| Date |
Text |
| 2002-10-22 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS UNDER A SEPARATE |
| | PERMIT. NEED SITE SPECIFIC CONDITIONS |
| | USING THE CERTIFICATE OF COMPLIANCE |
| | METHOD AND INSTALLATION AFFIDAVIT. SEE |
| | CITY IMPLEMENTATION STANDARD FOR HURRI |
| | CANE MISSILE IMPACT PROTECTION. |
| | **SEE GENERAL NOTES ON PAGE 1 OF STORM |
| | SHUTTERS DRAWINGS FOR ADDITIONAL LIMI- |
| | TATIONS FOR THIS STORM SHUTTERS. |
| | 2-PROVIDE SOIL TEST REPORT. |
| | 3-FLOOD ZONE A8. NEED TO PROVIDE THE |
| | ELEVATION CERTIFICATE. |
| | 4-GLASS BLOCK: |
| | A)PRODUCT APPROVAL IS NOT LEGIBLE. |
| | B)PROVIDE COMPLETE UL SPECS FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY. |
| | C)REVISE GLASS BLOCK DETAIL TO MATCH ONE |
| | HOUR FIRE RATED ASSEMBLY. SEE UL SPECS |
| | D)PROVIDE INFORMATION STATING THE FACE |
| | THICKNESS OF GLASS. NEED SAFETY GLASS |
| | IF FACE THICKNESS IS LESS THAN 0.25". |
| | SEC. 2405.2.2 FBC 2001. |
| | 5-ENTRY DOOR PRODUCT APPROVAL REPORT IS |
| | MISSING SOME PAGES. RESUBMIT AS REQ'D. |
| | 6-PROVIDE ENGINEERED CALCULATIONS FOR 1" |
| | WASHER USED AT GARAGE STRUCTURAL BUCK. |
| | NOTE: CONSIDER WOOD USED & REDUCTION |
| | FACTOR FOR P.T. WOOD. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |