| Plan Review Notes For Permit 02080496 |
| Permit Number |
02080496 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-FLOOD ZONE A8. WILL NEED TO PROVIDE | | | THE ELEVATI0N CERTIFICATE. | | | 2-PROVIDE UL SPECS FOR 1 HR FIRE RATED | | | GLASS BLOCK ASSEMBLY AS REQUIRED BY | | | TABLE 600 FBC 2001. | | | **ALSO, PROVIDE LEGIBLE PRODUCT APPROVAL | | | AND DRAWINGS FOR GLASS BLOCK. | | | 3-PROVIDE SOIL TEST REPORT. | | | 4-STORM SHUTTERS: A)DESIGN PRESSURES | | | SPECIFIED ON INSTALLATION SCHEDULE | | | HAVE LIMITATIONS ON PANELS SPAN. SEE | | | CALCULATED DESIGN PRESSURES BY ARCH. | | | AND REVISE AS REQUIRED. ALSO, CLARIFY | | | WHICH ANCHOR USED RAWL OR CAULK-IN. | | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE & SPACING | | | TO BE USED. | | | 5-SECOND FLOOR FRAMING PLAN: SPECIFY | | | DRAFSTOPPING LOCATION AT AREAS NOT TO | | | EXCEED 500 SF. SEE SEC. 2305.2.2 FBC. | | | 6-SPECIFY SIZE OF ANCHOR BOLT AND WASHER | | | FOR GARAGE STRUCTURAL BUCK DETAIL. |
|