| Plan Review Notes For Permit 02080497 |
| Permit Number |
02080497 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-STORM SHUTTERS: | | | A)DESIGN PRESSURES SPECIFIED ON THE INS- | | | TALLATION SCHEDULE HAVE LIMITATIONS ON | | | PANELS SPAN. SEE PLANS FOR DESIGN PRE- | | | SSURES CALCULATED BY THE ARCHITECT AND | | | REVISE SCHEDULE AS REQUIRED. ALSO, | | | CLARIFY TYPE OF ANCHOR USED, RAWL OR | | | CAULK-IN. | | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE & SPACING | | | TO BE USED. | | | 2-SPECIFY ANCHOR BOLT SIZE (LENGTH) AND | | | WASHER FOR GARAGE STRUCTURAL BUCK. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|