| Date |
Text |
| 2002-08-16 00:00:00 | PLAN REVIEW ONLY, NOT A PERMIT |
| | APPLICATION.NO SPECIFICATONS WERE |
| | PROVIDED |
| | |
| | AT TIME OF PERMIT APPLICATION A RECENT |
| | PROPERTY SURVEY WILL BE REQUIRED.SHOW |
| | THE BUILDING ELEVAION MEASURED FROM THE |
| | LOWEST POINT OF FIRE DEPARTMENT VEHICLE |
| | ACCESS, (STREET), TO HIGHEST OCCUPIABLE |
| | FLOOR.IF MORE THAN 75' COMPLY WITH FBC |
| | 412. |
| | |
| | THE MINIMUM CONSTRUCTION TYPE IS TYPE I |
| | FIRE SPRINKLERED.R2 OCCUPANCY.THE |
| | BUILDING WILL BE LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT AND MUST |
| | COMPLT WITH APPEDIX OF THE FBC AS |
| | AMENDED BY THE CITY OFWEST PALM BEACH. |
| | |
| | THIS WILL BE A THRESHOLD BUILDING AND |
| | WILL REQUIRE A THRESHOLD INSPECTION |
| | PLAN AND A THRESHOLD INSPECTOR.SEE |
| | FBC 105.13. |
| | |
| | SHEETS A65 AND A67 DEPICT SUSPENDED |
| | GYPSUM BOARD CEILINGS AND SOFFIT |
| | FRAMING.INCLUDE SPECIFIC CONNECTIONS |
| | IN THE DESIGN INCLUDING ATTACHMENT TO |
| | THE STRUCTURE ABOVE. |
| | |
| | THE PORTION OF THE BUILDING ON THE SOUTH |
| | ELEVATION, (TANGLEWOOD CT.) DOES NOT |
| | COMPLY WITH FBC TABLED 600 MEASURED 18' |
| | TO THE STREET CENTERLINE AS TO WALL |
| | FIRE RATING, (2HRS) AND ALLOWABLE |
| | PERCENTAGE OF EXTERIOR WALL OPENINGS. |
| | PLANS INDICATE 334 SF OF 300 SF |
| | ALLOWABLE AT THE FIRST FLOOR.THE UPPER |
| | FLOORS EXCEED THE ALLOWABLE BY A |
| | GREATER PERCENTAGE. |
| | |
| | THE FITNESS CENTER, FIFTH LEVEL, ON THE |
| | EAST ELEVATION INDICATES A TWELVE FEET |
| | SETBACK FROM AN INTERIOR PROPERTY LINE. |
| | THEREFORE THE EXTERIOR BEARING WALL IS |
| | REQUIRED TO BE 4 HR FIRE RATED AND IS |
| | LIMITED TO 20% PROTECTED OPENINGS.SEE |
| | FBC T-600 AND FBC 705.1.1.2. |
| | |
| | THE PARKING GARAGE WILL BE ENCLOSED AS |
| | PROVIDED FOR IN FBC 411.4.INDICATE |
| | THE WALLS, WHERE APPLICABLE, WILL |
| | COMPLY WITH FBC 411.2.3. (VEHICLE |
| | IMPACT RESISTANCE) |
| | |
| | SHEET LS-1 SHOWS INGRESS/EGESS FROM THE |
| | GARAGE ON THE EAST SIDE TO BE PARTIALLY |
| | ON THE ADJACENT PROPERTY.HOW IS THIS |
| | RESOLVED? |
| | |
| | SHOW THE VENTILATION REQUIRED BY FBC |
| | 411.4.2. |
| | |
| | DETAIL K/A87, AND OTHERS, SHOW THE USE |
| | OF PLYWOOD FOR A STRUCTURAL COMPONENT |
| | WHICH IS PROHIBITTED IN TYPE I |
| | CONSTRUCTION |
| | SEE FBC 603. |
| | |
| | SECTION G A.86, AND OTHERS SHOW A 3/4" |
| | DEEP RECESS FOR THE EXTERIOR MASONRY |
| | WALLS.FBC 2111.1.9 AS AMENDED BY THE |
| | CITY REQUIRES 1 1/2". |
| | |
| | PARTITION TYPE 21 ON SHEET A92 DOES NOT |
| | AGREE WITH UL465 ASSEMBLY. |
| | |
| | THE SHAFT DETAIL ON LS-8 IS NOT |
| | PRACTICAL FOR UL505 DESIGN. |
| | |
| | PARTITION TYPE 7, UL907 REQUIRES |
| | ADDITIONAL DETAILS SINCE THE BLOCK IS A |
| | PROPRIETARY ONE.SAME FOR PARTITION |
| | TYPES 4, 4A & 4B. |
| | |
| | THE NOTE "FIRE SAFING AS REQUIRED" ON |
| | SHEET A92 AND ELSEWHERE, IS NOT A |
| | SUBSTITUTE FOR SPECIFIC DESIGN MATERIAL |
| | INFORMATION SEE FBC 104.2.1. |
| | |
| | THE EXTERIOR WALLS DO NOT INDICATE THEIR |
| | RESPECTIVE FIRE RATINGS IN ACCORDANCE |
| | WITH FBC T 600 FOR TYPE I CONSTRUCTION. |
| | INCLUDE THE FIRE DESIGN NUMBERS. |
| | |
| | WHERE IN THE BUILDING DO THE CORRIDOR |
| | SUPPLY RISERS DEPICTED ON SHEET A/C 200 |
| | OCCUR?CONSTRUCTION DETAIL? |
| | |
| | STAIR #1 DOES NOT COMPLY WITH FBC |
| | 1010.3EXCEPTION 1 AS DOES STAIR #3. |
| | FURTHER, ONLY 50% OF THE EXITS MAY USE |
| | THE EXCEPTION, NOT 2/3 (66%). |
| | |
| | SHOW THE METHODS OF PROTECTION OF |
| | PENTRATION OF FIRE RATED ASSEMBLIES. |
| | SEE FBC 705.4. |
| | |
| | SHOW HOW FBC 705.6 WILL BE COMPLIED WITH |
| | |
| | THE VARIOUS FOAM TRIM ITEMS SHOWN FOR |
| | USE ON THE EXTERIOR WALL MUST COMPLY |
| | WITH FBC 1404.1.1 AND (FBC F102.2.7 |
| | AMENDMENT)NON COMBUSTIBLE MATERIAL. |
| | |
| | NOTE#21 ON SHEET S-01 SPEAKS TO |
| | PILINGS BUT THE PLANS DO NOT AGREE. |
| | PLEASE CLARIFY. |
| | |
| | THE NOTES ON S-O1 FOR THE POST TENSION |
| | #8 AND POST TENSION CONCRETE SLAB #1 |
| | CONFLICT WITH EACH OTHER.PLEASE |
| | CLARIFY THE DESIGN INTENT. |
| | |
| | THE SECTIONS ON SHEET S34 ARE NOT |
| | NUMBERED PROPERLY. |
| | |
| | SHOW THE BUILDING ENVELOPE PRESSURES. |
| | |
| | SHOW A DETAIL FOR THE EMERGENCY OVERFLOW |
| | SCUPPER.SEE FBC 1511.6.1.4.3. |
| | |
| | FA SHEETS 9, 9.1, 9.2, AND 10, CALLED |
| | OUT THE TITLE SHEET AO ARE MISSING. |
| | |
| | FP SHEETS 120, 119, 118, 116, 8.0 ARE |
| | MISSING.SEE NFPA 13-99 CHAPTER 8 FOR |
| | THE REQUIRED FIRE SPRINKLER INFORMATION. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL (561) 233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | PLEASE SEPARATE THE PLANS INTO SMALLER |
| | SECTIONS, IE BIND THE MEP SEPARATELY. |
| | THEY ARE OVERLY HEAVY AND UNWIELDLY IN |
| | THEIR PRESENT STATE. |