Plan Review Notes
Plan Review Notes For Permit 02080563
Permit Number 02080563
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-16 00:00:00PLAN REVIEW ONLY, NOT A PERMIT
 APPLICATION.NO SPECIFICATONS WERE
 PROVIDED
  
 AT TIME OF PERMIT APPLICATION A RECENT
 PROPERTY SURVEY WILL BE REQUIRED.SHOW
 THE BUILDING ELEVAION MEASURED FROM THE
 LOWEST POINT OF FIRE DEPARTMENT VEHICLE
 ACCESS, (STREET), TO HIGHEST OCCUPIABLE
 FLOOR.IF MORE THAN 75' COMPLY WITH FBC
 412.
  
 THE MINIMUM CONSTRUCTION TYPE IS TYPE I
 FIRE SPRINKLERED.R2 OCCUPANCY.THE
 BUILDING WILL BE LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND MUST
 COMPLT WITH APPEDIX OF THE FBC AS
 AMENDED BY THE CITY OFWEST PALM BEACH.
  
 THIS WILL BE A THRESHOLD BUILDING AND
 WILL REQUIRE A THRESHOLD INSPECTION
 PLAN AND A THRESHOLD INSPECTOR.SEE
 FBC 105.13.
  
 SHEETS A65 AND A67 DEPICT SUSPENDED
 GYPSUM BOARD CEILINGS AND SOFFIT
 FRAMING.INCLUDE SPECIFIC CONNECTIONS
 IN THE DESIGN INCLUDING ATTACHMENT TO
 THE STRUCTURE ABOVE.
  
 THE PORTION OF THE BUILDING ON THE SOUTH
 ELEVATION, (TANGLEWOOD CT.) DOES NOT
 COMPLY WITH FBC TABLED 600 MEASURED 18'
 TO THE STREET CENTERLINE AS TO WALL
 FIRE RATING, (2HRS) AND ALLOWABLE
 PERCENTAGE OF EXTERIOR WALL OPENINGS.
 PLANS INDICATE 334 SF OF 300 SF
 ALLOWABLE AT THE FIRST FLOOR.THE UPPER
 FLOORS EXCEED THE ALLOWABLE BY A
 GREATER PERCENTAGE.
  
 THE FITNESS CENTER, FIFTH LEVEL, ON THE
 EAST ELEVATION INDICATES A TWELVE FEET
 SETBACK FROM AN INTERIOR PROPERTY LINE.
 THEREFORE THE EXTERIOR BEARING WALL IS
 REQUIRED TO BE 4 HR FIRE RATED AND IS
 LIMITED TO 20% PROTECTED OPENINGS.SEE
 FBC T-600 AND FBC 705.1.1.2.
  
 THE PARKING GARAGE WILL BE ENCLOSED AS
 PROVIDED FOR IN FBC 411.4.INDICATE
 THE WALLS, WHERE APPLICABLE, WILL
 COMPLY WITH FBC 411.2.3. (VEHICLE
 IMPACT RESISTANCE)
  
 SHEET LS-1 SHOWS INGRESS/EGESS FROM THE
 GARAGE ON THE EAST SIDE TO BE PARTIALLY
 ON THE ADJACENT PROPERTY.HOW IS THIS
 RESOLVED?
  
 SHOW THE VENTILATION REQUIRED BY FBC
 411.4.2.
  
 DETAIL K/A87, AND OTHERS, SHOW THE USE
 OF PLYWOOD FOR A STRUCTURAL COMPONENT
 WHICH IS PROHIBITTED IN TYPE I
 CONSTRUCTION
 SEE FBC 603.
  
 SECTION G A.86, AND OTHERS SHOW A 3/4"
 DEEP RECESS FOR THE EXTERIOR MASONRY
 WALLS.FBC 2111.1.9 AS AMENDED BY THE
 CITY REQUIRES 1 1/2".
  
 PARTITION TYPE 21 ON SHEET A92 DOES NOT
 AGREE WITH UL465 ASSEMBLY.
  
 THE SHAFT DETAIL ON LS-8 IS NOT
 PRACTICAL FOR UL505 DESIGN.
  
 PARTITION TYPE 7, UL907 REQUIRES
 ADDITIONAL DETAILS SINCE THE BLOCK IS A
 PROPRIETARY ONE.SAME FOR PARTITION
 TYPES 4, 4A & 4B.
  
 THE NOTE "FIRE SAFING AS REQUIRED" ON
 SHEET A92 AND ELSEWHERE, IS NOT A
 SUBSTITUTE FOR SPECIFIC DESIGN MATERIAL
 INFORMATION SEE FBC 104.2.1.
  
 THE EXTERIOR WALLS DO NOT INDICATE THEIR
 RESPECTIVE FIRE RATINGS IN ACCORDANCE
 WITH FBC T 600 FOR TYPE I CONSTRUCTION.
 INCLUDE THE FIRE DESIGN NUMBERS.
  
 WHERE IN THE BUILDING DO THE CORRIDOR
 SUPPLY RISERS DEPICTED ON SHEET A/C 200
 OCCUR?CONSTRUCTION DETAIL?
  
 STAIR #1 DOES NOT COMPLY WITH FBC
 1010.3EXCEPTION 1 AS DOES STAIR #3.
 FURTHER, ONLY 50% OF THE EXITS MAY USE
 THE EXCEPTION, NOT 2/3 (66%).
  
 SHOW THE METHODS OF PROTECTION OF
 PENTRATION OF FIRE RATED ASSEMBLIES.
 SEE FBC 705.4.
  
 SHOW HOW FBC 705.6 WILL BE COMPLIED WITH
  
 THE VARIOUS FOAM TRIM ITEMS SHOWN FOR
 USE ON THE EXTERIOR WALL MUST COMPLY
 WITH FBC 1404.1.1 AND (FBC F102.2.7
 AMENDMENT)NON COMBUSTIBLE MATERIAL.
  
 NOTE#21 ON SHEET S-01 SPEAKS TO
 PILINGS BUT THE PLANS DO NOT AGREE.
 PLEASE CLARIFY.
  
 THE NOTES ON S-O1 FOR THE POST TENSION
 #8 AND POST TENSION CONCRETE SLAB #1
 CONFLICT WITH EACH OTHER.PLEASE
 CLARIFY THE DESIGN INTENT.
  
 THE SECTIONS ON SHEET S34 ARE NOT
 NUMBERED PROPERLY.
  
 SHOW THE BUILDING ENVELOPE PRESSURES.
  
 SHOW A DETAIL FOR THE EMERGENCY OVERFLOW
 SCUPPER.SEE FBC 1511.6.1.4.3.
  
 FA SHEETS 9, 9.1, 9.2, AND 10, CALLED
 OUT THE TITLE SHEET AO ARE MISSING.
  
 FP SHEETS 120, 119, 118, 116, 8.0 ARE
 MISSING.SEE NFPA 13-99 CHAPTER 8 FOR
 THE REQUIRED FIRE SPRINKLER INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 PLEASE SEPARATE THE PLANS INTO SMALLER
 SECTIONS, IE BIND THE MEP SEPARATELY.
 THEY ARE OVERLY HEAVY AND UNWIELDLY IN
 THEIR PRESENT STATE.