGE WAS FOUND, PLEASE |
| | NOTE PAGE ON E-9. |
| | |
| | 4)NOTE: PLEASE NOTE E-9.1 SHOWS ELEC- |
| | -TRICAL PLAN FOR PIT BUT NOTHING SHOWN? |
| | PLEASE SHOW ANY LIGHTING/PUMP/GFI RECEPT |
| | THAT MAY BE REQ`D PER NEC. |
| | |
| | 5)NOTE: PLEASE NOTE OUTLET SPACING IN |
| | MASTER BEDROOMS IN SOME UNITS FOR RECEPT |
| | -S WITHIN 6' OF DOOR. 210-52 |
| | |
| | 6)NOTE: PLEASE NOTE ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE ARE TO SHOWN AS |
| | GFI/GFI PROTECTED. PLEASE NOTE THAT THIS |
| | IS REQ`D OF ALL KITCHEN PENINSULARS AND |
| | ISLAND RECPETS. 210-8-A-6. |
| | |
| | 7)NOTE: PLEASE NOTE SOME APT UNITS WITH |
| | SAME LAYOUT ARE SHOWN MORETHAN ONCE. |
| | PLEASE VERIFY . |
| | |
| | 8)NOTE: PLEASE NOTE THAT ON 14.1 A NOTE |
| | BOX IS SET UP FOR CIRCUITING FOR |
| | CORRIDOR LIGHTING. PLEASE NOTE FOR OTHER |
| | CIRCUITING OF OTHER LTS ON OTHER FLOORS. |
| | |
| | 9)NOTE: PLEASE SEE KEY NOTES SET FORTHON |
| | E 16.0 ETC NOTE #`S 3&4. PLEASE NOTE |
| | THOSE PARTICULAR NOTES ARE NOT SHOWN ON |
| | PLANS/SHEETS REFERENCED. |
| | |
| | 10)NOTE: PLEASE NOTE THAT KEY NOTES ARE |
| | PLACED ON E205 THAT NEED TO BE ON E203, |
| | E201 IN ORDER TO CORRELATE W/ 207. |
| | |
| | 11)NOTE: PLEASE NOTE; PER ART 230-70-A |
| | OF LOCAL AMENDMENTS. NO MORETHAN 8' OF |
| | UNPROTECTED CONDUCTORS INSIDE THE BLDG. |
| | PLEASE NOTE FEEDS COMING INTO 5 OF 6 AND |
| | METERCENTER 4 OF 6. |
| | |
| | 12)NOTE: PLEASE NOTE PANEL SCHEDULE FOR |
| | PKV SHOWS CIRCUIT TO POOL PANEL AS PANEL |
| | "DD".MISPRINT? PLEASE CORRECT. |
| | |
| | 13)NOTE: PLEASE NOTE THAT 1600 EM MAIN |
| | IS SHOWN FEEDING PANEL PKV? PLEASE |
| | CLARIFY. PLEASE NOTE THAT EM MAIN IS |
| | ONLY SHOWN AS A DISCONNECT. |
| | |
| | 14)NOTE: PLEASE SHOW A DETAIL OVERVIEW |
| | OF MAIN ELECTRICAL ROOM, GENERATOR RM |
| | FIRE PUMP ROOM. PLEASE ALSO NOTE ROOM |
| | SEPARATION ON ONE-LINE RISER DIAGRAM. |
| | |
| | 15)NOTE: PLEASE PROVIDE NOTE FOR LABEL- |
| | -ING OF MAIN AND SERVICES FOR EQUIPMENT |
| | AND ON DOORS OF TWO MAIN ELECTRICAL |
| | ROOMS. 230-2-E |
| | |
| | 16)NOTE: PLEASE NOTE THAT ONE-LINE SHOWS |
| | PANEL 1HA AS 2HA. MISPRINT? PLEASE |
| | CORRECT. |
| | |
| | 17)NOTE: PLEASE NOTE THAT OCP AND WIRE |
| | SIZES NEED TO CORRELATE ON SHEETS FOR |
| | EDP-2 600A/#1, 500A/#4, 400A/#6 ETC. |
| | PLEASE SEE EDP-1 ALSO FOR CORRELATION |
| | OF OCP/WIRE. |
| | |
| | 18)NOTE:PLEASE NOTE MISSING TECHNICAL |
| | INFORMATION FOR PANEL ECH. NOTHING SHOWN |
| | |
| | 19)NOTE: PLEASE NOTE MISPRINT FOR #`S |
| | FOR CIRCUITS FROM EDP-1 TO ELEV #1 SHOWN |
| | ON ONE-LINE. |
| | |
| | 20)NOTE: PLEASE NOTE KEYNNOTES ON TOP |
| | OF SHEET E-207. |
| | #7- SHOWS 6000MCM? |
| | #9- SHOWS 650MCM? |
| | #9 AND #10 ARE MISSING FROM ONE-LINE ALL |
| | TOGETHER. |
| | |
| | 21)NOTE: PLEASE NOTE EDP-1 SHOWS ONE |
| | PUMP AT 30HP W/ 100A OCP AND #8? PLEASE |
| | CORRELATE W/ OTHER PUMP SHOWN. |
| | |
| | 22)NOTE: PLEASE VERIFY OR NOTE OCP FOR |
| | FIRE PUMP PER 695-4-B-1. |
| | PLEASE SUBMIT INFORMATION IF PART OF |
| | A LISTED ASSEMBLY WITH BUILD IN LOCKED |
| | ROTOR SETTING. |
| | |
| | 23)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL EQUIPMENT INCLUDING ALL PANELS AND |
| | DISCONNECTS AFTER MAINS. IT IS NOTE THAT |
| | MAINS ARE SHOWN W/ 100,000 AND 65,000 |
| | RATINGS. 110-9/215-5 |
| | |
| | 24)NOTE: PLEASE SEE E209.2 PANEL "S" |
| | SHOWS CIRCUIT 19 WITH #14 ON A 50A BRKR? |
| | PLEASE CORRECT. |
| | |
| | 25)NOTE: PLEASE NOTE THAT EQUIPMENT |
| | GROUNDING CONDUCTORS ARE MISSING ON ONE- |
| | LINE AND PANEL SCHEDULES? PLEASE CLARIFY |
| | IF ALL CONDUITS ARE RIGID AND/OR EMT |
| | ABOVE GROUND/SLAB AND OVERHEAD. PLEASE |
| | NOTE IF ANY OF THESE CONDUITS SHOWN |
| | ARE INDEED PVC THEN PLEASE SHOW ALL |
| | EQUIPMENT GRNDS SIZED PER 250-122 AND |
| | PER 250-24. |
| | |
| | 26)NOTE: PLEASE NOTE THAT ON E-209 ALL |
| | FEEDERS TO PANELS ARE SHOWN AS A BLANK?? |
| | PLEASE SUBMIT CONDUIT AND CONDUCTOR |
| | SIZES. |
| | |
| | 27)NOTE: PLEASENOTE THAT MANY OF THE |
| | A/C UNIT KW RATINGS ARE MISSING ON PANEL |
| | SCHEDULES. PLEASE ALSO NOTE THAT SOME |
| | DO NOT CORRELATE W/ LOAD CALCULATIONS |
| | AT THE BOTTOM OF PANEL SCHEDULES. PLEASE |
| | NOTE SOME SHOWN AS 3970 AND 5740 ON THE |
| | SAME PANEL. PLEASE CORRLEATE. |
| | |
| | 28)NOTE: PLEASE CLARIFY LOAD SHOWN FOR |
| | A/C LAODS . SHOWN AS 5.3KW W/ 1/4 HP |
| | MOTOR AND OTHERS SHOWN AS 3.7KW W/ 1/6 |
| | MOTOR. PLEASE NOTE THAT DEMAND IS SHOWN |
| | HIGHER? PLEASE NOTE 746W PER HP. PLEASE |
| | CLARIFY WHERE THE EXTRA LOAD IS COMING |
| | FROM? A-5,A-4X,A-3X, ETC ETC. |
| | |
| | 29)NOTE: PLEASE CLARIFY LOAD STUDY #1 |
| | SHOWN ON E-208.1. PLEASE NOTE UNITS |
| | SE-1 AT 9 AND SE-2 AT 15 AND THEN ADDED |
| | TO TOTAL OF 84? PLEASE VERIFY. |
| | |
| | 30)NOTE: PLEASE SUBMIT ALL INFORMATION |
| | ON PANELS. PLEASE NOTE PANEL SHOWN WITH |
| | NO INFORMATION, SIZE, TYPE ETC. |
| | |
| | 31)NOTE: PLEASE NOTE AND CLARIFY THAT |
| | " ELECTRICAL NOTES" FOR ENTIRE PROJECT |
| | WERE NOT SUBMITTED FOR REVIEW. COLOR |
| | CODING OF CONDUCTORS, WIRE METHODS ETC |
| | ETC. |
| | |
| | 32)NOTE: PLEASE SHOW AND NOTE ALL REQ` |
| | -MENTS FOR FAIR HOUSING ACT REGULATIONS, |
| | 24 CFR 100.205. |
| | PLEASE NOTE ALL HEIGHTS/LOCATIONS FOR |
| | ALL DEVICES. |
| | |
| | 33)NOTE: PLEASE NOTE, PLEASE SEE ANY |
| | FIRE REVIEW COMMENTS THAT MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | 34)NOTE: PLEASE NOTE THAT MANY UNIT FOR |
| | TYPES DO NOT CORRELATE WITH UNITS FROM |
| | E-209 AND A.01. |
| | |
| | 35)NOTE: PLEASE ALSO NOTE THAT SQ FT FOR |
| | UNITS ON E209 ALSO DO NOT CORRELATE |
| | WITH MOST OF THE UNIT SHOWN ON A.01. |
| | PLEASE CLARIFY AND CORRELATE PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, OR |
| | IF A MEETING CAN BE SET UP TO GO OVER |
| | COMMENTS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |