Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-21 00:00:00***************** UNSAT *************
  
 PLEASE NOTE THAT PLANS ARE NOT COMPLETE
 ENOUGH FOR FULL REVIEW AND THERE MAY BE
 OTHER COMMENTS TO FOLLOW.
  
 1)NOTE: PLEASE NOTE THAT NO LIGHTING
 FIXTURE SCHEDULE WAS SUBMITTED FOR
 REVIEW AND TO CORRELATE WITH LIGHTING
 PLANS SUBMITTED.
  
 2)NOTE: PLEASE CLARIFY REQ`MENTS FOR
 700-16 FOR ELEVATOR RMS AND ANY OTHER
 AREAS THAT ONLY CONTAIN ONE FIXTURE FOR
 ILLUMINATION.
  
 3)NOTE: PLEASE NOTE THAT NOTE ON E-9.0
 MENTIONS TO SEE 1/4" SCALE ON,,,,PLEASE
 INDICATE WHER TO FIND ON PLAN. WHEN
 PLANS WERE REVIEW PAGE WAS FOUND, PLEASE
 NOTE PAGE ON E-9.
  
 4)NOTE: PLEASE NOTE E-9.1 SHOWS ELEC-
 -TRICAL PLAN FOR PIT BUT NOTHING SHOWN?
 PLEASE SHOW ANY LIGHTING/PUMP/GFI RECEPT
 THAT MAY BE REQ`D PER NEC.
  
 5)NOTE: PLEASE NOTE OUTLET SPACING IN
 MASTER BEDROOMS IN SOME UNITS FOR RECEPT
 -S WITHIN 6' OF DOOR. 210-52
  
 6)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO SHOWN AS
 GFI/GFI PROTECTED. PLEASE NOTE THAT THIS
 IS REQ`D OF ALL KITCHEN PENINSULARS AND
 ISLAND RECPETS. 210-8-A-6.
  
 7)NOTE: PLEASE NOTE SOME APT UNITS WITH
 SAME LAYOUT ARE SHOWN MORETHAN ONCE.
 PLEASE VERIFY .
  
 8)NOTE: PLEASE NOTE THAT ON 14.1 A NOTE
 BOX IS SET UP FOR CIRCUITING FOR
 CORRIDOR LIGHTING. PLEASE NOTE FOR OTHER
 CIRCUITING OF OTHER LTS ON OTHER FLOORS.
  
 9)NOTE: PLEASE SEE KEY NOTES SET FORTHON
 E 16.0 ETC NOTE #`S 3&4. PLEASE NOTE
 THOSE PARTICULAR NOTES ARE NOT SHOWN ON
 PLANS/SHEETS REFERENCED.
  
 10)NOTE: PLEASE NOTE THAT KEY NOTES ARE
 PLACED ON E205 THAT NEED TO BE ON E203,
 E201 IN ORDER TO CORRELATE W/ 207.
  
 11)NOTE: PLEASE NOTE; PER ART 230-70-A
 OF LOCAL AMENDMENTS. NO MORETHAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE THE BLDG.
 PLEASE NOTE FEEDS COMING INTO 5 OF 6 AND
 METERCENTER 4 OF 6.
  
 12)NOTE: PLEASE NOTE PANEL SCHEDULE FOR
 PKV SHOWS CIRCUIT TO POOL PANEL AS PANEL
 "DD".MISPRINT? PLEASE CORRECT.
  
 13)NOTE: PLEASE NOTE THAT 1600 EM MAIN
 IS SHOWN FEEDING PANEL PKV? PLEASE
 CLARIFY. PLEASE NOTE THAT EM MAIN IS
 ONLY SHOWN AS A DISCONNECT.
  
 14)NOTE: PLEASE SHOW A DETAIL OVERVIEW
 OF MAIN ELECTRICAL ROOM, GENERATOR RM
 FIRE PUMP ROOM. PLEASE ALSO NOTE ROOM
 SEPARATION ON ONE-LINE RISER DIAGRAM.
  
 15)NOTE: PLEASE PROVIDE NOTE FOR LABEL-
 -ING OF MAIN AND SERVICES FOR EQUIPMENT
 AND ON DOORS OF TWO MAIN ELECTRICAL
 ROOMS. 230-2-E
  
 16)NOTE: PLEASE NOTE THAT ONE-LINE SHOWS
 PANEL 1HA AS 2HA. MISPRINT? PLEASE
 CORRECT.
  
 17)NOTE: PLEASE NOTE THAT OCP AND WIRE
 SIZES NEED TO CORRELATE ON SHEETS FOR
 EDP-2 600A/#1, 500A/#4, 400A/#6 ETC.
 PLEASE SEE EDP-1 ALSO FOR CORRELATION
 OF OCP/WIRE.
  
 18)NOTE:PLEASE NOTE MISSING TECHNICAL
 INFORMATION FOR PANEL ECH. NOTHING SHOWN
  
 19)NOTE: PLEASE NOTE MISPRINT FOR #`S
 FOR CIRCUITS FROM EDP-1 TO ELEV #1 SHOWN
 ON ONE-LINE.
  
 20)NOTE: PLEASE NOTE KEYNNOTES ON TOP
 OF SHEET E-207.
 #7- SHOWS 6000MCM?
 #9- SHOWS 650MCM?
 #9 AND #10 ARE MISSING FROM ONE-LINE ALL
 TOGETHER.
  
 21)NOTE: PLEASE NOTE EDP-1 SHOWS ONE
 PUMP AT 30HP W/ 100A OCP AND #8? PLEASE
 CORRELATE W/ OTHER PUMP SHOWN.
  
 22)NOTE: PLEASE VERIFY OR NOTE OCP FOR
 FIRE PUMP PER 695-4-B-1.
 PLEASE SUBMIT INFORMATION IF PART OF
 A LISTED ASSEMBLY WITH BUILD IN LOCKED
 ROTOR SETTING.
  
 23)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT INCLUDING ALL PANELS AND
 DISCONNECTS AFTER MAINS. IT IS NOTE THAT
 MAINS ARE SHOWN W/ 100,000 AND 65,000
 RATINGS. 110-9/215-5
  
 24)NOTE: PLEASE SEE E209.2 PANEL "S"
 SHOWS CIRCUIT 19 WITH #14 ON A 50A BRKR?
 PLEASE CORRECT.
  
 25)NOTE: PLEASE NOTE THAT EQUIPMENT
 GROUNDING CONDUCTORS ARE MISSING ON ONE-
 LINE AND PANEL SCHEDULES? PLEASE CLARIFY
 IF ALL CONDUITS ARE RIGID AND/OR EMT
 ABOVE GROUND/SLAB AND OVERHEAD. PLEASE
 NOTE IF ANY OF THESE CONDUITS SHOWN
 ARE INDEED PVC THEN PLEASE SHOW ALL
 EQUIPMENT GRNDS SIZED PER 250-122 AND
 PER 250-24.
  
 26)NOTE: PLEASE NOTE THAT ON E-209 ALL
 FEEDERS TO PANELS ARE SHOWN AS A BLANK??
 PLEASE SUBMIT CONDUIT AND CONDUCTOR
 SIZES.
  
 27)NOTE: PLEASENOTE THAT MANY OF THE
 A/C UNIT KW RATINGS ARE MISSING ON PANEL
 SCHEDULES. PLEASE ALSO NOTE THAT SOME
 DO NOT CORRELATE W/ LOAD CALCULATIONS
 AT THE BOTTOM OF PANEL SCHEDULES. PLEASE
 NOTE SOME SHOWN AS 3970 AND 5740 ON THE
 SAME PANEL. PLEASE CORRLEATE.
  
 28)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 A/C LAODS . SHOWN AS 5.3KW W/ 1/4 HP
 MOTOR AND OTHERS SHOWN AS 3.7KW W/ 1/6
 MOTOR. PLEASE NOTE THAT DEMAND IS SHOWN
 HIGHER? PLEASE NOTE 746W PER HP. PLEASE
 CLARIFY WHERE THE EXTRA LOAD IS COMING
 FROM? A-5,A-4X,A-3X, ETC ETC.
  
 29)NOTE: PLEASE CLARIFY LOAD STUDY #1
 SHOWN ON E-208.1. PLEASE NOTE UNITS
 SE-1 AT 9 AND SE-2 AT 15 AND THEN ADDED
 TO TOTAL OF 84? PLEASE VERIFY.
  
 30)NOTE: PLEASE SUBMIT ALL INFORMATION
 ON PANELS. PLEASE NOTE PANEL SHOWN WITH
 NO INFORMATION, SIZE, TYPE ETC.
  
 31)NOTE: PLEASE NOTE AND CLARIFY THAT
 " ELECTRICAL NOTES" FOR ENTIRE PROJECT
 WERE NOT SUBMITTED FOR REVIEW. COLOR
 CODING OF CONDUCTORS, WIRE METHODS ETC
 ETC.
  
 32)NOTE: PLEASE SHOW AND NOTE ALL REQ`
 -MENTS FOR FAIR HOUSING ACT REGULATIONS,
 24 CFR 100.205.
 PLEASE NOTE ALL HEIGHTS/LOCATIONS FOR
 ALL DEVICES.
  
 33)NOTE: PLEASE NOTE, PLEASE SEE ANY
 FIRE REVIEW COMMENTS THAT MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 34)NOTE: PLEASE NOTE THAT MANY UNIT FOR
 TYPES DO NOT CORRELATE WITH UNITS FROM
 E-209 AND A.01.
  
 35)NOTE: PLEASE ALSO NOTE THAT SQ FT FOR
 UNITS ON E209 ALSO DO NOT CORRELATE
 WITH MOST OF THE UNIT SHOWN ON A.01.
 PLEASE CLARIFY AND CORRELATE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR
 IF A MEETING CAN BE SET UP TO GO OVER
 COMMENTS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372